ARMY MIL-PRF-12574 M-1997 REFRIGERATION UNITS MECHANICAL PANEL TYPE 5000 BTU FOR REFRIGERATOR FIELD PORTABLE (150 CUBIC FOOT) [Use In Lieu Of ARMY MIL-R-0012574 L]《可携带野地制冷器5000 BTU.pdf
《ARMY MIL-PRF-12574 M-1997 REFRIGERATION UNITS MECHANICAL PANEL TYPE 5000 BTU FOR REFRIGERATOR FIELD PORTABLE (150 CUBIC FOOT) [Use In Lieu Of ARMY MIL-R-0012574 L]《可携带野地制冷器5000 BTU.pdf》由会员分享,可在线阅读,更多相关《ARMY MIL-PRF-12574 M-1997 REFRIGERATION UNITS MECHANICAL PANEL TYPE 5000 BTU FOR REFRIGERATOR FIELD PORTABLE (150 CUBIC FOOT) [Use In Lieu Of ARMY MIL-R-0012574 L]《可携带野地制冷器5000 BTU.pdf(24页珍藏版)》请在麦多课文档分享上搜索。
1、I INCH-POUND I h MIL-PRF-12574M 9 June 1997 SUPERSEDING MIL-R-0012574L (GL) 22 May 1992 MIL-R-12574K 30 June 1988 Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: U.S. Army Natick Research, Devel
2、opment, and Engineering Center, Natick, MA 01760-5018 by using the self-addressed Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter. 1 PERFORMANCE SPECIFICATION REFRIGERATION UNITS, MECHANICAL, PANEL TYPE, 5000 BTU REFRIGERATOR, FIELD, PO
3、RTABLE (150 CUBIC FOOT) FOR This specification is approved for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This document covers two types of panel type, mechanical, refrigeration units having a capacity of 5000 British thermal units (Btu) per hour and used w
4、ith a 150-cubic foot, portable field refrigerator (see 6. i) . 1.2 Classification. The refrigeration units will be of the following types as specified (see 6.2): Type I - Diesel Engine Driven Type II - Electric Motor Driven 2. APPLICABLE DOCUMENTS AMSC N/A FSC 4110 Provided by IHSNot for ResaleNo re
5、production or networking permitted without license from IHS-,-,-MIL-PRF-12574M 2.2 2 nts. 2.2.1 d . The following standards form part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in the issue of the Department of Defense
6、Index of Specifications and Standards (DoDISS) and supplement thereto, cited in the solicitation (see 6.2) . STAN DARDS DEPARTMENT OF DEFENSE MIL-STD- 4 6 1 - Requirements for the Control of Electromagnetic Interference Emissions and Susceptibility Characteristics Guidelines MIL-STD-462 - Measuremen
7、t of Electromagnetic Interference MIL-STD-8 10 - Environmental Test Methods and Engineering MIL-STD-147 4 - Noise Limits for Military Materiel (Metric) (Unless otherwise indicated, copies of the above standards are available from the Standardization Document Order Desk, 700 Robbins Avenue, Building
8、4D, Philadelphia, PA 19111-5094). 2.3 Non-Government publications. The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of the documents which are .DoD adopted are those listed in the issue of the DoDISS cited in the solicitation
9、. Unless otherwise specified, the issues of documents not listed in the DoDISS are the issues of the documents cited in the solicitation (see 6.2). NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION Standards Publication No. 250 - Enclosures for Electrical E quipme n t (Application for copies should be a
10、ddressed to the National Electrical Manufacturers Association, 1300 No. 17th Street, Suite 1847, Rosslyn, VA 22209). NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) Standard No. 70 - National Electrical Code 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-
11、,-,-I MIL-PRF-12574M 9999906 2042908 140 MIL-PRF-12574M (Application for copies should be addressed to the National Fire Protection Association, One Battery March Park, Quincy, MA 02269-9101). UNDERWRITERS LABORATORIES INC. (UL) Standard 207- Refrigerant Containing Components and Standard 486- Wire
12、Connectors and Solder Lugs Accessories, Nonelectrical (Application for copies should be addressed to the Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096). 2.4 Order of mecedence. In the event of a conflict between the text of this document and the references cited here
13、in, the text of this document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 First article. When specified (see 6.2), a sample shall be subjected to first article inspection in accorda
14、nce with 4.1.1. 3.2 op eratinu recruirements. Refrigeration units shall satisfy the following functional, operational and performance requirements. 3.2.1 4-hour oneration. Refrigeration units shall operate properly with suction and discharge pressures safely controlled. 3.2.2 72-hour operation. Refr
15、igeration units shall operate properly and maintain noted conditions at thermostat settings of OF and 35F. 3.2.3 Refrigeration can acitv. Refrigeration units shall have minimum net capacities of 5,000 Btu/hr at a thermostat setting of OF and 7,500 Btu/hr at a thermostat setting of 35F. 3.2.4 Defrost
16、 svstem. Refrigeration units shall have a defrost cycle terminated by temperature, automatically initiated by a time control adjustable between 6 and 24 hours and have the capacity to produce not less than 6 pounds of condensate within 30 minutes. 3.2.5 Moisture content. The moisture content of the
17、refrigeration system shall be kept at a minimum to maintain proper operation of the refrigeration unit. 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-12574M 3.2.6 Refriaerant leakaue. Refrigerant containing components shall be gastight. 3
18、.2.7 Operation time. Type I refrigeration units shall operate for a minimum of 38 hours without refueling. 3.2.8 Control panel. The refrigeration units shall have a control panel for the operator having, but not limited to, the following items: 1. 2. 3. 4. 5. 6. 7. 8. 9. Start, run, stop control Ope
19、ration indicator Refrigerator temperature control Refrigeration unit running time indicator High and low side pressure indicators Refrigerator interior temperature indicator Defrost operation indicator Fuel capacity indicator for type I units Battery charging circuit voltage indicator for type I uni
20、ts 3.2.9 Ozone-deDletina substances. The refrigerant shall be commercially available nonozone-depleting, and environmentally safe. Class I ozone-depleting substances, as determined by the Environmental Protection Agency, shall not be contained in, and shall be prohibited from use during the fabricat
21、ion of the refrigeration units (see 6.6) . 3.2.10 TemDerature control. The selected temperature of the refrigeration units shall be controlled automatically. temperature control shall allow an incremental selection of normal refrigerator temperatures. The 3.2.11 1 Di . Unless otherwise specified for
22、 type I refrigeration units (see 6.2), the diesel engines electrical system shall operate on 12-volt direct current (DC). The engine shall operate on diesel and JP-8 fuels. 3.2.12 Power reauirements. Unless otherwise specified for type II refrigeration units (see 6.2), the refrigeration units shall
23、operate on 208/230 volt, 3-phase, 60-hertz (Hz) and 3-phase, 50-Hz power on the voltage specified in the contract or order (see 6.2). 3.2.13 Finish. The refrigeration units except where detrimental to proper operation shall have a nontoxic chemical agent resistant green finish (see 6.7.1). The word
24、“CARC“, together with the month and year of finishing, shall be stencilled near the identification plate in block letters not less than 1 inch high using lusterless 4 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-. NIL-PRF-12574M m 9999906 2042930
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILPRF12574M1997REFRIGERATIONUNITSMECHANICALPANELTYPE5000BTUFORREFRIGERATORFIELDPORTABLE150CUBICFOOTUSEINLIEUOFARMYMILR0012574L

链接地址:http://www.mydoc123.com/p-446990.html