1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULApril 3, 20081SUBJECT 546OUTLINE OF INVESTIGATIONFORCONDUCTOR TERMINATION COMPOUNDSISSUE NUMBER: 1APRIL 3, 2008Summary of TopicsThis is the First Issue of the Outline of Investigation for Conduct
2、orTermination Compounds which documents the test program to beemployed for evaluating conductor termination compounds for use onsplice and termination connections of aluminum, copper-clad aluminumand copper conductors.The UL Foreword is no longer located within the UL Standard. For informationconcer
3、ning the use and application of the requirements contained in thisStandard, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2008 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAP
4、RIL 3, 2008SUBJECT 5462No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Units of Measurement .43 Undated References 4CONSTRUCTION4 Samples .44.1 Conductor termination compound .44.2 Wire 44.3
5、Connectors 5PERFORMANCE5 General 56 Stability of Conductor Termination Compound 67 Stability of Wire and Cable Connections 67.1 General .67.2 Step stress current cycling test .78 Compatibility With Different Types of Wire And Cable Insulation 78.1 General .78.2 Physical properties tests .88.3 High-v
6、oltage arc tracking-rate performance level or high voltage-low current-dry arcresistance performance level testing 89 Characterization Tests .89.1 General .89.2 Qualitative infrared analysis 99.3 Homogeneity testing 9MARKINGS10 General .9APRIL 3, 2008 SUBJECT 546 3UL COPYRIGHTED MATERIAL NOT AUTHORI
7、ZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 This outline describes tests for determining whether conductor termination compounds for use onsplice and termination connections of aluminum, copper-clad aluminum and copper conductors whereused to retard o
8、xidation at the conductor/connector interface do not have a deleterious effect on theconductor metal, insulation or equipment when used in accordance with the manufacturers installationinstructions. In Sections 9.1 9.3, this outline also describes analytical methods for characterizing aconductor ter
9、mination compound to provide a basis for identification and for comparison with productionlots to reveal compositional changes.1.2 This outline does not investigate other properties of conductor termination compounds such assolubility, flammability, and toxicity.2 Units of Measurement2.1 Values stat
10、ed without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.3 Undated References3.1 Any undated reference to a code or standard appearing in the requirements of this outline ofinvestigation shall be interpreted as referring to the latest edition of tha
11、t code or standard.CONSTRUCTION4 Samples4.1 Conductor termination compound4.1.1 Approximately 1 gallon (3.78 liters) of the conductor termination compound is required for use in thistest program. At least one of the containers shall be a 1 quart size.4.2 Wire4.2.1 Wire material from all four of the
12、wires described in Table 4.1 are to be used in the Stability of Wireand Cable Connections and Compatibility With Different Types of Wire And Cable Insulation sections ofthis outline. The wires for the testing performed shall comply with the appropriate requirements in theStandard for Thermoset-Insul
13、ated Wires and Cables, UL 44 and the Standard for Thermoplastic-InsulatedWires and Cables, UL 83.APRIL 3, 2008SUBJECT 5464UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 4.1WireWire Representing Insulation Operating/ElevatedTemperature R
14、ating (C)Type THHW or Type THW PVC (Polyvinyl Chloride) 60/100 (THW) 90/121 (THHW)Type THHN or Type THWN PVC insulation with a nylon jacket 90/121Type XHHW XL (Polyethylene) 90/121Type RHW with a CP outer surface orType RHH with a CP outer surfaceCP (Chlorsulfonated Polyethylene) 90/121RHW or RHH EP
15、 (Ethylene Propylene) 90/1214.3 Connectors4.3.1 The minimum number of connector specimens and specimen types for test are shown in the Table4.2.Table 4.2ConnectorsMinimum Number Of Specimens And Specimen Types For TestClause Test Number of specimens Specimen types6.2 Elevated Temperature 4 Screw-tig
16、htening terminal typehaving a clamping surfacewith parallel grooves7.2 Step Stress Current Cycling 4 1) crimp -type2) direct-bearing set screwtype3) saddle or bolted clamp typePERFORMANCE5 General5.1 The following are the tests employed in this program on both connector samples with conductortermina
17、tion compound and connector samples without conductor termination compound and for physicalproperties evaluation samples of various wire insulations with and without conductor terminationcompound to determine that the conductor termination compound:a) Maintains stable connection performance; andb) D
18、oes not adversely affect the physical properties of the conductor insulationAPRIL 3, 2008 SUBJECT 546 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL6 Stability of Conductor Termination Compound6.1 Resistance to flow at elevated and low temp
19、erature testing shall be used to evaluate the stability ofthe conductor termination compound.6.2 Elevated Temperature Testing: The grooves of a mechanical connector with a parallel grooveclamping surface are to be filled fully with the conductor termination compound. The clamping screw is tobe tight
20、ened and excess conductor termination compound removed from the outer surfaces of the clamps.The clamp is to be mounted with one end of each groove pointed down at an angle of 45 degrees to thehorizontal in an oven at a temperature equal to the maximum temperature at which the conductortermination c
21、ompound is to be used, for a period of six hours. There shall be no evidence of conductortermination compound dripping out of the clamp when paper located below the clamp is examined.6.3 Low Temperature Testing: A short length, 6 to 9 inches (152 to 229 mm) of Nos. 12, 10 or 8 AWGsolid aluminum cond
22、uctor shall be coated with a layer of the conductor termination compound. Thethickness shall be approximately the same as would be used in an actual connection. The coated samplesis then to be placed in a cold box, at the lowest temperature for a period of 24 hours. The samples shallthen be removed
23、one at a time, and bent 90 degrees around a mandrel having a radius equal to six timesthe overall diameter of the test conductor. There shall be no evidence of cracks forming in the conductortermination compound coating.7 Stability of Wire and Cable Connections7.1 General7.1.1 A step stress current
24、cycling test is used to evaluate the stability of wire and cable connectionsusing the conductor termination compound. The samples tested are to include those provided with theconductor termination compound under investigation and identical samples without the conductortermination compound. The effec
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT5462008OUTLINEOFINVESTIGATIONFORCONDUCTORTERMINATIONCOMPOUNDSISSUE1 导线 端接 符合 材料 调查 大纲 发布 编号

链接地址:http://www.mydoc123.com/p-1069456.html