《NAVY UFGS-07 21 13-2011 BOARD AND BLOCK INSULATION《板和块状绝缘》.pdf》由会员分享,可在线阅读,更多相关《NAVY UFGS-07 21 13-2011 BOARD AND BLOCK INSULATION《板和块状绝缘》.pdf(19页珍藏版)》请在麦多课文档分享上搜索。
1、*USACE / NAVFAC / AFCESA / NASA UFGS-07 21 13 (May 2011)-Preparing Activity: NAVFAC SupersedingUFGS-07 21 13 (August 2010)UFGS-07 21 13 (February 2010)UFGS-07 21 13 (April 2006)UFGS-07214 (August 2004)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2011*SECTI
2、ON TABLE OF CONTENTSDIVISION 07 - THERMAL AND MOISTURE PROTECTIONSECTION 07 21 13BOARD AND BLOCK INSULATION05/11PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 SUSTAINABLE DESIGN CERTIFICATION1.4 DELIVERY, STORAGE, AND HANDLING1.4.1 Delivery1.4.2 Storage1.5 SAFETY PRECAUTIONS1.5.1 Respirators1.5.2 Oth
3、er Safety ConsiderationsPART 2 PRODUCTS2.1 BLOCK OR BOARD INSULATION2.1.1 Thermal Resistance2.1.2 Fire Protection Requirement2.1.3 Other Material Properties2.1.4 Premolded Concrete Masonry Insert2.1.5 Recycled Materials2.1.6 Prohibited Materials2.2 VAPOR RETARDER AND DAMPPROOFING2.2.1 Vapor Retarder
4、 in Frame Walls and Roofs2.2.2 Dampproofing for Masonry Cavity Walls2.2.3 Vapor Retarder under Floor Slab2.3 PRESSURE SENSITIVE TAPE2.4 PROTECTION BOARD OR COATING2.5 ACCESSORIES2.5.1 Adhesive2.5.2 Mechanical FastenersPART 3 EXECUTIONSECTION 07 21 13 Page 1Provided by IHSNot for ResaleNo reproductio
5、n or networking permitted without license from IHS-,-,-3.1 EXISTING CONDITIONS3.2 PREPARATION3.2.1 Blocking Around Heat Producing Devices3.3 INSTALLATION3.3.1 Insulation Board3.3.2 Electrical Wiring3.3.3 Cold Climate Requirement3.3.4 Continuity of Insulation3.4 INSTALLATION ON WALLS3.4.1 Installatio
6、n using Furring Strips3.4.2 Installation on Masonry Walls3.4.3 Adhesive Attachment to Concrete and Masonry Walls3.4.4 Mechanical Attachment on Concrete and Masonry Walls3.4.5 Protection Board or Coating3.5 INSTALLATION ON UNDERSIDE OF CONCRETE FLOOR SLAB3.5.1 Mechanically Fastened Systems3.5.2 Adhes
7、ively Bonded Systems3.6 PERIMETER AND UNDER SLAB INSULATION3.6.1 Manufacturers Instructions3.6.2 Insulation on Vertical Surfaces3.6.3 Insulation Under Slab3.6.4 Protection of Insulation3.7 VAPOR RETARDER3.8 ACCESS PANELS AND DOORS- End of Section Table of Contents -SECTION 07 21 13 Page 2Provided by
8、 IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-07 21 13 (May 2011)-Preparing Activity: NAVFAC SupersedingUFGS-07 21 13 (August 2010)UFGS-07 21 13 (February 2010)UFGS-07 21 13 (April 2006)UFGS-07214 (August 2004)UNIFIED FACI
9、LITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2011*SECTION 07 21 13BOARD AND BLOCK INSULATION05/11*NOTE: This guide specification covers the requirements for board and block thermal insulation.Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format
10、 Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information
11、 and requirements not required in respective project, whether or not brackets are present.Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).*NOTE: This guide specification is intended for both retrofit of
12、 existing buildings and new construction.*NOTE: Specify board-type insulations for masonry and concrete walls and under concrete floor slabs. Also specify board-type insulation where the type of construction favors their economical usage and their application would be less difficult than blanket or
13、loose fill insulations.*NOTE: On the drawings, show:SECTION 07 21 13 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-1. Locations where insulation will be used.2. Thermal resistance value (R-Value) for each location.3. Location of vapor retarde
14、r, if required.4. Method of attachment of insulation board.5. Location and size of attic ventilation openings where required.*NOTE: Attic Ventilation1. Provide net, unobstructed attic ventilation areas over insulated ceilings as recommended by ASHRAE Handbook of Fundamentals, Chapter 21, and as foll
15、ows:2. For attics with vapor retarder, provide 0.1 square meter one square foot of net ventilation area for each 30 square meters 300 square feet of attic floor area.3. For attics without vapor retarder, provide 0.1 square meter one square foot of net ventilation area for each 15 square meters 150 s
16、quare feet of attic floor area.4. For insulation of cathedral ceilings, provide at least a 50 mm 2 inch gap between upper face of insulation and underside of roof sheathing. Provide ventilation openings at bottom and top of ventilated cavity; show on drawings.*PART 1 GENERAL1.1 REFERENCES*NOTE: This
17、 paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a
18、 RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project SECTION 07 21
19、13 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this specification to the extent referenced. The publications ar
20、e referred to within the text by the basic designation only.ASTM INTERNATIONAL (ASTM)ASTM C 1289 (2010) Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation BoardASTM C 165 (2007) Standard Test Method for Measuring Compressive Properties of Thermal InsulationsASTM C 20
21、3 (2005a) Breaking Load and Flexural Properties of Block-Type Thermal InsulationASTM C 272 (2001; R 2007) Water Absorption of Core Materials for Structural Sandwich ConstructionsASTM C 552 (2007) Standard Specification for Cellular Glass Thermal InsulationASTM C 553 (2008) Standard Specification for
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS0721132011BOARDANDBLOCKINSULATION 块状 绝缘 PDF

链接地址:http://www.mydoc123.com/p-984718.html