ASTM D4084-2007(2012) Standard Test Method for Analysis of Hydrogen Sulfide in Gaseous Fuels (Lead Acetate Reaction Rate Method)《气体燃料中硫化氢分析的标准试验方法(醋酸铅反应速率法)》.pdf
《ASTM D4084-2007(2012) Standard Test Method for Analysis of Hydrogen Sulfide in Gaseous Fuels (Lead Acetate Reaction Rate Method)《气体燃料中硫化氢分析的标准试验方法(醋酸铅反应速率法)》.pdf》由会员分享,可在线阅读,更多相关《ASTM D4084-2007(2012) Standard Test Method for Analysis of Hydrogen Sulfide in Gaseous Fuels (Lead Acetate Reaction Rate Method)《气体燃料中硫化氢分析的标准试验方法(醋酸铅反应速率法)》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D4084 07 (Reapproved 2012)Standard Test Method forAnalysis of Hydrogen Sulfide in Gaseous Fuels (LeadAcetate Reaction Rate Method)1This standard is issued under the fixed designation D4084; the number immediately following the designation indicates the year oforiginal adoption or, in th
2、e case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the determination of hydrogensulfide (H2S) in gaseous fuels. I
3、t is applicable to the measure-ment of H2S in natural gas, liquefied petroleum gas (LPG),substitute natural gas, landfill gas, sewage treatment off gasses,recycle gas, flare gasses, and mixtures of fuel gases. Thismethod can also be used to measure the hydrogen sulfideconcentration in carbon dioxide
4、. Air does not interfere. Theapplicable range is 0.1 to 16 parts per million by volume(ppm/v) (approximately 0.1 to 22 mg/m3) and may be extendedto 100 % H2S by manual or automatic volumetric dilution.1.2 This standard does not purport to address all of thesafety concerns, if any, associated with it
5、s use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D1193 Specification for Reagent WaterD1914 Practice for Conversion Unit
6、s and Factors Relating toSampling and Analysis of AtmospheresD2420 Test Method for Hydrogen Sulfide in LiquefiedPetroleum (LP) Gases (Lead Acetate Method)D3609 Practice for Calibration Techniques Using Perme-ation TubesD7166 Practice for Total Sulfur Analyzer Based On-line/At-line for Sulfur Content
7、 of Gaseous FuelsE2165 Practice for Establishing an Uncertainty Budget forthe Chemical Analysis of Metals, Ores, and RelatedMaterials (Withdrawn 2007)33. Summary of Test Method3.1 Measurement of H2S is accomplished by ratiometricallycomparing a reading of an unknown sample with that of aknown standa
8、rd using a differential colorimetric detection.Pure H2S is used as a primary standard and mixed volumetri-cally with a sulfur free matrix gas that is ideally similar incomposition to the sample gas. A gaseous sample at constantflow is humidified and passed over lead-acetate-impregnatedpaper. H2S rea
9、cts with lead acetate to form a brown stain on thepaper. The rate of reaction and resulting rate of color change isproportional to the concentration of H2S in the sample. Theanalyzer is comprised of an optical system, a photon detectionsystem, a signal differentiation system of first order, and asig
10、nal output system. When there is no change in the color ofthe tape, and no resulting change in photodetector output, E,the first derivative, dE/dt, is zero. This results in an analyzerthat automatically zeroes when there is no H2S.4. Significance and Use4.1 This test method is useful in determining
11、the concentra-tion of hydrogen sulfide in gaseous samples and in verifyingcompliance with operational needs and/or environmental limi-tations for H2S content. The automated performance operationof this method allows unattended measurement of H2S con-centration. The user is referred to Practice D7166
12、 for unat-tended on-line use of instrumentation based upon the leadacetate reaction rate method.5. Apparatus5.1 Volumetric Measuring DevicesA graduated 10-L cyl-inder (see Fig. 1) having a movable piston for volumetricallymeasuring test gas. Gastight syringes of 0.1 and 0.5-mLvolume for volumetrical
13、ly measuring 100 % H2S. Gas tightsyringes of other volumes can be used. These graduateddevices are not needed when the permeation tube method ofdynamic mixing is used to prepare the reference sample sincethis method will generate a reference mixture.5.2 Sample PumpA pump capable of providing more th
14、an8 mL/s (approximately 1 ft3/h) or less than 1 mL/s at 70 kPa(approximately 10.15 psig). Gas-wetted parts are ideally con-structed from either aluminum or polytetrafluorethylene1This test method is under the jurisdiction ofASTM Committee D03 on GaseousFuels and is the direct responsibility of Subco
15、mmittee D03.05 on Determination ofSpecial Constituents of Gaseous Fuels.Current edition approved Nov. 1, 2012. Published December 2012. Originallyapproved in 1981. Last previous edition approved in 2007 as D4084 07. DOI:10.1520/D4084-07R12.2For referenced ASTM standards, visit the ASTM website, www.
16、astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3The last approved version of this historical standard is referenced onwww.astm.org.Copyright ASTM International, 100 Bar
17、r Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1(PTFE). Stainless steel may be used when higher safety thanafforded by aluminum or PTFE is required.5.3 Colorimetric Rate of Reaction SensorSelect a deviceof sufficient sensitivity to measure a minimum rate of changeof colo
18、r density corresponding to 0.1-ppm H2S by volume inthe sample gas. (See Fig. 2.)5.4 Recorder, having an adjustable span of 1 to 10-V fullscale with an input impedance of 1 M or higher. A printer orother output means, such as a data logger or DistributedControl System (DCS) , can be used.6. Reagents
19、and MaterialsNOTE 1Warning: Hydrogen Sulfide contained in lecture bottles,permeation tubes or compressed gas cylinders may be flammable andharmful or fatal if ingested or inhaled. Lecture bottles, permeation tubesand compressed gas standards should only be handled in well ventilatedlocations away fr
20、om sparks and flames. Improper handling of compressedgas cylinders containing air, nitrogen or hydrocarbons can result inexplosion. Rapid release of nitrogen or hydrocarbon gasses can result inasphyxiation. Compressed air supports combustion.6.1 Acetic Acid SolutionAdd 50 mL of glacial acid(CH3COOH)
21、 to distilled water or dionized water to make 1 LFIG. 1 Calibration Sample Preparation Cylinder withMovable PistonFIG. 2 Flow System for H2S Measurement Showing Calibration, LPG, and Gaseous Sample ConnectionsD4084 07 (2012)2of solution (5 %). Type II distilled water as specified inSpecification D11
22、93 is satisfactory for the dilution. Waterdionized to 1 megaohm-centimeter is also satisfactory for thedilution.6.2 Reference Gas:6.2.1 Hydrogen Sulfide Source99.5 % by volume purity orbetter. An alternative H2S source is an H2S mixture obtainedusing permeation tube procedures. Hydrogen sulfide gene
23、ratedfrom a solid heated to generate H2S may be used instead of aH2S source if desired. H2S contained in permeation tubes orcompressed gas cylinders may be flammable and harmful orfatal if ingested or inhaled. Permeation tubes and compressedgas standards should only be handled in well ventilatedloca
24、tions away from sparks and flames. (WarningHydrogensulfide is an extremely toxic gas.)6.2.2 Dilution GasesChemically pure grade or purifiedgas. Blend or obtain a sulfur-free gas of the same relativedensity as the sample gas to be analyzed. Blends of gases, ofsimilar composition to the sample gas, ar
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD408420072012STANDARDTESTMETHODFORANALYSISOFHYDROGENSULFIDEINGASEOUSFUELSLEADACETATEREACTIONRATEMETHOD

链接地址:http://www.mydoc123.com/p-516247.html