UL 20 CRD-2014 UL Standard for Safety General-Use Snap Switches - Section Paragraph Reference New Supplement SA Subject AC Only Flush Switch with Integral Power Supply with Class .pdf
《UL 20 CRD-2014 UL Standard for Safety General-Use Snap Switches - Section Paragraph Reference New Supplement SA Subject AC Only Flush Switch with Integral Power Supply with Class .pdf》由会员分享,可在线阅读,更多相关《UL 20 CRD-2014 UL Standard for Safety General-Use Snap Switches - Section Paragraph Reference New Supplement SA Subject AC Only Flush Switch with Integral Power Supply with Class .pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): WMUZStandard Number: UL 20Standard Title: Standard for General-Use Snap SwitchesEdition Date: May 10, 2010Edition Number: 13Section / Paragraph Reference: Ne
3、w Supplement SASubject: AC Only Flush Switch with Integral Power Supply with Class 2 OutputConnectorsDECISION:SUPPLEMENT SA AC ONLY FLUSH SWITCH WITH INTERGAL POWER SUPPLY WITH CLASS 2OUTPUT CONNECTORSINTRODUCTIONSA1 ScopeSA1.1 The requirements of this supplement cover an AC Only flush switch with i
4、ntegral power supply withone or more Class 2 output low-voltage connectors, intended to be installed in an outlet box.SA1.2 These requirements are applicable to an AC only flush-type switch rated 120 V AC only.SA1.3 An AC Only flush switch with integral power supply with one or more Class 2 output l
5、ow-voltageconnectors is intended only for flush installation in an appropriate enclosure suitable for the application.SA1.4 An AC Only flush switch with integral power supply with one or more Class 2 output low-voltageconnectors shall comply with the applicable requirements of this standard, UL 20,
6、except as modified bythe requirements in this supplement.SA1.5 This supplement does not apply to the enclosure or any part, which forms the enclosure, includingthe outlet box, flush device cover plate or both.SA1.6 This supplement only applies to an AC Only Flush switch with an integral power supply
7、 with Class2 output low voltage connectors. It does not apply to a flush switch and separable Class 2 power supplyor where the Class 2 power supply is either located or derived outside the outlet box.SA2 GlossarySA2.1 For the purpose of this supplement, the following definitions apply.SA2.2 AC ONLY
8、FLUSH SWITCH WITH INTEGRAL POWER SUPPLY WITH ONE OR MORE CLASS 2OUTPUT LOW-VOLTAGE CONNECTORS An AC Only Flush Switch, with an integral power supply andassociated Class 2 output low voltage connectors intended for flush mounting in or on an outlet box forfixed installation on a branch circuit.Constr
9、uctionUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSA3 GeneralSA3.1 In addition to the construction, performance and marking requirements contained in this standard,an AC Only flush switch with integral power supply with one or more Class 2
10、 output low-voltageconnectors shall also comply with the applicable requirements of UL 1310, the Standard for Class 2 PowerUnits.SA3.2 An AC Only flush switch with integral power supply with one or more Class 2 output low-voltageconnectors shall be provided with a suitable flush device cover plate o
11、r outlet box cover that complies withthe applicable requirements of the Standard for Cover Plates for Flush-Mounted Wiring Devices, UL 514D.Exception: An AC Only flush switch with integral power supply with one or more Class 2 outputlow-voltage connectors need not be provided with a cover plate or b
12、ox cover if all the following conditionsare met:a) The device is intended for use with a cover plate having dimensions that comply with WiringDevices - Dimensional Specifications, ANSI/NEMA WD6 for features intended to accommodatea flush-mounted wiring device of the dimensions specified in ANSI/NEMA
13、 WD6; andb) Markings specified in SA12.1 are visible after installation using a cover plate havingdimensions specified in (a); andc) No cover plate modifications are needed in order to comply with this Standard.SA3.3 The Class 2 low-voltage output connectors of an AC Only flush switch with integral
14、power supplyshall be insulated and extend beyond the plane of the receptacle mounting yoke.SA3.4 The Class 2 low-voltage power supply shall be configured for supply from a single branch circuit.SA4 Polymeric EnclosureSA4.1 In addition to the insulating material requirements of UL 20, Section 4.7, a
15、polymeric material usedto enclose the Class 2 power supply circuitry shall have a flame rating not less than 5V, or comply withthe 127 mm Flame Test specified in UL 746C (Polymeric Material - Use in Electrical EquipmentEvaluations).SA5 SpacingsSA5.1 In addition to the spacing requirements of UL 20,
16、Section 4.9, an AC Only flush switch with integralpower supply with one or more Class 2 output low-voltage connectors, shall also comply with the spacingsrequirements for the power supply circuitry of UL 1310, the Standard for Class 2 Power Units.SA5.2 An AC Only flush switch with integral power sup
17、ply with one or more Class 2 output low-voltageconnectors shall maintain a minimum of a 1/4 inch (6.35 mm) separation of branch circuit wiring and Class2 connections after installation. Compliance is checked my measurement and if necessary, assembly testas identified in Section SA9.SA5.3 An AC Only
18、flush switch with integral power supply with one or more Class 2 output low-voltageconnectors shall provide adequate spacings clearance of 3/64 inch (1.2 mm) between each terminal andthe metal of a standard outlet box of the minimum size in which it is intended to be installed. Complianceis checked
19、by assembly test as identified in Section SA9.SA6 Terminals and LeadsSTANDARD NUMBER: UL 20 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSA6.1 An AC Only flush switch with integral power supply with one or more Class 2 output low-voltage
20、connectors, shall be provided with a neutral terminal or lead as described in UL 20, Section 5.5.3 and shallalso be identified as described in UL 20, paragraphs 4.5.3.22 through 4.5.3.25.SA6.2 The neutral terminal or lead as identified in clause SA6.1 shall not be bonded to the groundingterminal or
21、dead-metal.SA6.3 Circuitry shall be arranged such that a grounding connection or conductor will not carry currentunder normal operating conditions.PERFORMANCESA7 Temperature TestSA7.1 A previously untested shall not attain a temperature at any point sufficiently high to constitute a riskof fire, to
22、damage any materials employed in the device, or to exceed the temperature rises specified inTable SA7.1.SA7.2 To determine if the AC Only flush switch with integral power supply with one or more Class 2 outputlow-voltage connectors complies with clause SA7.1, the device shall carry its maximum switc
23、h ratedcurrent and shall simultaneously draw the marked ampere rating through the low voltage outputconnectors either individually or collectively until constant temperatures are attained on the switchterminals or wire leads and identified components in Table SA7.1.SA7.3 The device shall be mounted
24、according to the manufacturers instructions and be tested in anon-metallic outlet box mounted in the test wall according to Figure SA7.1. If the device cannot physicallyfit in a box of 63 mm (2.5 in) depth and 75 mm (3 in) height, it shall be tested in a box identified in themanufacturers installati
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL20CRD2014ULSTANDARDFORSAFETYGENERALUSESNAPSWITCHESSECTIONPARAGRAPHREFERENCENEWSUPPLEMENTSASUBJECTACONLYFLUSHSWITCHWITHINTEGRALPOWERSUPPLYWITHCLASSPDF

链接地址:http://www.mydoc123.com/p-1067761.html