ASTM F855-2014 Standard Specifications for Temporary Protective Grounds to Be Used on De-energized Electric Power Lines and Equipment 《断开的电力线及设备上使用的临时保护性接地装置的标准规格》.pdf
《ASTM F855-2014 Standard Specifications for Temporary Protective Grounds to Be Used on De-energized Electric Power Lines and Equipment 《断开的电力线及设备上使用的临时保护性接地装置的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM F855-2014 Standard Specifications for Temporary Protective Grounds to Be Used on De-energized Electric Power Lines and Equipment 《断开的电力线及设备上使用的临时保护性接地装置的标准规格》.pdf(30页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F855 09F855 14Standard Specifications forTemporary Protective Grounds to Be Used on De-energizedElectric Power Lines and Equipment 1This standard is issued under the fixed designation F855; the number immediately following the designation indicates the year of originaladoption or, in th
2、e case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.Asuperscriptepsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 These specifications cover the equipment making up the temporary grounding system used on
3、de-energized electric powerlines, electric supply stations, and equipment.1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations togovern in detail the correct use and maintenance of such equipment.1.3 The uses and maintenance of th
4、is equipment are beyond the scope of these specifications.1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:SectionsClamps for Temporary Protective Grounds 4 16Ferrules for Temporary Protective Grounds 17 30Cables for Temporar
5、y Protective Grounds 31 39Protective Grounds (Complete Assembly With Clamps, Ferrules,and Cable)40 521.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.1.6 Currents presented in Table 1 are based upon cable melting times, as de
6、termined from equations by I. M. Onderdonk andare to used in situations involving an asymmetry value less than 20 % (X/R 1.8). See Appendix X3.1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “ADesktopComputer Program for Calculating Rating
7、 of Temporary Grounding Cables” and are to be used in situations involving anasymmetry value greater then 20 % (X/R 1.8), see Appendix X4.NOTE 1Table 1 represents the clamp and assembly ratings that existed prior to this revision. Table 2 represents new ratings now required for highX/R situations.1.
8、6.2 See Appendix X3 and Appendix X4 for a discussion of these topics.1.7 The values stated in Newton-Meter units are to be regarded as the standard. The values in parentheses are the inch-poundunits.1.8 The following precautionary caveat pertains to the test method portions, Sections 12 and 25 of th
9、ese specifications:Thisstandard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations priorto use.2.
10、Referenced Documents2.1 ASTM Standards:2B172 Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Members, for Electrical ConductorsB173 Specification for Rope-Lay-Stranded Copper Conductors Having Concentric-Stranded Members, for Electrical Conduc-tors1 These specifications a
11、re under the jurisdiction ofASTM Committee F18 on Electrical Protective Equipment for Workers and are the direct responsibility of SubcommitteeF18.45 on Mechanical Apparatus.Current edition approved May 1, 2009Oct. 1, 2014. Published July 2009November 2014. Originally approved in 1983. Last previous
12、 edition approved in 20042009 asF855 04.F855 09. DOI: 10.1520/F0855-09.10.1520/F0855-14.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summar
13、y page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends t
14、hat users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1D470 Test Methods for
15、 Crosslinked Insulations and Jackets for Wire and CableD753 Specification for General Purpose Polychloroprene Jacket for Wire and Cable (Withdrawn 1984)3D2219 Specification for Poly(Vinyl Chloride) Insulation for Wire and Cable, 60C OperationD2633 Test Methods for Thermoplastic Insulations and Jacke
16、ts for Wire and CableD2768 Specification for General-Purpose Ethylene-Propylene Rubber Jacket for Wire and Cable (Withdrawn 2007)3D2770 Specification for Ozone-Resisting Ethylene-Propylene Rubber Integral Insulation and Jacket for Wire and Cable(Withdrawn 2007)3E8/E8M Test Methods for Tension Testin
17、g of Metallic Materials2.2 ANSI Standard:4C 37.09 Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Basis2.3 ICEA/NEMA Standard:5ICEA S-19-81/NEMAWC 3-80 (R 1986) Rubber Insulated Wire and Cable for the Transmission and Distribution of ElectricalEnergy2.4 IEC Standa
18、rd:6IEC 61230 Ed. 2, 2008, Portable Equipment for Earthing or Earthing and Short-Circuiting2.5 IEEE Standard:7IEEE 386 Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600VIEEE 1048 Guide for Protective Grounding of Power LinesIEEE 1246 Guide for Temporary Prot
19、ective Grounding Systems Used in Substations3. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 continuous current ratingdesignated RMS current which can be carried continuously under specified conditions.3.1.2 protective ground assemblya temporary electrical connection between a
20、source of potential energization and the earth,rated for the maximum anticipated fault current or continuous induced current, or both.3.1.2.1 DiscussionThroughout this specification, kc mil = 1000 circular mils.3.1.3 protective grounding equipmentdevices installed temporarily on de-energized electri
21、c power circuits for the purposes ofpotential equalization and to conduct a short circuit current for a specified duration (time).3 The last approved version of this historical standard is referenced on www.astm.org.4 Available from American National Standards Institute, 11 West 42nd St., 13th Floor
22、, New York, NY 10036.5 Available from Insulated Cable Engineers Assoc., P.O. Box P, South Yarmouth, MA 02664.6 Available from International Electrotechnical Commission (IEC), 3 rue de Varemb, Case postale 131, CH-1211, Geneva 20, Switzerland, http:/www.iec.ch.7 Available from Institute of Electrical
23、 and Electronics Engineers, Inc. (IEEE), 445 Hoes Ln., P.O. Box 1331, Piscataway, NJ 08854-1331, http:/www.ieee.org.TABLE 1 Protective Ground Cable, Ferrule, Clamp and Assembly Ratings for Symmetrical CurrentGradeGrounding Clamp TorqueStrength, min Short Circuit PropertiesAContinuousCurrentRating, A
24、RMS, 60HzYieldB UltimateWithstand Rating, SymmetricalkARMS, 60 HzUltimate Rating CapacityCD , SymmetricalkARMS, 60 Hzlbfin. nm lbfin. nm15cycles(250 ms)30 cycles(500ms)Copper CableSize15cycles(250ms)30cycles(500ms)60cycles(1 s)MaximumCopper TestCable Size1 280 32 330 37 14 10 #2 18 13 9 2/0 2002 280
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF8552014STANDARDSPECIFICATIONSFORTEMPORARYPROTECTIVEGROUNDSTOBEUSEDONDEENERGIZEDELECTRICPOWERLINESANDEQUIPMENT

链接地址:http://www.mydoc123.com/p-537402.html