ASTM E196-2006(2012) 1875 Standard Practice for Gravity Load Testing of Floors and Low Slope Roofs《地面和低斜屋顶重力荷载测试的标准实施规程》.pdf
《ASTM E196-2006(2012) 1875 Standard Practice for Gravity Load Testing of Floors and Low Slope Roofs《地面和低斜屋顶重力荷载测试的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM E196-2006(2012) 1875 Standard Practice for Gravity Load Testing of Floors and Low Slope Roofs《地面和低斜屋顶重力荷载测试的标准实施规程》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E196 06 (Reapproved 2012)Standard Practice forGravity Load Testing of Floors and Low Slope Roofs1This standard is issued under the fixed designation E196; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of las
2、t revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This practice covers static load testing
3、 of floors and lowslope roofs (roofs having a slope of less than 1 in 12) underactual or simulated service conditions, and is applicable totypical elements or sections of structures fabricated for test orto actual existing building components. This practice is in-tended for use in determining the st
4、rength and stiffness ofelements or sections of floors and roofs of buildings undergravity loads, as well as in checking the design, materials,connections, and the quality of the fabrication of such buildingconstructions.1.2 The values stated in SI units are to be regarded asstandard. The values give
5、n in parentheses are mathematicalconversions to inch-pound units that are provided for informa-tion only and are not considered standard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to e
6、stablish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E575 Practice for Reporting Data from Structural Tests ofBuilding Constructions, Elements, Connections, and As-sembliesE631 Terminology
7、 of Building Constructions3. Terminology3.1 For definitions of terms in this practice, see TerminologyE631.4. Significance and Use4.1 This practice is intended to be used by parties involvedin the testing of floors and roofs of structures either in the fieldor the laboratory. Tests are either proof
8、tests or tests to failure,and are applicable to all construction materials. The practice isnot intended for use in routine quality control testing ofindividual building elements or constructions.5. Types of Tests5.1 Proof TestsProof tests are intended to give assurancethat the construction will supp
9、ort a specified load or will notexceed a given deflection under this load, or both. If the flooror roof is to be placed in service after the proof test, or is partof an existing structure which must remain in service after thetest, great care must be exercised to determine that structuraldamage has
10、not occurred, or that if failure did occur, damage isminimal and the safety of personnel is not jeopardized.5.2 Failure TestsFailure tests are carried out to obtainmore detailed information on the performance, ultimate loadcarrying capacity, the mode of failure, the adequacy of theconnections, and t
11、o develop the complete load-deflection curvefor the construction(s).6. Test Specimens6.1 The area or size of the test specimen shall be arepresentative section, taken to duplicate the structural perfor-mance of the actual floor or roof, or shall be a typical elementor bay of an existing structure. W
12、hen a loading test isperformed on a particular floor or roof composed of manyidentical segments, the selection of a representative test sectionshall be approved by the building official or party for whom thetest is being performed. Normally only one representativeportion of the structure need be tes
13、ted, except where variousareas of a floor or roof are subject to differing types of loading,or where a number of structural elements or sections in abuilding are suspect and to be proof loaded.6.2 The condition of the materials in the assembly to betested shall be reasonably equivalent, at the time
14、of test, to theconditions assumed in the design or representative of the actualin-service conditions.1This practice is under the jurisdiction of ASTM Committee E06 on Perfor-mance of Buildings and is the direct responsibility of Subcommittee E06.11 onHorizontal and Vertical Structures/Structural Per
15、formance of Completed Structures.Current edition approved Oct. 1, 2012. Published October 2012. Originallyapproved in 1962. Last previous edition approved in 2006 as E196 06. DOI:10.1520/E0196-06R12.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service
16、 at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States17. Simulated Structures7.1 When a loading test i
17、s carried out on a simulatedstructure, the support conditions and the fixity of the edges ofthe floor or roof developed in the actual structure shall bereproduced as closely as possible in the test specimen.7.2 The materials, structural shapes, connections,connectors, and construction used in the si
18、mulated structureshall duplicate as closely as practical those used or intended foruse in the actual structure.8. General Testing Arrangement8.1 Verification of Design AssumptionsFloors or roofsshall be loaded in a manner satisfying the original designassumptions. Floors or roofs designed for unifor
19、m loadingshall be tested under uniform loading or by a method that willsimulate the forces and moments generated by a uniformlydistributed load. When structures with protrusions or structuralelements that are located above the surface to be loaded aretested, care shall be taken to ensure that the lo
20、ading procedureused does not inadvertently restrain lateral buckling of theseelements.8.2 Uniform Live LoadAn actual uniform live load isapplied to the test specimen(s). This shall be achieved using anair bag, a vacuum chamber, water, or other suitable materials.If water is used as a loading medium,
21、 care must be taken tominimize the effects of ponding which will produce a nonuni-form load. One means of minimizing the ponding is bydividing the area to be loaded by water into a series of separatecompartments that are filled individually.NOTE 1The unintentional failure of a test structure loaded
22、by watercan be extremely messy and can create unanticipated problems.8.3 Simulated Uniform Live LoadA simulated uniformlive load shall be applied by dead weights, jacks, cables andpulleys, or any other method that will simulate a uniformlydistributed load by concentrated loads. If the loads are appl
23、iedby jacks, distribute the bearing forces over a sufficient area topreclude local damage. Where a uniformly distributed load isrepresented by dead weights such as masonry units, metalingots, or other materials of known weight, they shall be placedso as to preclude any arch action or bridging effect
24、 in theloading material which can affect the induced bending stresses.8.4 Concentrated LoadWhen a floor or roof is designedfor a concentrated load or loads in addition to a uniform load,a concentrated load test shall also be performed that simulatesthe actual condition of loading. If the bearing are
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME196200620121875STANDARDPRACTICEFORGRAVITYLOADTESTINGOFFLOORSANDLOWSLOPEROOFS 地面 屋顶 重力 荷载 测试 标准 实施

链接地址:http://www.mydoc123.com/p-527110.html