1、Designation: B231/B231M 16Standard Specification forConcentric-Lay-Stranded Aluminum 1350 Conductors1This standard is issued under the fixed designation B231/B231M; the number immediately following the designation indicates the yearof original adoption or, in the case of revision, the year of last r
2、evision. A number in parentheses indicates the year of last reapproval.A superscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope1.1 This specification covers aluminum 135
3、0-H19 (extrahard), 1350-H16 or -H26 (34 hard), 1350-H14 or -H24 (12hard), and 1350-H142 or -H242 (12 hard), bare concentric-lay-stranded conductors constructed with a straight round centralwire surrounded by one or more layers of helically layed wires.The conductors are for general use for electrica
4、l purposes(Explanatory Note 1 and Note 2).1.2 The values stated in either SI units or inch-pound unitsare to be regarded separately as standard. The values stated ineach system may not be exact equivalents; therefore, eachsystem shall be used independently of the other. Combiningvalues from the two
5、systems may result in non-conformancewith the standard.1.2.1 For density, resistivity and temperature, the valuesstated in SI units are to be regarded as standard.NOTE 1Prior to 1975, aluminum 1350 was designated as ECaluminum.NOTE 2The aluminum and temper designations conform to ANSIStandard H35.1/
6、H35.1M. Aluminum 1350 corresponds to Unified Num-bering System A91350 in accordance with Practice E527.NOTE 3Sealed conductors that are intended to prevent longitudinalwater propagation and are further covered/insulated are also permittedwithin the guidelines of this specification.2. Referenced Docu
7、ments2.1 The following documents of the issue in effect on dateof material purchase form a part of this specification to theextent referenced herein:2.2 ASTM Standards:2B193 Test Method for Resistivity of Electrical ConductorMaterialsB230/B230M Specification for Aluminum 1350H19 Wirefor Electrical P
8、urposesB263 Test Method for Determination of Cross-SectionalArea of Stranded ConductorsB354 Terminology Relating to Uninsulated Metallic Electri-cal ConductorsB609/B609M Specification for Aluminum 1350 RoundWire, Annealed and Intermediate Tempers, for ElectricalPurposesB682 Specification for Metric
9、Sizes of Electrical ConductorsE29 Practice for Using Significant Digits in Test Data toDetermine Conformance with SpecificationsE527 Practice for Numbering Metals and Alloys in theUnified Numbering System (UNS)2.3 ANSI Documents:3ANSI H35.1 American National StandardAlloy and TemperDesignation Syste
10、m for AluminumANSI H35.1M American National Standard Alloy andTemper Designation Systems for Aluminum Metric2.4 NIST Document:4NBS Handbook 100Copper Wire Tables2.5 Aluminum Association Document:5Publication 50 Code Words for Overhead Aluminum Elec-trical Conductors3. Classification3.1 For the purpo
11、se of this specification, conductors areclassified as follows (Explanatory Note 1 and Note 2):3.1.1 Class AAFor bare conductors usually used in over-head lines.3.1.2 Class AFor conductors to be covered with weather-resistant materials, and for bare conductors where greaterflexibility than is afforde
12、d by ClassAAis required. Conductorsintended for further fabrication into tree wire or to be insulatedand laid helically with or around aluminum or ACSRmessengers, shall be regarded as Class A conductors withrespect to direction of lay only (see 7.4).1This specification is under the jurisdiction of A
13、STM Committee B01 onElectrical Conductors and is the direct responsibility of Subcommittee B01.07 onConductors of Light Metals.Current edition approved Oct. 1, 2016. Published October 2016. Originallyapproved in 1948. Last previous edition approved in 2012 as B231/B231M 12.DOI: 10.1520/B0231_B0231M-
14、16.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANS
15、I), 25 W. 43rd St.,4th Floor, New York, NY 10036.4Available from National Technical Information Service (NTIS), U.S. Depart-ment of Commerce, 5285 Port Royal Rd., Springfield, VA 22161.5Available from the Aluminum Association, Inc., 900 19th Street, NW, Suite300, Washington, DC 20006.Copyright ASTM
16、International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.1.3 Class BFor conductors to be insulated with variousmaterials such as rubber, paper, varnished cloth, and so forth,and for the conductors indicated under Class A where greaterflexibility is require
17、d.3.1.4 Classes C and DFor conductors where greaterflexibility is required than is provided by Class B conductors.4. Ordering Information4.1 Orders for material under this specification shall includethe following information:4.1.1 Quantity,4.1.2 Conductor size: square millimetres, if cross-sectional
18、area is specified as a requirement (Section 8 and Tables 1-4),4.1.2.1 Conductor size, number, and diameter of wires forClass B, C, or D conductors, if cross-sectional area is notspecified as a requirement (see 8.2),4.1.3 Class (see 3.1),4.1.4 Temper (see 5.1),4.1.5 Details of special-purpose lays, w
19、hen required (see 7.2through 7.5),4.1.6 Special tension tests if required (see 14.1 and 15.1),4.1.7 Package size and type (see 17.1 and Table 1 or Table2),4.1.8 Special package marking, if required (Section 19),4.1.9 Heavy wood lagging, if required (see 18.2),4.1.10 Place of inspection (Section 17),
20、 and4.1.11 Method of cross-sectional area determination if notoptional (see 12.1).5. Requirements for Wires5.1 Aluminum wire employed in ClassesAAandAconduc-tors shall be 1350-H19, unless otherwise specified. The pur-chaser shall designate the temper of conductors of Classes B,C, and D.5.1.1 For con
21、ductor tempers other than 1350-H19, whentemper designations are not more specific in the inquiry andpurchase order, the manufacturer shall have the followingoptions on manufacturing method:5.1.1.1 Strand the conductor from wires drawn to finaltemper;5.1.1.2 Strand the conductor from wires drawn to H
22、19temper and annealed to final temper prior to stranding;5.1.1.3 Strand the conductor from 1350-H19 wires andanneal the stranded conductor to final temper.5.2 Before stranding, the aluminum wire used shall meet therequirements of Specifications B230/B230M or B609/B609M,whichever is applicable.5.3 Al
23、l wires in the conductor shall be of the same temper.6. Joints6.1 Only cold-pressure joints or electric-butt, cold-upsetjoints may be made in the six outer finished wires of (1) ClassAA conductors composed of seven wires or (2) Class Aconductors composed of seven wires used in overhead lines. Inothe
24、r conductors, electric-butt welds, cold-pressure welds, orelectric-butt, cold-upset welds may be made in the finishedwires composing conductors, but such welds shall not be closerthan prescribed in Table 5 (Explanatory Note 3).7. Lay7.1 For Class AA conductors composed of seven wires ormore, the pre
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB231B231M2016STANDARDSPECIFICATIONFORCONCENTRICLAYSTRANDEDALUMINUM1350CONDUCTORS 同心 式绞合铝 1350 导体
链接地址:http://www.mydoc123.com/p-460692.html