《BS 4553-3-1998 Specification for 600 1000 V single-phase split concentric electric cables - Cables having thermosetting insulation and low emission of smoke and corrosive gases whe.pdf》由会员分享,可在线阅读,更多相关《BS 4553-3-1998 Specification for 600 1000 V single-phase split concentric electric cables - Cables having thermosetting insulation and low emission of smoke and corrosive gases whe.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS 4553-3:1998 Incorporating Amendments Nos. 1 and 2 Specification for 600/1 000 V single-phase split concentric electric cables Part 3: Cables having thermosetting insulation and low emission of smoke and corrosive gases when affected by fire ICS 29.060.20 BS 4553-3:1998 This Briti
2、sh Standard, having been prepared under the direction of the Electrotechnical Sector Board, was published under the authority of the Standards Board and comes into effect on 15 August 1998 BSI 29 April 2005 First published, February 1970 Second edition, January 1988 Third edition, February 1992 The
3、following BSI references relate to the work on this standard: Committee reference GEL/20/2 Draft for comment 97/201035 DC ISBN 0 580 29576 1 Committees responsible for this British Standard The preparation of this British Standard was entrusted by Technical Committee GEL/20, Electric cables, to Subc
4、ommittee GEL/20/2, Mains cables, 1 kV and above, upon which the following bodies were represented: Association of Consulting Engineers British Approvals Service for Cables British Cables Association British Plastics Federation Electricity Association ERA Technology Ltd. London Underground Ltd. UK St
5、eel Association Amendments issued since publication Amd. No. Date Comments 14192 5 February 2004 See foreword 15643 29 April 2005 Certification text in foreword changedBS 4553-3:1998 BSI 29 April 2005 i Contents Page Committees responsible Inside front cover Foreword ii 1S c o p e 1 2 Normative refe
6、rences 1 3 Definitions 2 4V o l t a g e d e s i g n a t i o n 3 5 Phase conductor 3 6I n s u l a t i o n 3 7 Identification of phase core 3 8B e d d i n g 4 9 Concentric layer 4 10 Binders 4 11 Oversheath 5 12 Cable marking 5 13 End sealing 6 14 Schedule of tests 6 15 Test conditions 6 16 Routine te
7、sts 6 17 Sample tests 8 18 Type tests 8 Annex A (informative) Recommendations for the selection and operation of cables 10 Annex B (informative) Recommendations for installation of cables 11 Annex C (informative) Information to be provided with enquiry or order 12 Annex D (normative) Measurement of
8、thickness 12 Annex E (normative) Voltage tests on completed cables 12 Annex F (Spare) 12 Annex G (normative) Compatibility test 13 Annex H (informative) Notes on type tests 13 Annex J (informative) Guide to use 14 Bibliography 17 Table 1 Schedule of tests 7 Table 2 Compatibility requirements 8 Table
9、 3 600/1 000 V XLPE-insulated single-phase split concentric cables with stranded copper phase conductors 9 Table 4 600/1 000 V XLPE-insulated single-phase split concentric cables with solid aluminium phase conductors 9BS 4553-3:1998 ii BSI 29 April 2005 Foreword This British Standard has been prepar
10、ed by Subcommittee GEL/20/2. It is one of three parts of a full technical revision of BS 4553:1992, which is withdrawn. The start and finish of text introduced or altered by amendment is indicated in the text by tags !“. Tags indicating changes to text carry the number of the amendment. For example,
11、 text altered by amendment No. 1 is indicated by !“. BS 4553-3 specifies the range of split concentric cables which have thermosetting insulation and non-halogenated sheaths and a low emission of smoke and acid gas when affected by fire. In addition, the standard contains the option of solid alumini
12、um conductors or stranded copper conductors, as well as the option of using a separate extruded bedding to build up the core to a diameter suitable for applying the split concentric layer. BS 4553-1 specifies the range of split concentric cables but which have PVC insulation and sheath. BS 4553-2 sp
13、ecifies a similar range of split concentric cables, but which have thermosetting insulation and sheath. Amendment No. 1:2004 implements the changes to the identification of cores by colours, in accordance with HD 308 S2. The principal identification colours are now: Single phase Green-and-yellow (Ea
14、rth); blue (Neutral); brown (Live). Three phase Green-and-yellow (Earth); blue (Neutral); brown, black, grey (Live). Users should ensure that any interconnection between cables with these new colours and those with the pre-existing ones is carried out safely. BS 7671, as amended in parallel with thi
15、s standard, gives some guidance in this respect, but does not cover all installation conditions or cables uses. The provisions introduced by amendment No. 1:2004 are effective from 1 stApril 2004. The original version of this standard remains current until 31 stMarch 2006. Product certification/insp
16、ection/testing. Users of this British Standard are advised to consider the desirability of third-party certification/inspection/testing of product conformity with this British Standard. Users seeking assistance in identifying appropriate conformity assessment bodies or schemes may ask BSI to forward
17、 their enquiries to the relevant association. WARNING. This standard calls for the use of substances and/or procedures that may be injurious to health if adequate precautions are not taken. It refers only to technical suitability and does not absolve the user from legal obligations relating to healt
18、h and safety at any stage. Annex D, Annex E and Annex G are normative. Annex A, Annex B, Annex C, Annex H and Annex J are informative. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British
19、 Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pages i and ii, pages 1 to 17 and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued.BS 4553-
20、3:1998 BSI 29 April 2005 1 1 Scope This British Standard specifies requirements for construction and describes methods of test for XLPE-insulated single-phase split concentric cables for operation on an earthed neutral system at nominal voltages up to and including 1 000 V between phases and 600 V t
21、o earth and which, when assessed by the specified tests, produce lower levels of smoke and corrosive products under exposure to fire, compared with corresponding cables conforming to BS 4553-1 and BS 4553-2. In this standard, the level of corrosive (and acid) gases is determined by measurement of hy
22、drochloric acid (HCl) in accordance with !BS EN 50267-2-1 “. The cables specified in this part of BS 4553 have a central phase conductor insulated with XLPE and a concentric layer comprising bare copper wires (earth continuity conductor) and copper wires covered with extruded polymer (neutral conduc
23、tor). The cables are intended for use in fixed installations in industrial areas, buildings and similar applications. They are suitable for use in situations where the combination of ambient temperature and temperature rise due to loading current results in a conductor temperature not exceeding 90 C
24、 and for a maximum short-circuit conductor temperature of 250 C. NOTE 1 Limitation on the temperature of the cables may be imposed in situations where they may be touched. NOTE 2 Due to the relatively high conductor temperature, there is a risk of drying out the surrounding soil causing an increase
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS455331998SPECIFICATIONFOR6001000VSINGLEPHASESPLITCONCENTRICELECTRICCABLESCABLESHAVINGTHERMOSETTINGINSULATIONANDLOWEMISSIONOFSMOKEANDCORROSIVEGASESWHEPDF

链接地址:http://www.mydoc123.com/p-544495.html