1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULDECEMBER 28, 20151UL 1551Outline of Investigation for Sprinkler Systems WireIssue Number: 1December 28, 2015Summary of TopicsThis first issue of the Outline of Investigation for Sprinkler Systems
2、 Wire,UL 1551, covers the construction and performance requirements forsprinkler systems wire intended for direct burial service for satellitesolenoid control on golf courses and lawns, terminated to Type UF or USEcable.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectr
3、onic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2015 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTE
4、D MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULDECEMBER 28, 2015UL 15512No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Units of Measurement .43 U
5、ndated References 4CONSTRUCTION4 Conductor 45 Insulation 56 Conductor Assembly 57 Shields 68 Jacket .6PERFORMANCE9 Tests 7MARKINGS10 Cable Markings 811 Tag Marking .912 Date of Manufacture .9DECEMBER 28, 2015 UL 1551 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WIT
6、HOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These cables are rated 300, or 600v, 60C (140F) or 75C (167F). The insulated-conductor sizesare 30V 22 14 AWG, 150 300V 20 8 AWG, 600V 18 2 AWG and single conductor 300V or 600V18 2 AWG solid or stranded copper.1.2 This outline covers the construction an
7、d performance requirements for sprinkler systems wireintended for direct burial service for satellite solenoid control on golf courses and lawns, terminated toType UF or USE cable.1.3 A product that contains features, characteristics, components, materials, or systems new or differentfrom those cove
8、red by the requirements in this Outline of Investigation, and that involves a risk of fire,electric shock, or injury to persons shall be evaluated using the appropriate additional component andend-product requirements to maintain the level of safety as originally anticipated by the intent of thisOut
9、line of Investigation. A product whose features, characteristics, components, materials, or systemsconflict with specific requirements or provisions of this Outline of Investigation does not comply with thisOutline of Investigation Revision of requirements shall be proposed and adopted in conformanc
10、e with themethods employed for development, revision, and implementation of this Outline of Investigation.2 Units of Measurement2.1 Values stated without parentheses are the requirements. Values in parentheses are explanatory orapproximate information.3 Undated References3.1 Any undated reference to
11、 a code or standard appearing in the requirements of this Outline ofInvestigation shall be interpreted as referring to the latest edition of that code or standard.CONSTRUCTION4 Conductor4.1 Anealed solid of stranded copper, bare or coated, in size 22 2 AWG.DECEMBER 28, 2015UL 15514UL COPYRIGHTED MAT
12、ERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5 Insulation5.1 Conductors shall be insulated with LDPE, HDPE, or PVC (compounds for Types TW, THW, orTHWN) using a wet-locations insulating compound rated for at least 60C (167F).5.2 Insulated conductors other th
13、an those described in 5.1 shall have materials in thicknesses describedin Table 5.1 and with temperature ratings appropriate for the specific construction of the sprinkler systemswire in which they are to be used. The materials shall be evaluated for the requested temperature ratingas described in L
14、ong-Term Aging Section of the Reference Standard for Electric Wires, Cables, andFlexible Cords, UL 1581. Investigation of the electrical, mechanical, and physical characteristics of theseinsulated conductors shall show these conductors to be comparable to the conductors described in 5.1.The investig
15、ation shall include tests such as crushing, impact, deformation, heat shock, and cold bend.Table 5.1Minimum thickness of insulationRating AWG SizeMinimum Average Thickness Minimum Thickness at Any Pointmils mm mils mm30V 22 14 15 0.38 13 0.33150 or 300V 20 8 25 0.64 22 0.56600V 18 8 45 1.14 40 1.026
16、 2 60 1.52 54 1.37300 or 600V (singleconductor)18 8 45 1.14 40 1.026 2 60 1.52 54 1.376 Conductor Assembly6.1 Cable may be a single conductor without a jacket or a multiple conductor cable with an overall jacket.Conductors of different sizes may be used in the same cable. The insulated conductors sh
17、all be cabled.The length of lay is not specified. The cables shall be provided with fillers where needed to make thefinished cable round.6.2 The assembly may be enclosed in a nonmetallic braid, tape, or wrap.DECEMBER 28, 2015 UL 1551 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION O
18、RDISTRIBUTION WITHOUT PERMISSION FROM UL7 Shields7.1 A shield is not required but is acceptable over an individual insulated conductor, over a pair ofinsulated conductors, over one or several groups of insulated conductors in any group, or over the entirecable assembly. Several shields may be used i
19、n a given cable.7.2 A shield shall be of metal and shall consist of one or more of the following:a) A laminated shield tape of polymeric material and metal(s) with or without a bare metal-coated or uncoated (uncoated not acceptable with an aluminum-faced tape) copper drain wire incontact with the me
20、tal(s) part of the tape. The tape may be applied with the metal(s) side in orout. The size of a drain wire is not specified. A drain wire may be solid or stranded.b) A corrugated or smooth single-metal or bi-metal tape applied longitudinally, helically, orinterlocked with or without a bare metal-coa
21、ted or uncoated (uncoated not acceptable with analuminum tape) copper drain wire in contact with the metal. The tape may be polymer-coatedon one side if there is a drain wire or on both sides if a drain wire is not used. Any inward-facing coating may bond to the insulation but, where the metal tape
22、is applied over more thanone conductor or member, any inward-facing coating shall not bond to the conductors in thecable. The size of a drain wire is not specified. A drain wire may be solid or stranded.Interlocked aluminum tape shall comply with the requirements for a metal covering but, if thecabl
23、e has an overall cable jacket, the strip thickness and width are not specified.c) A serving, wrap, or braid of aluminum wires or metal-coated or uncoated (uncoated notacceptable in contact with aluminum wires) copper wires.8 Jacket8.1 A jacket of LDPE, HDPE, or PVC (Class 43), and of the thicknesses
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT15512015ULOUTLINEFORINVESTIGATIONSPRINKLERSYSTEMSWIREISSUE1PDF

链接地址:http://www.mydoc123.com/p-1069180.html