1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSeptember 20, 20131UL 1683Outline of Investigation for Electric Heating Products For Installation UnderFloor CoveringsISSUE NO: 2September 20, 2013Summary of TopicsThis is the second issue of the
2、 Outline of Investigation for ElectricHeating Products For Installation Under Floor Coverings, UL 1683. Wetlocation requirements are being added to the Outline.COPYRIGHT 2013 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSI
3、ON FROM ULSEPTEMBER 20, 2013UL 16832No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .62 Units of Measurement .83 References .84 Glossary .8CONSTRUCTION5 General .106 Enclosure .117 Flammability 1
4、57.1 Flexible heating products, heating cables, and cables with carrier .157.2 Rigid heating products with polymeric enclosures .167.3 Heating products directly in contact with carpet .168 Connectors 169 Supplemental Insulation, Insulating Bushings and Assembly Aids 1710 Current-Carrying Parts 1711
5、Non-Heating Leads .1712 Free Non-Heating Leads .1813 Heating Leads 1814 Splices and Connections 1915 Electrical Insulation .1916 Electrical Spacings 1917 Grounding .2017.1 All products 2017.2 Heating cables .2118 Accessories 22PERFORMANCEALL HEATING PRODUCTS19 General 2220 Test Voltage .2421 Normal
6、Temperature Test 2621.1 General .2621.2 Wood subfloor installation .3021.3 Concrete subfloor installation 3021.4 Installation .3021.5 Test procedure .30ELECTRIC HEATING CABLES (INCLUDES CABLES ON A CARRIER)22 Power Input Test .3423 Dielectric Voltage-Withstand Test .3424 Insulation Resistance Test .
7、3425 Splice Test .3526 Grounding Component Ampacity Test 35SEPTEMBER 20, 2013 UL 1683 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULALL ELECTRIC HEATING PANELS AND HEATING PANEL SETS (INCLUDES FLEXIBLE FILM-TYPEAND RIGID PANELS)27 Power Inp
8、ut Test .3628 Contact Loss Test 36FLEXIBLE HEATING PANELS AND HEATING PANEL SETS (FILM-TYPE HEATERS)29 Dielectric Voltage-Withstand Test (Dry) 3730 Dielectric Voltage-Withstand Test (In Water) .3831 Cold Bend Test .3832 Mechanical Abuse Tests 3932.1 General .3932.2 Conditioning .3933 Scratch Test .4
9、034 Non-heating Conductor (Busbar) Overload Test 40RIGID HEATING PANELS AND HEATING PANEL SETS35 Dielectric Voltage-Withstand Test (Dry) 4136 Dielectric Voltage-Withstand Test (Water) 4137 Impact Bend Test .4138 Drop Test .42EMBEDDED HEATING PRODUCTS39 General 4240 Performance .42ELECTRIC HEATING PR
10、ODUCTS TO BE INSTALLED UNDER OR IN DECORATIVE CONCRETEFLOORING41 General 4242 Performance .43ELECTRICAL HEATING PRODUCTS TO BE INSTALLED IN DIRECT CONTACT WITH SOLIDSURFACE FLOOR COVERING (INCLUDES NON-EMBEDDED INSTALLATION UNDER TILE,LAMINATE, HARDWOOD)43 General 4344 Performance .43ELECTRIC HEATIN
11、G PRODUCTS TO BE INSTALLED IN DIRECT CONTACT WITH CARPET45 General 4346 Performance .4347 Overvoltage Test .4448 Continuous Static Loading Test .4449 Spot Load Temperature Test .4450 Impact Test 4451 Crush Test .4452 Cold Bend Test .4553 Cold Crease Test .45SEPTEMBER 20, 2013UL 16834UL COPYRIGHTED M
12、ATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL54 DC Resistance Test .4555 Mechanical Strength Test 4656 Immersion Test .4657 Penetration Test 4658 Connections Test 4659 Flame Retardant Tests 4660 Aging Test and Dielectric Voltage-Withstand Test (In Water) .
13、4761 Dynamic Loading Test .47WET LOCATION HEATING EQUIPMENT - HEATING CABLE BASED CONSTRUCTION62 General 4763 Performance .4763.1 Dielectric voltage-withstand test in water (complete assembly) .4763.2 Long-term insulation resistance in water test (heating cable and non-heating cables) .4863.3 Long-t
14、erm resistance to water test (complete assembly) 4863.4 Resistance to water test (complete assembly) .4964 Markings .4965 Instructions 49MANUFACTURING AND PRODUCT TESTS - ALL PRODUCTS66 Details .49RATINGS - ALL PRODUCTS67 Details .51MARKINGS - ALL PRODUCTS68 Details .5168.1 General .5168.2 Electric
15、Heating Cables and Cables on Carrier .5268.3 Electric heating panels 52INSTALLATION AND OPERATING INSTRUCTIONS - ALL PRODUCTS69 Details .54SEPTEMBER 20, 2013 UL 1683 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These
16、 requirements cover fixed electric heating products for installation under floor coverings andabove a subfloor, in accordance with the National Electrical Code, NFPA 70, Article 424, for use onsystem voltages not exceeding 600 V.1.2 These requirements cover electric heating products of the type spec
17、ified in 1.3, only when installedper 1.4.1.3 These requirements cover the following product types:a) Electric heating cables and cables on carriers;b) Flexible and rigid electric heating panels, mats, and heating panel sets;c) Electric flexible heating products, including carbon film-type constructi
18、ons; andd) Any combination of the above.1.4 These requirements cover one or more of the following installation types:a) Above a subfloor, the subfloor being constructed of wood, concrete, or other material;b) Directly underneath a floor covering such as tile, carpet, wood, laminate, sheet vinyl,deco
19、rative concrete, or other floor covering;c) Embedded in and covered with a layer of thinset, mortar, or the like under a floor covering;d) Not embedded, and in direct contact with combustible or combustion resistant materialsubfloor or floor covering, except as noted in 1.7(j);e) In dry or damp loca
20、tions per the National Electrical Code, NFPA 70; andf) Any combination of the above.1.5 These requirements do not cover electric space, floor, or ceiling heating products that are fullyaddressed by individual requirements that are separate from this Outline, including:a) Electric heating cables that
21、 are within the scope of the Standard for Electric Space HeatingCables, UL 1673; andb) Electric heating panels and heating panel sets that are within the scope of the Standard forElectric Heating Panels and Heating Panel Sets, UL 1693.SEPTEMBER 20, 2013UL 16836UL COPYRIGHTED MATERIAL NOT AUTHORIZED
22、FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL1.6 These requirements do not cover electric heating products that are covered by individualrequirements that are separate from this Outline. Other related standards include:a) Electrical Resistance Heat Tracing for Commercial and Ind
23、ustrial Applications, UL 515;b) Movable and Wall- or Ceiling-Hung Electric Room Heaters, UL 1278;c) Outline of Investigation for Mobile Home Pipe Heating Cables, UL 1462;d) Outline of Investigation for Roof and Gutter De-Icing Cable Units, UL 1588;e) Outline of Investigation for Residential Pipe Hea
24、ting Cables, UL 2049;f) Fixed and Location-Dedicated Electric Room Heaters, UL 2021; andg) Electric Heating Appliances, UL 499.1.7 These requirements do not cover the following:a) Heating products connected to the supply by use of a flexible cord with attachment plug;b) Heating products that are mov
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT16832013OUTLINEOFINVESTIGATIONFORELECTRICHEATINGPRODUCTSFORINSTALLATIONUNDERFLOORCOVERINGSISSUE2PDF

链接地址:http://www.mydoc123.com/p-1069187.html