PPI STATEMENT Q-2007 Plastics Pipe Institute Position Statement on Polyethylene Materials For Closed-Loop Ground-Coupled Refrigeration and Heating Applications.pdf
《PPI STATEMENT Q-2007 Plastics Pipe Institute Position Statement on Polyethylene Materials For Closed-Loop Ground-Coupled Refrigeration and Heating Applications.pdf》由会员分享,可在线阅读,更多相关《PPI STATEMENT Q-2007 Plastics Pipe Institute Position Statement on Polyethylene Materials For Closed-Loop Ground-Coupled Refrigeration and Heating Applications.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、STATEMENT Q Plastics Pipe Institute Position Statement on Polyethylene Materials For Closed-Loop Ground-Coupled Refrigeration and Heating Applications Issued October 1995 Revised March 1999 Revised June 2007 Closed-Loop Ground-Coupled (also referred to as “Geothermal”) refrigeration and heating appl
2、ications use polyethylene pipe and fittings that are buried in the ground or submerged in water. This network of pipe and fittings, a ground-coupled heat exchanger, is connected to a mechanical fluid-source refrigeration unit. The ground-coupled heat exchanger is the thermal source during heating cy
3、cles and the thermal sink during cooling cycles. A basic system includes: 1. Mechanical Components Water-Source Refrigeration Unit, Pumps and Valves 2. Ground-Coupled Heat Exchanger Piping System Polyethylene Pipe and Fittings a. Buried in a Horizontal Plane b. Buried in a Vertical Configuration c.
4、Submerged in a Surface Body of Water 3. Heat Transfer Fluid Water, Water/Antifreeze Solution, or Brine solution 1. MECHANICAL COMPONENTS: Mechanical components and installation practices should be designed for closed-loop ground-coupled refrigeration and heating applications. For details regarding e
5、quipment, components and installation, contact the American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, N.E., Atlanta, GA 30329, (404) 636-8400. 2. GROUND-COUPLED HEAT EXCHANGER PIPING SYSTEM: The ground-coupled heat exchanger piping system sh
6、ould be designed to handle the capacity of the building or the mechanical unit load for the specific geographical location. The PPI PE Handbook contains information on PE pipe used in HVAC applications. For additional information regarding design, contact either ASHRAE or IGSHPA (International Groun
7、d Source Heat Pump Association, 347 Cordell South, Oklahoma State University, Stillwater, OK 74078, (405) 744-5175). The piping material is critical to the overall success of the closed-loop ground-coupled system. This system experiences changes in pressure up to 60 psig due to thermal expansion and
8、 contraction of the heat transfer fluid over a temperature range of 25F to 115F. This cycle of change, in both pressure and temperature, occurs to some degree every time the system is operated. The typical average static pressure at ground level is 40 psig; however, substantially greater pressures c
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- PPISTATEMENTQ2007PLASTICSPIPEINSTITUTEPOSITIONSTATEMENTONPOLYETHYLENEMATERIALSFORCLOSEDLOOPGROUNDCOUPLEDREFRIGERATIONANDHEATINGAPPLICATIONSPDF

链接地址:http://www.mydoc123.com/p-1016760.html