REG NASA-LLIS-0848-2000 Lessons Learned Maintenance& Test Criteria for Circuit Breakers.pdf
《REG NASA-LLIS-0848-2000 Lessons Learned Maintenance& Test Criteria for Circuit Breakers.pdf》由会员分享,可在线阅读,更多相关《REG NASA-LLIS-0848-2000 Lessons Learned Maintenance& Test Criteria for Circuit Breakers.pdf(15页珍藏版)》请在麦多课文档分享上搜索。
1、Best Practices Entry: Best Practice Info:a71 Committee Approval Date: 2000-04-20a71 Center Point of Contact: KSCa71 Submitted by: Wil HarkinsSubject: Maintenance molded-case, draw-out, high-voltage, etc.). Once the circuit breaker types are identified, one can start to identify the criterion for cir
2、cuit breaker inspection, test, and maintenance. There are many sources of information available to assist one in defining this criterion (example: Federal electric shock and secondary injuries caused by contact with energized circuits or devices that are electrostatically charged after removal of te
3、st potential. Also physical damage resulting from short circuits, insulation failures, or faulty equipment.Identification of safety equipment that is required when working on circuit breakers should be provided. This equipment may consist of nonmetallic hardhats with chin straps, safety goggles, rub
4、ber gloves, sleeves, blankets/mats as required, area barricades and signs.Safety precautions that personnel should be aware of should be identified. For example; turn off power, look out, and disconnect sources of electrical energy before working on equipment. Use of insulated hand tools designed fo
5、r specific work. Use of protective equipment such as safety approved rubber-insulated gloves with protectors, insulating blankets/mats, and non-metallic hardhats. Wear safety eye protection glasses if there is a possibility of arcing or sparking. Ensure that non-current carrying metallic parts of eq
6、uipment are grounded. Inspect visually or conduct tests to determine the adequacy of grounds.The following is extracted from KSC GP-1002 and illustrates how that practice addressed one of the types of circuit breakers found at KSC.Molded-Case Circuit BreakersProvided by IHSNot for ResaleNo reproduct
7、ion or networking permitted without license from IHS-,-,-1. Application. Molded-case circuit breakers are used to interrupt fault currents, to provide overload protection, and to switch the electrical circuit.2. Construction. Molded-case circuit breakers contain two elements: a switch consisting of
8、a set of contacts with suitable mechanical linkage to operate the contacts; and a trip unit which is an overload and fault sensing device.3. Operation. When the thermal or magnetic trip senses an overload condition in the electrical circuits, a spring-loaded latch is tripped. The released spring mec
9、hanism rapidly opens the breaker contacts and de-energizes the faulted circuit. Most molded-case circuit breakers are equipped with a thermal element composed of a bimetallic strip to provide a time delay and establish the tripping characteristics.The instantaneous-trip device is magnetic. High curr
10、ent flow through the breaker picks up the armature of the magnetic trip device. Movement of the armature releases the latch and opens the breaker contacts. Some breakers are available with an adjustable instantaneous trip. The pickup of this trip may be changed in the field from approximately 5 to 1
11、0 times the continuous rating of the breaker.Breakers labeled “non-automatic have no trip unit and are used as load interrupting switches only.4. Maintenance. (1) Preventive Maintenance. Circuit breakers shall be exercised at intervals recommended in Table 1. If the circuit breaker is equipped with
12、a trip indicator, exercise it to verify that it also operates properly. During routine maintenance, check molded-case circuit breakers for improper terminal connection at the time of installation, distorted plug-in tabs or sockets, poorly cleaned or corroded conductors, improper conductors for the l
13、ugs in use, and loose terminations. All of the above are fault conditions which may cause heating and deterioration of the circuit breaker and its response characteristics.Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-refer to D descriptionD Table
14、1. Recommended Maintenance/Test Intervals for Molded-Case Circuit Breakers Note: The above are minimum recommended maintenance/test intervals. Additional tests may be made when the operating agency has experience to indicate need for concern.If overheating of connections is evident through discolora
15、tion or arcing, the breaker should be removed from service and all conducting surfaces cleaned. The breaker should then pass operations tests and the installation megger test before reinstallation.Those breakers with adjustable instantaneous magnetic trip devices should be set at the highest setting
16、 unless otherwise directed.(2) Corrective Maintenance. Perform corrective maintenance on molded-case circuit breakers Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-after fault conditions occur. Follow the procedures given in paragraph 4.(1) and per
17、form the tests required in Table 1 (see paragraph 5). If a molded-case circuit breaker interrupts a fault current whose magnitude is equal to its interrupting rating, the breaker may not be operable.5. Tests. (1) Insulation Megger Tests. Perform insulation megger tests at the intervals indicated in
18、Table 1 and the following instructions.De-energize and, if necessary, remove the breaker from the panel for test. Do not place the megger on large masses of iron nor near strong magnetic fields. Set the megger scale range selector switch in a position that gives a reading in midscale or above. Obser
19、ve megger readings after a minimum of one minute or when the pointer has reached an apparent stabilized value; record the readings. After completion of the test, apply temporary grounds to all test materials and disconnect all leads.This procedure tests one phase to ground with all other phases grou
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- REGNASALLIS08482000LESSONSLEARNEDMAINTENANCETESTCRITERIAFORCIRCUITBREAKERSPDF

链接地址:http://www.mydoc123.com/p-1018494.html