NAVY MIL-PRF-32227-2006 FLAME DETECTOR ZONE MODULE (FDZM) SWITCH CLOSURE ZONE MODULE (SCZM) AND ISOLATOR ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS)《高级火和烟敏感元件系统(AFSSS)火焰带检测组件(FDZ.pdf
《NAVY MIL-PRF-32227-2006 FLAME DETECTOR ZONE MODULE (FDZM) SWITCH CLOSURE ZONE MODULE (SCZM) AND ISOLATOR ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS)《高级火和烟敏感元件系统(AFSSS)火焰带检测组件(FDZ.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-PRF-32227-2006 FLAME DETECTOR ZONE MODULE (FDZM) SWITCH CLOSURE ZONE MODULE (SCZM) AND ISOLATOR ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS)《高级火和烟敏感元件系统(AFSSS)火焰带检测组件(FDZ.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、Comments, suggestions, or questions on this document should be addressed to: Commander, Naval Sea Systems Command, ATTN: SEA 05Q, 1333 Isaac Hull Avenue, SE, Stop 5160, Washington Navy Yard DC 20376-5160 or emailed to CommandStandardsnavy.mil, with the subject line “Document Comment”. Since contact
2、information can change, you may want to verify the currency of this address information using the ASSIST Online database at http:/assist.daps.dla.mil. AMSC N/A FSC 6320 INCH-POUND MIL-PRF-32227 25 October 2006 PERFORMANCE SPECIFICATION FLAME DETECTOR ZONE MODULE (FDZM), SWITCH CLOSURE ZONE MODULE (S
3、CZM), AND ISOLATOR, ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS) This specification is approved for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers the performance requirements for Flame Detector Zone Modules (FDZM) (see 6.8.6), Switch
4、 Closure Zone Modules (SCZM) (see 6.8.16), and isolators (see 6.8.9) and their respective enclosures, which are components of an overall Advanced Fire and Smoke Sensor System (AFSSS) for use on naval ships. These devices may be of commercial-off-the-shelf (COTS) design, but must be rugged (see 6.8.1
5、3) enough to meet all of the requirements of this performance specification and the rigors of Navy shipboard service. Performance requirements for the other associated AFSSS components (e.g., ionization (see 6.8.8) and photoelectric (see 6.8.10) smoke sensors (see 6.8.15), heat sensors (see 6.8.7),
6、flame detectors (see 6.8.5), and alarm panel (see 6.8.2) are contained in their respective AFSSS specifications. 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4, or 5 of this specification. This section does not include documents cited in othe
7、r sections of this specification or recommended for additional information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4, or 5 of this specifica
8、tion, whether or not they are listed. 2.2 Government documents. 2.2.1 Specifications, standards, and handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cite
9、d in the solicitation or contract. DEPARTMENT OF DEFENSE SPECIFICATIONS MIL-S-901 - Shock Tests, H.I. (High Impact); Shipboard Machinery, Equipment and Systems, Requirements for MIL-E-2036 - Enclosures for Electric and Electronic Equipment MIL-DTL-24643 - Cables and Cords, Electric, Low Smoke, for S
10、hipboard Use General Specifications for Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-32227 DEPARTMENT OF DEFENSE STANDARDS MIL-STD-167-1 - Mechanical Vibrations of Shipboard Equipment (Type I Environmental and Type II Internally Excited) M
11、IL-STD-461 - Requirements for the Control of Electromagnetic Interference Characteristics of Subsystems and Equipment (Copies of these documents are available online at http:/assist.daps.dla.mil/quicksearch/ or http:/assist.daps.dla.mil or from the Standardization Document Order Desk, 700 Robbins Av
12、enue, Building 4D, Philadelphia, PA 19111-5094.) 2.3 Non-Government publications. The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. NATIONAL FIRE PROTECTION A
13、SSOCIATION (NFPA) NFPA 72 - National Fire Alarm Code (Copies of this document are available from National Fire Protection Association, 11 Tracy Drive, Avon, MA 02322 or online at www.nfpa.org.) UNDERWRITERS LABORATORES INC. (UL) UL 864 - Control Units for Fire-Protective Signaling Systems (Copies of
14、 this document are available from Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096 or online at .) 2.4 Order of precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this document takes precedence. Nothing
15、in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 First article. When specified (see 6.2 and 6.3), a sample shall be subjected to first article inspection in accordance with 4.2. 3.2 Design requirements. 3.2.1 Des
16、ign, materials, and manufacturing process. The contractor shall select the materials, but the materials shall meet all of the interface, operational, and performance requirements specified herein. 3.2.2 Recycled, recovered, or environmentally preferable materials. Recycled, recovered, or environment
17、ally preferable materials should be used to the maximum extent possible, provided that the material meets or exceeds the operational and maintenance requirements, and promotes economically advantageous life cycle costs. 3.3 Configuration. The overall FDZM, SCZM, and isolator shall each consist of th
18、e appropriate electronics contained inside an appropriate enclosure. The terms “Flame Detector Zone Module”, “Switch Closure Zone Module”, and “isolator”, as used in this specification, refer to the overall FDZM, SCZM, and isolator, consisting of the devices appropriate electronics and the appropria
19、te enclosure. FDZMs, SCZMs, and isolators shall operate properly in both overhead or bulkhead mounted positions. 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-32227 3.3.1 Interchangeability. The AFSSS FDZM shall have a unique model number
20、 assigned to it, and shall be physically identical and interchangeable with all other AFSSS FDZMs from the same manufacturer. The AFSSS SCZM shall have a unique model number assigned to it and shall be physically identical and interchangeable with all other AFSSS SCZMs from the same manufacturer. Th
21、e AFSSS isolator shall have a unique model number assigned to it and shall be physically identical and interchangeable with all other AFSSS isolators from the same manufacturer. 3.3.2 Individual addressability. The FDZM and the SCZM shall each have an adjustable mechanical device or dipswitch that c
22、an be easily set to allow each device to be individually identifiable and addressable by the AFSSS alarm panel once installed in a specific location in a shipboard compartment. Once set, this device or dipswitch shall be easily capable of later being set to a different address, without the use of sp
23、ecial tools or equipment, to support interchangeability. This individual addressability requirement may also apply to the isolator, but it is not specifically required for the isolator. 3.3.3 Enclosure. An enclosure shall securely house and enclose the FDZM, SCZM, and isolator. The enclosure for the
24、 isolator shall possess enough flat surface area to allow two separate LS2SWU-1 cables (see MIL-DTL-24643) (i.e., the sensor loop) with appropriate watertight stuffing tubes (see MIL-E-2036) to penetrate the enclosure. The enclosure for the SCZM shall possess enough flat surface area to allow three
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILPRF322272006FLAMEDETECTORZONEMODULEFDZMSWITCHCLOSUREZONEMODULESCZMANDISOLATORADVANCEDFIREANDSMOKESENSORSYSTEMAFSSS

链接地址:http://www.mydoc123.com/p-981013.html