UL SUBJECT 1630-1999 Outline of Investigation for Residential Hose Cabinets (Issue 3)《住宅消防栓箱的调查大纲 发布编号 3》.pdf
《UL SUBJECT 1630-1999 Outline of Investigation for Residential Hose Cabinets (Issue 3)《住宅消防栓箱的调查大纲 发布编号 3》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 1630-1999 Outline of Investigation for Residential Hose Cabinets (Issue 3)《住宅消防栓箱的调查大纲 发布编号 3》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、March 24, 1999 1 Subject 1630 OUTLINE OF INVESTIGATION FOR RESIDENTIAL HOSE CABINETS Issue Number: 3 MARCH 24,1999 COPYRIGHT Q 1989,1999 UNDERWRITERS LABORATORIES INC. No Text on This Page CONTENTS FOREWORD 4 INTRODUCTION 1 Scope . 5 2 Glossary . 5 3 General 5 CONSTRUCTION 4 General 6 5 Installation
2、 . 6 6 Materials . 6 7 Pipe Connections . 6 8 Cabinet 6 PERFORMANCE 9 Installation and Operation Test . 7 10 Nozzle Range Test . 7 11 Leakage Test 7 12 Hydrostatic Strength Test . 7 13 Pull Strength Test 7 14 Cold Resistance Test . 8 15 Accelerated Aging Test . 8 16 Water Immersion Test 8 17 Adhesio
3、n Tests 8 17.1 General 8 17.2 Cover 8 17.4 Test Procedure . 9 1 7.3 Specimens . 9 MANUFACTURING AND PRODUCTION TESTS 18 Production-Line Hydrostatic Pressure Test 9 MARKING 19 Details . 10 4 SUBJECT 1630 MARCH 24,1999 FOREWORD A. This Outline of Investigation contains basic requirements for products
4、covered by Underwriters Laboratories Inc. (UL) under its Follow-Up Service for this category within the limitations given below and in the Scope section of this Outline of Investigation. They are subject to revision as further experience and investigation may show is necessary or desirable. B. The o
5、bservance of these requirements by a manufacturer is one of the conditions of the continued coverage of the manufacturers product. C. A product which complies with the text of this Outline of Investigation will not necessarily be judged to comply with the Outline of Investigation if, when examined a
6、nd tested, it is found to have other features which impair the level of safety contemplated by these requirements. D. A product employing materials or having forms of construction which conflict with specific requirements of the Outline of Investigation cannot be judged to comply with the Outline of
7、 Investigation. A product employing materials or having forms of construction not addressed by this Outline of Investigation may be examined and tested according to the intent of the requirements and, if found to meet the intent of this Outline of Investigation, may be judged to comply with the Outl
8、ine of Investigation. E. UL, in performing its functions in accordance with its objectives, does not assume or undertake to discharge any responsibility of the manufacturer or any other party. The opinions and findings of UL represent its professional judgement given with due consideration to the ne
9、cessary limitations of practical operation and state of the art at the time.the Outline of Investigation is processed. UL shall not be responsible to anyone for the use of or reliance upon this Outline of Investigation by anyone. UL shall not incur any obligation or liability for damages, including
10、consequential damages, arising out of or in connection with the use, interpretation of, or reliance upon this Outline of Investigation. F. Many tests required by the Outline of Investigations of UL are inherently hazardous and adequate safeguards for personnel and property shall be employed in condu
11、cting such tests. STD LJL SUBJECT Lb3lJ-ENGL Lril ri275?95 118455i1b 78q = MARCH 24,1999 SUBJECT 1630 5 INTRODUCTION 1 Scope 1.1 These requirements cover residential hose cabinets that are intended for installation, by connection to domestic water supplies, in single family dwellings, mobile homes,
12、and apartments for use in controlling incipient fires by the occupants within the dwelling. 1.2 Residential hose cabinets are not intended to replace the Class II or Class III service as described by the Standard for Standpipe Hose Systems, NFPA 14. 1.3 These requirements cover residential hose cabi
13、nets using fire hose having a 3/4-, 7/8-, or 1 -inch (19.1-, 22.2-, or 25.4-mm) inside diameter in lengths of not more than 100 feet (30 m) and shut-off type nozzles intended for operation at pressures not exceeding the marked rating of the device. 1.4 A product that contains features, characteristi
14、cs, components, materials, or systems new or different from those covered by the requirements in this Outline of Investigation, and that involves a risk of fire, electric shock, or injury to persons, shall be evaluated using the appropriate additional component and end-product requirements as determ
15、ined necessary to maintain the acceptable level of safety as originally anticipated by the intent of this Outline of Investigation. A product whose features, characteristics, components, materials, or systems conflict with specific requirements or provisions of this Outline of Investigation cannot b
16、e judged to comply with this Outline of Investigation. Where considered appropriate, revision of requirements shall be proposed and adopted in conformance with the methods employed for development, revisions, and implementation of this Outline of Investigation. 2 Glossary 2.1 For the purposes of the
17、se requirements, the following definitions apply. 2.2 SERVICE PRESSURE - The static outlet pressure in psig (kPa) of the piping to which the residential hose cabinet is connected. 2.3 WORKING PRESSURE - The flowing pressure in psig (kPa) available at the nozzle end of the hose. 3 General 3.1 If a va
18、lue for measurement is followed by a value in other units in parentheses, the second value may be only approximate. The first stated value is the requirement. 3.2 A component of a product covered by these requirements shall comply with the requirements for that component and shall be used in accorda
19、nce with its recognized rating and other limitations of use. A component need not comply with a specific requirement that: a) Involves a feature or characteristic not needed in the application of the component in a product covered by these requirements, or b) Is superseded by these requirements. MAR
20、CH 24,1999 6 SUBJECT 1630 3.3 A component shall be used in accordance with its recognized rating established for the intended conditions of use. 3.4 Specific components are- recognized as being incomplete in construction features or restricted in performance capabilities. Such components are intende
21、d for use only under limited conditions, such as certain temperatures not exceeding specified limits, and shall be used only under those specific conditions for which they have been recognized. CONSTRUCTION 4 General 4.1 A cabinet shall be constructed for operation at the rated service pressure. 5 I
22、nstallation 5.1 A cabinet shall be constructed to permit direct installation through the use of ordinary tools, such as drills, saws, wrenches, and screwdrivers, or through tools supplied with the device. See Installation and Operation Test, Section 9. 5.2 The means for mounting and support of a cab
23、inet shall be independent of the hose rack and piping connections. 6 Materials 6.1 The materials used in the construction of those parts of a cabinet that are stressed after assembly shall be resistant to stress corrosion. 7 Pipe Connections 7.1 An inlet provided for the installation of a cabinet sh
24、all be threaded or tapped with taper threads in accordance with the Standard for Pipe Threads, General Purpose (Inch), ANSUASME Bl.20.1-1983(R1992), or shall be capable of being soldered. 8 Cabinet 8.1 A cabinet shall be of a size to permit full and ready access to all operating components and shall
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT16301999OUTLINEOFINVESTIGATIONFORRESIDENTIALHOSECABINETSISSUE3 住宅 消防栓 调查 大纲 发布 编号 PDF

链接地址:http://www.mydoc123.com/p-1069184.html