ASHRAE 135 ERTA-2016 BACnet - A Data Communication Protocol for Building Automation and Control Networks.pdf
《ASHRAE 135 ERTA-2016 BACnet - A Data Communication Protocol for Building Automation and Control Networks.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 135 ERTA-2016 BACnet - A Data Communication Protocol for Building Automation and Control Networks.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、135-2016 Errata October 25, 2016 2016 ASHRAE. All rights reserved 1BACnet Errata ANSI/ASHRAE STANDARD 135-2016 A Data Communication Protocol for Building Automation and Control Networks October 25, 2016 This document lists all known errata to ANSI/ASHRAE Standard 135-2016 as of the above date. Each
2、entry is cited first by clause, then page number, except where an erratum covers more than one clause. The back page marking identifying the electronic publication of Standard 135-2016 is “Product code: D-86451 6/16”. Changes are indicated by using strikeout for text to be removed and italics for te
3、xt to be added, unless noted otherwise. 1) Clause 4.1, p. 12: The list of standard datalink layer options for BACnet is misformatted. Ethernet (ISO 8802-3) Clause 7 ARCNET (ATA 878.1) Clause 8 MS/TP Cause9P l 10 LonTalk (ISO/IEC 14908.1) Clause 11 BACnet/IP Annex J BACnet/IPv6 Annex U ZigBee Annex O
4、 ZigBee Annex O 2) Table 13-7, p. 602: UNSIGNED RANGE is misplaced outside the table. The reference to Clause 13.3.9 is not shown. Table 13-7. Standardized Event Algorithms Event Algorithm Clause NONE 13.3.17. .UNSIGNED_OUT_OF_RANGE 13.3.15 UNSIGNED_RANGE 13.3.9UNSIGNED_RANGE 3) Clause K.2.16, 2nd,
5、p. 1055: Repeated word “the“. K.2.16 BIBB - Alarm and Event Management-View and Modify-A (AE-VM-A) Device A displays and modifies limits and related parameters in standard event-initiating objects. Device A shall support DS-RP-A and DS-WP-A. The A device shall be capable of using ReadProperty to ret
6、rieve and WriteProperty to modify any of the the event and fault algorithm parameters listed in Tables K-11 and K-12. Such parameters may be present in individual properties, in event parameter properties, or in fault parameter properties. See the respective property specifications. Device A may use
7、 alternate services where support for execution of the alternate service is supported by Device B. . 135-2016 Errata October 25, 2016 2016 ASHRAE. All rights reserved 24) Clause K.2.16, 3rd, p. 1055: The word “writing“ is missing. . Devices claiming conformance to AE-VM-A shall be capable of reading
8、, presenting and writing all standard properties in standard objects that are configuration parameters of standard event and/or fault algorithms that have high and low numerical limits, as listed in Tables K-11 and K-12. 5) Clause K.1.25 and K.1.26, p. 1055: The word “Multiple“ is misspelled in the
9、title. K.1.25 BIBB - Data Sharing-Change Of Value Mulitple Multiple-A (DS-COVM-A) K.1.26 BIBB - Data Sharing-Change Of Value Mulitple Multiple-B (DS-COVM-B) 6) Clause L.1, 1st, p. 1079: The second sentence is unclear. L.1 Operator Interface Profiles The following table indicates which BIBBs shall be
10、 supported by the device types of this family, for each interoperability area. The B-XAWS is excluded from this table. The B-XAWS is not shown in this table and is described in Clause L.1.1. . 7) Table 12-71, p. 518, Clause 12.56.32, p. 533, Clause J.4.3.2, p. 1028, and Clause J.4.5, 2nd, p. 1029: T
11、he references to J.7.8 are incorrect. Table 12-71. Properties of the Network Port Object Type Property Identifier Property Datatype Conformance Code Object_Identifier BACnetObjectIdentifier R. . .Profile_Name CharacterString O1 . . 9 Required to be present if the Network_Type is IPV4, Protocol_Level
12、 is BACNET_APPLICATION, and the device is capable of communicating through a NAT router as described in Clause J.7.8 J.7.5. 10 Required if Network_Type is IPV4, Protocol_Level is BACNET_APPLICATION, and the device is configured to communicate through a NAT router as described in Clause J.7.8 J.7.5.
13、. 12.56.32 BACnet_IP_NAT_Traversal This property, of type BOOLEAN, indicates whether (TRUE) or not (FALSE) this port is configured to operate in a NAT environment, as described in Clause J.7.8 J.7.5, and the global address is indicated by the value of the BACnet_IP_Global_Address property. . 135-201
14、6 Errata October 25, 2016 2016 ASHRAE. All rights reserved 3J.4.3.2 Broadcast Distribution Table Format The BDT consists of one entry for the address of the BBMD for the local IP subnet and an entry for the BBMD on each remote IP subnet to which broadcasts are to be forwarded. Each entry consists of
15、 the 6-octet B/IP address with which the BBMD is accessed and a 4-octet broadcast distribution mask. If the IP router to the subnet performs network address translation (NAT), then the BDT entry shall contain the global IP address of the IP router. The operation of BBMDs in the presence of NAT is de
16、scribed in Clause J.7.8 J.7.5. If messages are to be distributed on the remote IP subnet using directed broadcasts, the broadcast . J.4.5 BBMD Operation - Broadcast Distribution . address as well as to each foreign device currently in the BBMDs FDT. A BBMD on a subnet with no other BACnet devices (s
17、uch as a NAT-supporting BBMD, see Clause J.7.8 J.7.5) may omit the broadcast using the B/IP broadcast address. The method by which a BBMD determines whether or not other BACnet devices are present is a local matter. 8) Clause W.10, 2nd, p. 1209: The word “it“ on first line of 2ndparagraph should be
18、“its“. W.10 Representation of Metadata If metadata items are represented as part of their associated data item, they are represented in a brief “short form“ because their type is fixed and therefore assumed. The “short form“ encodes only the metadata name and its value or children. For example, when
19、 included along with it its associated data item, (e.g., /path/to/example), the minimum metadata is encoded as: 9) Clause 12.56.55, 2nd, p. 537: The reference to Clause 12 is misleading. 12.56.55 Auto_Slave_Discovery . Slave detection shall be accomplished by the proxy device using ReadProperty serv
20、ices to read, at a minimum, the Device objects Protocol_Services_Supported property for each MAC address on the network connected to this port. The ReadProperty service shall use the special object instance of 4194303 as described in Clause 12 Clause 15.5.2. If the device is found to support executi
21、on of the Who-Is service, it is ignored; otherwise, the device shall be added to the Slave_Address_Binding property. The slave detection algorithm shall be repeated periodically. The period at which it is repeated is a local matter. 10) Clause 21, BACnetPropertyIdentifier, p. 845: The word “see“ is
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE135ERTA2016BACNETADATACOMMUNICATIONPROTOCOLFORBUILDINGAUTOMATIONANDCONTROLNETWORKSPDF

链接地址:http://www.mydoc123.com/p-454143.html