《ASTM D2219-2011 Standard Specification for Poly(Vinyl Chloride) Insulation for Wire and Cable 60&x00B0 C Operation《在60 ℃环境中使用的电线和电缆的聚乙烯(氯乙烯)绝缘层的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM D2219-2011 Standard Specification for Poly(Vinyl Chloride) Insulation for Wire and Cable 60&x00B0 C Operation《在60 ℃环境中使用的电线和电缆的聚乙烯(氯乙烯)绝缘层的标准规格》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D2219 11An American National StandardStandard Specification forPoly(Vinyl Chloride) Insulation for Wire and Cable, 60COperation1This standard is issued under the fixed designation D2219; the number immediately following the designation indicates the year oforiginal adoption or, in the c
2、ase of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This specification covers a thermoplastic insulation ofpoly(vinyl chloride) or the copol
3、ymer of vinyl chloride andvinyl acetate.1.2 This insulation is recommended for use at conductortemperatures not in excess of 60C in wet or dry locations at amaximum voltage rating of 600 V for power and controlcircuits.1.3 In many instances, the insulation material cannot betested unless it has been
4、 formed around a conductor or cable.Therefore, tests are done on insulated wire or cable in thisspecification solely to determine the relevant property of theinsulation material and not to test the conductor or completedcable.1.4 The values stated in inch-pound units are to be regardedas standard. T
5、he values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4.1 In some cases (including the title), temperatures aredescribed in degrees Celsius only.2. Referenced Documents2.1 ASTM Standards:2D1711 Terminology Relat
6、ing to Electrical InsulationD2633 Test Methods for Thermoplastic Insulations andJackets for Wire and Cable3. Terminology3.1 Definitions:3.1.1 For definitions of terms used in this specification, referto Terminology D1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 aging (act of), nexpos
7、ure of materials to air or oil ata temperature and a time as specified in Table 1.4. Physical Properties4.1 The insulation shall conform to the requirements forphysical properties prescribed in Table 1.5. Electrical Requirements5.1 Perform the ac voltage, insulation resistance, and dcvoltage tests i
8、n that order when any of these tests are required.The sequence for other testing is not specified.5.2 AC Voltage TestTest the insulated conductor at the acwithstand voltage as specified in Table 2. Unless otherwisespecified, omit this test if the dc withstand voltage testdescribed in 5.4 is performe
9、d.5.2.1 For cables or conditions of service where mechanicalstresses govern, such as in vertical risers, it is possible that theminimum conductor sizes in Table 2 are not strong enough.5.2.2 The thicknesses given in Table 2 apply to aerial cablesand to single conductors installed in conduits above g
10、round andto the individual conductors of all multiple-conductor cables1This specification is under the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct responsibility ofSubcommittee D09.18 on Solid Insulations, Non-Metallic Shieldings and Covering
11、sfor Electrical and Telecommunication Wires and Cables.Current edition approved Aug. 1, 2011. Published August 2011. Originallyapproved in 1963. Last previous edition approved in 2007 as D2219 02(2007)e1.DOI: 10.1520/D2219-11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orco
12、ntact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.TABLE 1 Physical Properties RequirementsUnaged Requirements:Tensile strength, min, psi (MPa) 1500 (10.3)Elongation at rupture, min, % 1
13、00Aged Requirements:After air oven test at 1006 1C for 168 h:Tubular Specimensup to size AWG 6 (13.3 mm2)Tensile strength, min, % of unaged value 65Elongation, min, % of unaged value 65Buffed die-cut Specimenssizes AWG 6 and largerTensile strength, min, % of unaged value 65Elongation, min, % of unag
14、ed value 45Heat shock, 121 6 1C no cracksHeat distortion, 121 6 1C, max, % 50Vertical flame test, after passesfive 15-s applicationsOil resistance test:After oil immersion at 70 6 1C for 4 h:Tubular Specimensup to size AWG 6 (13.3 mm2)Tensile strength, min, % of unaged value 85Elongation, min, % of
15、unaged value 85Buffed die-cut Specimenssizes AWG 6 and largerTensile strength, min, % of unaged value 80Elongation, min, % of unaged value 60Cold bend test, 106 1C for 1 h no cracks1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive,
16、 PO Box C700, West Conshohocken, PA 19428-2959, United States.having a common jacket metallic sheath or protective coveringover the assembly, except as shown in 5.2.2.1.5.2.2.1 For single-conductor cables for installation in under-ground ducts or direct earth burial, add 15 mils (0.38 mm) tothe insu
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD22192011STANDARDSPECIFICATIONFORPOLYVINYLCHLORIDEINSULATIONFORWIREANDCABLE60X00B0COPERATION 60 环境

链接地址:http://www.mydoc123.com/p-511225.html