1、 AMSC N/A FSC 5920 W-F-1814/56D 15 November 2013 SUPERSEDING W-F-1814/56C 01 October 2009 FEDERAL SPECIFICATION SHEET FUSE, CARTRIDGE, HIGH INTERRUPTING CAPACITY, CLASSES RK1 AND RK5 (CURRENT-LIMITING) 250 VOLTS, 0-30 AMPERES The General Services Administration has authorized the use of this federal
2、 specification sheet by all federal agencies. The complete requirements for procuring the fuses described herein shall consist of this document and the latest issue in effect of W-F-1814. FIGURE 1. Classes RK1 and RK5 fuses, 250 volts, 0-30 amperes. INCH-POUND Provided by IHSNot for ResaleNo reprodu
3、ction or networking permitted without license from IHS-,-,-W-F-1814/56D 2 Ltr Inches mm Ltr Inches mm Min Max Min Max Min Max Min Max A 1.970 2.030 50.04 51.56 H - .150 - 3.81 B .500 - 12.70 - J .026 .036 .66 .91 C .151 .161 3.84 4.09 K .850 - 21.59 - D .085 .130 2.16 3.30 L - .130 - 3.30 E - .530 -
4、 13.46 M .070 - 1.78 - F .554 .570 14.07 14.48 N .151 .161 3.84 4.09 G - .115 - 2.92 NOTES: 1. Dimensions are in inches. 2. Metric equivalents are given for general information only. 3. Solid line indicates location, shape, and dimensions for minimum rejection groove. 4. Dashed line indicates locati
5、on, shape, and dimensions for maximum rejection groove. 5. Unless otherwise specified, tolerances are .02 (0.51 mm) for two-place decimals and .005 (0.13 mm) for three-place decimals. FIGURE 1. Classes RK1 and RK5 fuses, 250 volts, 0-30 amperes - continued. REQUIREMENTS: Interface and physical dimen
6、sions: See figure 1. Physical: Nonrenewable. Terminals: Ferrule type. The ferrules shall be approximately circular in cross-section. Material: Brass, copper, or copper alloy. Strength: 5 inch-pound torque between body and ferrules. Alignment: The inside diameter of tubular gauge shall be not more th
7、an .571 inch (14.50 mm). Body: Insulating material: Fiber, ceramic, melamine-impregnated glass fiber, or other suitable material. Electrical: Voltage: 250 volts or less. Frequency: 48 Hz to 60 Hz. Current: See table I. Provided by IHSNot for ResaleNo reproduction or networking permitted without lice
8、nse from IHS-,-,-W-F-1814/56D 3 Current carrying capacity: 110 percent of rated current indefinitely with temperature rise on the terminals not to exceed 50C (90F) above ambient on the body and the ferrules. Overload interrupt: Instantaneous: Shall interrupt within 1 hour at 135 percent of rated cur
9、rent and within 2 minutes at 200 percent of rated current. Time delay: In addition to the above requirement, the fuse shall not interrupt 500 percent of rated current within 10 seconds. Interrupting capacity rating: 200,000 amperes rms symmetrical at 250 volts, 48 Hz to 60 Hz and a power factor of 2
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAWF181456D2013FUSECARTRIDGEHIGHINTERRUPTINGCAPACITYCLASSESRK1ANDRK5CURRENTLIMITING250VOLTS030AMPERESPDF

链接地址:http://www.mydoc123.com/p-701579.html