UL 120101-2017 UL Standard for Safety Definitions and Information Pertaining to Electrical Equipment in Hazardous Locations (COMMENTS DUE MAY 15 2017).pdf
《UL 120101-2017 UL Standard for Safety Definitions and Information Pertaining to Electrical Equipment in Hazardous Locations (COMMENTS DUE MAY 15 2017).pdf》由会员分享,可在线阅读,更多相关《UL 120101-2017 UL Standard for Safety Definitions and Information Pertaining to Electrical Equipment in Hazardous Locations (COMMENTS DUE MAY 15 2017).pdf(86页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSubject 120101March 31, 2017SUMMARY OF TOPICSThe following changes in requirements to the Standard for Safety for Definitions and InformationPertaining to Electrical Equipment in Hazardous Locati
2、ons, UL 120101, are being proposed forpreliminary review and comment only:1. For Preliminary Review Only: Proposed Second Edition of the Standard for Definitionsand Information Pertaining to Electrical Equipment in Hazardous Locations, UL 120101COMMENTS DUE: MAY 15, 2017This proposal is for review a
3、nd comment only (no ballot at this time). Please note that comments on apreliminary review document will not receive a response from the proposal author through CSDS.Instead, the proposal author will be asked to review the comments and adjust the proposals and/orsupporting rationale as the author de
4、termines to be appropriate. The preliminary review process is aninformal mechanism that provides authors with the opportunity to refine their proposals before theyadvance to the next stage in ULs standards development process.In some cases, the author of the proposals may choose to discontinue them.
5、 In this case, the authorneed not do anything after preliminary review has ended. Normally, the next step in the process is themore formal STP ballot and stakeholder review process. Only comments posted during the STP ballotand stakeholder review process will be provided with a response in CSDS.For
6、your convenience in review, proposed additions to existing requirements are shown underlined andproposed deletions are shown lined-out.1. For Preliminary Review Only: Proposed Second Edition of the Standard for Definitions andInformation Pertaining to Electrical Equipment in Hazardous Locations, UL
7、120101BACKGROUNDThis document was developed by ISA12 and is now being maintained by UL STP 60079.RATIONALEProposal submitted by: Brad Zimmermann, STP 60079 Chair on behalf of the TG79X-1R CommitteeMembersThis proposed new edition is to provide an update to the most recent information in the related
8、field.It is the proposal submitters opinion that this proposal affects the following topics/sections of theStandard: instruction requirement.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULPROPOSALMARCH 31, 2017SUBJECT 120101 -2-UL COPYRIGHTED
9、 MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL1 PurposeThis document provides definitions and information pertaining to protection techniques, terminology, andthe installation of electrical equipment in hazardous (classified) locations and provides an int
10、roduction andbasic background to the ISA 12, Electrical Safety, series of publications and committee activities. Itreplaces ANSI/ISA-12.01.01-2009, Definitions and Information Pertaining to Electrical Instruments inHazardous (Classified) Locations, published in 2009.This document provides a general
11、review of applicable codes and standards, and it should not be usedin lieu of those codes and standards for equipment design, manufacture, installation, maintenance andtest criteria.2 Scope2.1 This document provides general guidance for safe design, installation, and maintenance of electricalequipme
12、nt in hazardous (classified) locations using appropriate means to prevent ignition of flammablegases and vapors, flammable liquids, combustible dusts, or ignitable fibers or flyings.2.2 This document covers only locations made hazardous, or potentially hazardous, due to the presenceof flammable gase
13、s or vapors, flammable liquids, combustible dusts, or ignitable fibers or flyings. Thedocument is not necessarily relevant to the hazards posed by pyrophoric materials, explosives orpropellants containing their own oxidizers.2.3 This document is concerned only with design, manufacture, installation,
14、 maintenance, and test criteriarelated to arcs, sparks, or hot surfaces produced by electrical and non-electrical* equipment that maycause ignition of flammable gas or vapor-in-air mixtures, clouds or blankets of combustible dust, or easilyignitable fibers or flyings. Equipment should also comply wi
15、th the applicable ordinary locationrequirements (e.g., ANSI/ISA- UL 61010-1).* Under development (Mechanical and ESD for example). Some equipment may produce static electricity or cause hightemperatures or sparks due to mechanical failure. The materials of construction of parts in such equipment wil
16、l be an importantconsideration for application in hazardous locations.2.4 This document does not cover mechanisms of ignition from external sources, such as static electricityor lightning. Some equipment may produce static electricity. The materials of construction of parts in suchequipment will be
17、an important consideration for application in hazardous locations. The extra precautionsnecessary for this are beyond the scope of this document.2.5 This document does not consider the effects of installation in corrosive atmospheres and the resultingdeleterious conditions to the original design int
18、egrity of the equipment. The additional precautionsnecessary for these conditions are outside the scope of this document.2.6 This document is not an instruction manual. However, it is intended to provide introductory guidanceto those involved with the design, manufacture, installation, and maintenan
19、ce of equipment used inhazardous (classified) locations. It is also intended to promote uniformity of practice among those skilledin the art. Nothing contained in this document is to be construed as a fixed rule without regard to soundengineering judgment.MARCH 31, 2017SUBJECT 120101 -3-UL COPYRIGHT
20、ED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2.7 For hazardous location equipment, atmospheric conditions are generally considered to bea) an ambient temperature range of -20 C (-4 F) to 40 C (104 F) for zones and to -25 C (-13 F) to+40 C (104 F) for d
21、ivisions;b) air with normal oxygen content, typically 21 percent by volume;c) a pressure of 80 kPa (11.6 psia) to 110 kPa (16 psia); andNOTE Equipment specified for atmospheric conditions beyond the above is generally permitted but may be subjected to additionalrequirements.2.8 Specialized industrie
22、s such as, but not limited to, mining and shipping may be regulated by thespecific authority having jurisdiction. This document does not include specific requirements or the rulesand regulations unique to any specific industry.2.9 Various organizations have developed codes, guides, and standards tha
23、t have substantialacceptance by industry and governmental bodies. Codes, guides, and standards useful in the design andinstallation of electrical instruments in hazardous (classified) locations are listed in Annex C. These arenot considered to be a part of this document except for those specific sec
24、tions of documents referencedelsewhere in this document.2.10 In accordance with the purpose of this document, an attempt was made to avoid originality inprinciples whenever possible, but rather to utilize definitions, explanations, etc., from acceptedpublications. As a result, much of the material,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL1201012017ULSTANDARDFORSAFETYDEFINITIONSANDINFORMATIONPERTAININGTOELECTRICALEQUIPMENTINHAZARDOUSLOCATIONSCOMMENTSDUEMAY152017PDF

链接地址:http://www.mydoc123.com/p-1067365.html