ANSI NEIS 120-2012 Standard for Installing Armored Cable (AC) and Metal-Clad Cable (MC).pdf
《ANSI NEIS 120-2012 Standard for Installing Armored Cable (AC) and Metal-Clad Cable (MC).pdf》由会员分享,可在线阅读,更多相关《ANSI NEIS 120-2012 Standard for Installing Armored Cable (AC) and Metal-Clad Cable (MC).pdf(42页珍藏版)》请在麦多课文档分享上搜索。
1、An AmericAn nAtionAl StAndArdNECA/NACMA 120-2012 Standard forInstalling Armored Cable (AC) and Metal-Clad Cable (MC)Published byNational Electrical Contractors AssociationJointly developed withNACMAStandard forInstalling Armored Cable (AC)and Metal-Clad Cable (MC)NECA/NACMA 120-2012An AmericanNation
2、al StandardPublished byNational Electrical Contractors AssociationJointly developed withNACMATMnullNOTICE OF COPYRIGHTThis document is copyrighted by NECAReproduction of these documents either in hard copy or soft (including posting on the web) is prohibited without copyright permission. For copyrig
3、ht permission to reproduce portions of this document, please contact NECA Standards hospitals, nursing homes, limited care facilities, clinics, medical and dental offices, and ambulatory care facilities, whether permanent or movableNo YesIn other than patient care areas of hospitals, for mechanical
4、protection of emergency system (critical and life-safety branches) where fishedYes Yes7 nStandard for Installing Armored Cable (AC) and Metal-Clad Cable (MC) NECA/NACMA 120Type of AC CableWhere not subject to physical damage, Type AC cable is permitted to be installed:Without insulated equipment gro
5、unding conductorWith insulated equipment grounding conductorIn patient care areas of hospitals, for mechanical protection of emergency system (critical and life-safety branches) where fishedNo YesIn patient care areas of nursing homes, limited care facilities, clinics, medical and dental offices, an
6、d ambulatory care facilities hospitals, for wiring of life safety and critical branchesNo YesAreas of nursing homes and limited care facilities wired in accordance with Chapters 1 through 4 of the NEC where the areas are used exclusively as patient sleeping roomsYes YesIn assembly occupancies, fire-
7、rated construction Yes YesIn assembly occupancies, non fire-rated constructionYes YesFor theaters, audience areas of motion picture and television studios, performance areas, and similar locations, fire-rated constructionNo YesFor theaters, audience areas of motion picture and television studios, pe
8、rformance areas, and similar locations, non fire-rated constructionYes YesFor motion picture and television studios and similar locations, permanent wiring of stage or setNo YesFor cranes and hoists (dry locations only) No YesFor elevators, dumbwaiters, escalators, moving walks, wheelchair lifts and
9、 stairway chair liftsYes YesFor information technology equipment, under raised floorsYes Yes4.4 Uses Not PermittedType AC cable is not permitted to be installed: As service-entrance conductors. Where subject to physical damage unless protected by conduit or tubing In damp or wet locations In air voi
10、ds of masonry block walls where the walls are exposed to or are subject to excessive moisture or dampness Where exposed to corrosive conditions Embedded in plaster finish on brick or other masonry in damp or wet locations4.5 Connectorsa) AC cable connectors. Fittings for connecting Type AC cable are
11、 required to be marked as suitable for such use. The identification is either on the smallest container in which the product is packaged or is on the connector itself. Select the appropriate size of n 8NECA/NACMA 120 Standard for Installing Armored Cable (AC) and MetalClad Cable (MC)cable connector
12、for the trade size of the cable. Some connectors are suitable for connecting two cables. The reference in the UL White Book for Type AC cable connectors is (AWSX).b) AC cable set-screw connectors. As provided in the UL White Book (AWEZ) for Armored Cable, connectors of the set-screw type are only pe
13、rmitted to be used with cables having steel armor. They are not acceptable on cables with aluminum armor.c) Other connectors. Connectors for Type MC cable and power and control tray cable are also suitable for use with Type AC cable when specifically indicated on the connector or the shipping carton
14、.d) Insulating bushings. Connectors or clamps that connect Type AC cable to boxes or cabinets are designed so the required insulating bushing is visible for inspection after the cable is connected. The insulating bushing is often referred to in trade jargon as a “red head.” e) Grounding. All listed
15、connectors for Type AC cable are suitable for grounding since the armor of Type AC cable serves as the equipment grounding conductor. Remove paint or other insulating material between the enclosure and the connector to ensure a proper grounding connection.Figure 4.5Connectors for Type AC and Type MC
16、 cables.9 n1. Scope5.1 DescriptionType MC cable is a factory assembly of one or more insulated current-carrying conductors and one or more equipment grounding conductors (if required) in an overall metallic sheath. MC cable is manufactured with three different types of armor in the following configu
17、rations:1. Interlocking metal-tape (steel or aluminum) (MCI)2. Interlocking metal-tape (steel or aluminum) Armor ground (MCI-A)3. Smooth metal tube (aluminum only) (MCS)4. Corrugated metal tube (copper or aluminum) (MCC)Type MC cable consists of one or more current-carrying conductors, one or more e
18、quipment grounding conductors if required, and in some cases optical fibers. MC cables containing optical fibers are designated Type MC-OF and are considered composite cables in accordance with NEC Article 770.5.2 Conductorsa) Branch circuits, Feeders, and Services. Type MC cable is permitted to con
19、tain conductors from 18 AWG through 2000 kcmil for copper and 12 AWG through 2000 kcmil for aluminum. Typical branch circuit Type MC cables have copper conductors with THHN, THHN/THWN/THWN-2 or XHHW/XHHW-2 insulation and are suitable for circuits up to 600 volts. Typical feeder and service size Type
20、 MC cables have aluminum or copper conductors with THHN/THWN-2 or XHHW/XHHW-2 insulation and are suitable for circuits up to 600 volts. Higher voltage constructions and other insulation types may be available.b) Medium voltage. Type MV cables are available with conductor insulations rated from 2,400
21、 to 35,000 volts and may be marked for use as Type MC cables. c) Fire alarm. Type MC cables intended for fire alarm/control applications have TFN, TFFN, THHN or other suitable insulation.5.3 Special MC Cable ConfigurationsIn addition to “standard” configurations used for services, feeders and branch
22、 circuits, MC cables are manufactured for the following specific applications:Fire Alarm. This Type MC cable is manufactured with either steel or aluminum armor and contains 18 through 10 AWG copper conductors with TFN, TFFN, or THHN insulation. Other appropriate conductor insulations may be used. I
23、n addition, the cable contains a bare or insulated equipment grounding conductor. Install according to NEC Article 760 or NFPA 72 National Fire Alarm and Signaling Code. Composite Cable. This Type MC-OF cable construction contains electrical power and/or control conductors with one or more optical f
24、iber elements. It is installed in accordance with the NEC Article for the type of power or control conductors involved. Composite Type MC cable is available with a PVC jacket and is suitable for direct burial in earth or in concrete. Composite Type MC cable with electric power conductors is permitte
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSINEIS1202012STANDARDFORINSTALLINGARMOREDCABLEACANDMETALCLADCABLEMCPDF

链接地址:http://www.mydoc123.com/p-437441.html