1、Designation:E60307 Designation: E603 12An American National StandardStandard Guide forRoom Fire Experiments1This standard is issued under the fixed designation E603; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last
2、revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONThis guide has been written to assist those planning to conduct full-scale compartment fireexperiments. There are many issu
3、es that should be resolved before such an experimental program isinitiated, and this guide is written with the objective of identifying some of these issues and presentingconsiderations that will affect each choice of procedure.This guide deals with any or all stages of fire growth in a compartment.
4、 Whether it is a single- ormulti-room experiment, observations can be made from ignition to flashover or beyond full-roominvolvement.One major reason for conducting research on room fires is to learn about the room fire buildupprocess so the results of standard fire test methods can be related to pe
5、rformance in full-scale roomfires, allowing the further refinement of these test methods or development of new ones.Another reason concerns computer fire modeling. Full-scale tests can generate data needed formodeling. Comparisons of modeling with full-scale test results can serve to validate the mo
6、del.The various results among room fire tests reflect different experimental conditions. The intent of thisguide is to identify these conditions and discuss their effects so meaningful comparisons can be madeamong the room fire experiments conducted by various organizations.1. Scope1.1 This guide ad
7、dresses means of conducting full-scale fire experiments that evaluate the fire-test-response characteristics ofmaterials, products, or assemblies under actual fire conditions.1.2 It is intended as a guide for the design of the experiment and for the use and interpretation of its results. The guide i
8、s alsouseful for establishing laboratory conditions that simulate a given set of fire conditions to the greatest extent possible.1.3 This guide allows users to obtain fire-test-response characteristics of materials, products, or assemblies, which are usefuldata for describing or appraising their fir
9、e performance under actual fire conditions.1.3.1 The results of experiments conducted in accordance with this guide are also useful elements for making regulatorydecisions regarding fire safety requirements. The use for regulatory purposes of data obtained from experiments conducted usingthis guide
10、requires that certain conditions and criteria be specified by the regulating authority.1.4 The rationale for conducting room fire experiments in accordance with this guide is shown in 1.5-1.81.5 Room fire experiments are a means of generating input data for computer fire models and for providing out
11、put data withwhich to compare modeling results.1.6 One of the major reasons for conducting room fire experiments is as an experimental means of assessing the potential firehazard associated with the use of a material or product in a particular application. This should be borne in mind when designing
12、nonstandard experiments.1.7 A rationale for conducting room fire experiments is the case when smaller-scale fire tests inadequately represent end-useapplications.1.8 A further rationale for conducting room fire experiments is to verify the results obtained with smaller scale tests, tounderstand the
13、scaling parameters for such tests.1.9 Room fire tests can be placed into four main categories: reconstruction, simulation, research, and standardization.1.10 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under1This guide is under t
14、he jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.21 on Smoke and CombustionProducts.Current edition approved July 1, 2007. Published August 2007. Originally approved in 1977. Last previous edition approved in 2006 as E603-061. DOI:10.1520/E
15、0603-07.Current edition approvedApril 15, 2012. PublishedApril 2012. Originally approved in 1977. Last previous edition approved in 2007 as E603 - 07. DOI: 10.1520/E0603-12.1This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what chang
16、es have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the offici
17、al document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials,products, or assemblies under actual f
18、ire conditions1.11 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.2.
19、 Referenced Documents2.1 ASTM Standards:2D4442 Test Methods for Direct Moisture Content Measurement of Wood and Wood-Base MaterialsD4444 Test Method for Laboratory Standardization and Calibration of Hand-Held Moisture MetersD5424 Test Method for Smoke Obscuration of Insulating Materials Contained in
20、 Electrical or Optical Fiber Cables WhenBurning in a Vertical Cable Tray ConfigurationD5537 Test Method for Heat Release, Flame Spread, Smoke Obscuration, and Mass Loss Testing of Insulating MaterialsContained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray ConfigurationE
21、176 Terminology of Fire StandardsE800 Guide for Measurement of Gases Present or Generated During FiresE906 Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using a Thermopile MethodE1321 Test Method for Determining Material Ignition and Flame Spread PropertiesE1354 Tes
22、t Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen ConsumptionCalorimeterE1355 Guide for Evaluating the Predictive Capability of Deterministic Fire ModelsE1537 Test Method for Fire Testing of Upholstered FurnitureE1590 Test Method for Fire Testing of Mattres
23、sesE1822 Test Method for Fire Testing of Stacked ChairsE2067 Practice for Full-Scale Oxygen Consumption Calorimetry Fire TestsE2257 Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies2.2 UL Standards:UL 1715Room Corner Test3UL Subject 1040Large Scale Open Corner Test3UL 1040
24、Fire Test of Insulated Wall ConstructionUL 1715 Fire Test of Interior Finish Material2.3 ICBO Standards:4Uniform Building Code Standard UBC 8-2 Standard Test Method for Evaluating Room Fire Growth Contribution of TextileWallcoveringsUniform Building Code Standard UBC 26-3 Room Fire Test Standard for
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME6032012RED5000STANDARDGUIDEFORROOMFIREEXPERIMENTS 房间 着火 实验 标准 指南 PDF

链接地址:http://www.mydoc123.com/p-533129.html