UL SUBJECT 199E-2004 OUTLINE OF INVESTIGATION FOR FIRE TESTING OF SPRINKLERS AND WATER SPRAY NOZZLES FOR PROTECTION OF DEEP FAT FRYERS (Issue 1)《深油煎锅保护用洒水器和喷水嘴耐火试验的调查大纲 发布编号 1》.pdf
《UL SUBJECT 199E-2004 OUTLINE OF INVESTIGATION FOR FIRE TESTING OF SPRINKLERS AND WATER SPRAY NOZZLES FOR PROTECTION OF DEEP FAT FRYERS (Issue 1)《深油煎锅保护用洒水器和喷水嘴耐火试验的调查大纲 发布编号 1》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 199E-2004 OUTLINE OF INVESTIGATION FOR FIRE TESTING OF SPRINKLERS AND WATER SPRAY NOZZLES FOR PROTECTION OF DEEP FAT FRYERS (Issue 1)《深油煎锅保护用洒水器和喷水嘴耐火试验的调查大纲 发布编号 1》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、May 6, 20041SUBJECT 199EOUTLINE OF INVESTIGATIONFORFIRE TESTING OF SPRINKLERS AND WATER SPRAY NOZZLES FORPROTECTION OF DEEP FAT FRYERSIssue Number: 1MAY 6, 2004Summary of TopicsThis first issue of the Subject 199E Outline of Investigation for FireTesting of Sprinklers and Water Spray Nozzles for Pro
2、tection of Deep FatFryers covers the performance during fire tests of automatic sprinklersand water spray nozzles used in restaurant cooking areas.The UL Foreword is no longer located within the UL Standard. For informationconcerning the use and application of the requirements contained in thisStand
3、ard, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2004 UNDERWRITERS LABORATORIES INC.MAY 6, 2004SUBJECT 199E2No Text on This PageCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .54 Undated References 55 Glossary .5PERFORMANCE6 General 57 Deep F
4、at Fryer Extinguishment Tests .68 Deep Fat Fryer Cooking Temperature Splash Test 7MAY 6, 2004 SUBJECT 199E 3INTRODUCTION1 Scope1.1 These requirements cover the performance during fire tests of automatic sprinklers and water spraynozzles intended for the protection of deep fat fryer cooking equipment
5、 used in restaurant cooking areas,which are intended to be installed in accordance with the Standard for Installation of Sprinklers, NFPA 13.1.2 Spray nozzles are also required to comply with the requirements for the Standard for Spray NozzlesFire Protection Service, UL 2351.1.3 Sprinklers are also
6、required to comply with the requirements for the Standard for Automatic Sprinklersfor Fire Protection Service, UL 199.1.4 The term product as used in these requirements refers to all spray nozzles and sprinklers or anypart thereof covered by these requirements unless specifically noted otherwise.1.5
7、 Where the term “spray nozzle” is referenced herein the requirements also apply to sprinklers.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component.2.2 A component need not comply with a spec
8、ific requirement that:a) Involves a feature or characteristic not needed in the application of the component in theproduct covered by this Outline of Investigation; orb) Is superseded by a requirement in this Outline of Investigation.2.3 A component shall be used in accordance with its rating establ
9、ished for the intended conditions ofuse.2.4 Specific components are incomplete in construction features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only und
10、er those specific conditions.MAY 6, 2004SUBJECT 199E43 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of t
11、his standard shall beinterpreted as referring to the latest edition of that code or standard.5 Glossary5.1 For the purpose of these requirements, the following definitions apply.5.2 AUTOMATIC FIXED SPRAY NOZZLE A water spray nozzle intended to open automatically byoperation of a heat responsive elem
12、ent that maintains the discharge orifice closed by means such asthe exertion of pressure on a cap (button or disc).5.3 DEEP FAT FRYER A cooking device that has a surface of liquid grease or one in which greaseis involved. The protected area is limited to the cooking surfaces of the appliance only.5.
13、4 GREASE For test purposes grease is new vegetable shortening incorporating an antifoamingagent.5.5 HEAT RESPONSIVE ELEMENT That portion of a spray nozzle that breaks, melts, or otherwisefunctions to initiate the automatic operation of the spray nozzle when exposed to sufficient heat.PERFORMANCE6 Ge
14、neral6.1 The deep fat fryer used is to be a commercially available natural gas or propane fired deep fat fryer,at least 9 inches (229 mm) deep, and having a cooking surface area as specified in the manufacturersinstallation instructions. For a deep fat fryer with an integral drip board, or similar i
15、tem, the calculatedcooking area, along with the drip area, is to be as indicated in the manufacturers installation instructions.6.2 The length and width of the cooking area of the appliance being tested are to correspond to themaximum area coverage limitation specified in the installation instructio
16、ns.6.3 Multiple fryer protection for single discharge nozzle coverage is to be tested in accordance with themanufacturers installation instructions.6.4 A larger appliance shall not be protected with multiple nozzles.6.5 Each deep fat fryer test is to be conducted in an environment in which the ambie
17、nt temperature is notless than 50F (10C).MAY 6, 2004 SUBJECT 199E 57 Deep Fat Fryer Extinguishment Tests7.1 When tested in accordance with 7.2 7.11, a spray nozzle shall:a) Contain the flame to a lateral distance not greater than 18 inches (457 mm) from any edgeof the protected area of the deep fat
18、fryer during discharge of the water, during the first 5seconds of discharge. For a deep fat fryer with an integral drip board, or similar item, the lateraldistance is to be measured from the protected area or drip board as appropriate. Videotapingthe appliance from the front and side is an acceptabl
19、e method to determine compliance withthis requirement.Exception: Flames extending at a lateral distance not greater than 36 inches (914 mm) from anyedge of the fryer are acceptable provided that they do not exist for more than 1 second.b) Control the fire after the initial 5 seconds of discharge by
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT199E2004OUTLINEOFINVESTIGATIONFORFIRETESTINGOFSPRINKLERSANDWATERSPRAYNOZZLESFORPROTECTIONOFDEEPFATFRYERSISSUE1

链接地址:http://www.mydoc123.com/p-1069209.html