ASHRAE LO-09-012-2009 Capture and Containment Ventilation Rates for Commercial Kitchen Appliances Measured during RP-1362《RP-1362期间测量的商业厨房用具的俘获和密闭通风》.pdf
《ASHRAE LO-09-012-2009 Capture and Containment Ventilation Rates for Commercial Kitchen Appliances Measured during RP-1362《RP-1362期间测量的商业厨房用具的俘获和密闭通风》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LO-09-012-2009 Capture and Containment Ventilation Rates for Commercial Kitchen Appliances Measured during RP-1362《RP-1362期间测量的商业厨房用具的俘获和密闭通风》.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、2009 ASHRAE 161This paper is based on findings resulting from ASHRAE Research Project RP-1362.INTRODUCTIONThe capture and containment (C&C) exhaust ventilation rates for commercial cooking appliances currently published in the ASHRAE Applications Handbook, Kitchen Ventilation, Chapter 30 (ASHRAE, 20
2、05) were obtained through a consensus of industry representatives, including hood manu-facturers, appliance manufacturers, kitchen designers, and foodservice consultants. To support this consensus, the body of research regarding capture and containment to date has been significant. However, many app
3、liance types have not been documented and others need review. The test matrix for the ASHRAE RP-1362 work statement identified 20 addi-tional appliances to be tested with the goal of improving the heat gain information available in Table 5, Recommended Rates of Heat Gain from Typical Commercial Cook
4、ing Appli-ances, in Chapter 31 (ASHRAE, 2008) and provide expanded data for Chapter 30. To compliment the specified appliances, refrigeration equipment was added to the test matrix. The compilation of new capture and containment data, in parallel with new heat gain data, will support the efforts of
5、ASHRAE in providing engineers with better design guidelines for commercial kitchen ventilation systems. The information regarding the heat gain evaluation can be found in the technical paper titled Revised Heat Gain Rates from Typical Commer-cial Cooking Appliances from RP-1362 (Swierczyna, et al, 2
6、008), as well as in the main project report titled ASHRAE Research Project 1362 Revised Heat Gain and Capture and Containment Exhaust Rates from Typical Commercial Cook-ing Appliances (Swierczyna, et al, 2008).The capture and containment performance of the hooded equipment was characterized by the t
7、hreshold capture and containment exhaust airflow rate as determined in accordance with ASTM F1704-05 Standard Test Method for Capture and Containment Performance of Commercial Kitchen Exhaust Ventilation Systems (ASTM, 2005). The capture and contain-ment conditions were established for full-load coo
8、king condi-tions using two full-scale schlieren systems and one shadowgraph system that allow visualization of the thermal and cooking plumes in real time (Schmid, et al, 1997). Heavy-load cooking or simulation was conducted in accordance with the appropriate ASTM performance test methods or as othe
9、r-wise recommended and endorsed by the project monitoring sub-committee (PMS) (ASTM, 2008).In this paper, exhaust capture and containment rates are discussed. First, the data is summarized across all appliance duty classes. Then, the impact of side panels on capture and containment performance is pr
10、esented. Next, a more detailed review of the capture and containment results are presented by duty class, including the extra-heavy, heavy, medium, and light duty classes, as well as typically unhooded equipment that could operate as hooded equipment. Lastly, capture and containment exhaust rates th
11、at greatly differed from the rates established for the duty class are highlighted, along with potential duty class reclassification. EXPERIMENTAL DESIGNAppliance Specifications and CalibrationAppliances were specified and chosen according to Table 5, Recommended Rates of Heat Gain from Typical Comme
12、r-Capture and Containment Ventilation Rates for Commercial Kitchen Appliances Measured during RP-1362Paul Sobiski Rich Swierczyna Don Fisher, PEMember ASHRAE Associate Member ASHRAE Associate Member ASHRAEPaul Sobiski is a research engineer and Rich Swierczyna is a lab operations manager at the Arch
13、itectural Energy Corp., Commercial Kitchen Ventilation Laboratory, Wood Dale, IL. Don Fisher is CEO with Fisher-Nickel, Inc., San Ramon, CA.LO-09-012 (RP-1362) 2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 200
14、9, vol. 115, part 2. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.162 ASHRAE Transactionscial Cooking Appliances. The appliances were calibrated according to the appropriate AST
15、M Standard Test Methods. In selected cases, derivatives of the test procedures, as approved by the PMS, were applied to the appliance under consider-ation. In other cases, the ASTM Standard Test Method did not exist and the calibration was performed to represent the typical operation of the applianc
16、e.Appliance/Hood RelationshipsThe horizontal distance from the hood to the appliance, typically referred to as hood overhang, may seem to be a straightforward measurement. However, variations are possi-ble. At the appliance, the overhang can be measured to the cooking surface or to the vertical surf
17、ace of the appliance. At the hood, the overhang can be measured to the outside edge of the hood, or the inside edge if there are performance-enhanc-ing features.The appliance was usually located in the right hand posi-tion of a three-appliance cook line. It was positioned under the 10-foot hood at a
18、 12.0-inch (305 mm) front overhang, and a 6.0-inch (153 mm) side overhang. The dimensions were measured from the edge of the hood to the cooking surface, in most cases. For appliances where this was not practical, such as ovens, the vertical skin of the appliance was used. Hood SpecificationsMost of
19、 the hooded appliances were evaluated under a wall-mounted canopy hood that measured 10 feet long by 4 feet deep by 2 feet tall (3.05 m by 1.22 m by 0.61 m). It was equipped with six 19.6-inch by 19.6-inch by 1.8 inch (498 mm by 498 mm by 46 mm) cyclone-type grease filters, and exhausted through a 3
20、6.0-inch by 12.0-inch (914 mm by 305 mm) exhaust collar. This collar transitioned to the existing 24.0-inch (610 mm) exhaust ductwork over a height of 36.0 inches (914 mm). To represent a generic application, the canopy hood was specified to have no performance-enhancing features such as flanges or
21、interior geometric features. The hood was equipped with open hems on three sides of the hood to accommodate the mounting of side panels or hood exten-sions. The front lower edge of the hood was located at 6.50 feet (1.98 m) above the finished floor. A 6.0-inch (153 mm) fascia was attached between th
22、e top of the hood and the suspended ceiling. To facilitate visualization along all edges of the hood, it was mounted to a clear back wall, which makes the hood appear to be without a back wall in photographs throughout the paper. A photograph of a typical setup is shown in Figure 1.Alternative hoods
23、 were used as needed to accommodate unique appliance dimensions. For appliances requiring a canopy hood greater than 4 feet (1.22 m) deep, a 1-foot (0.30 m) extension was added to the canopy hood. This modification provided a consistent hood design and quick-change capabil-ity, compared to removing
24、and installing alternative exhaust hoods. For appliances requiring a 5-foot (1.52 m) deep canopy hood but better tested on an individual basis, a 5 foot by 5-foot (1.52 m by 1.52 m) wall-mounted canopy hood was used. Appliances such as dishwashers and holding cabinets were well suited for this hood.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELO090122009CAPTUREANDCONTAINMENTVENTILATIONRATESFORCOMMERCIALKITCHENAPPLIANCESMEASUREDDURINGRP1362RP1362

链接地址:http://www.mydoc123.com/p-455299.html