1、 1 Copyright 2012 IEEE. All rights reserved. Interpretation Section 9. Grounding methods for electric supply and communications facilities Rule 094B Grounding electrodes Made electrodes (2012 Edition, pages 28-30) (17 December 2012) IR570 The intention is to classify our service pedestal post as a m
2、ade electrode under Rule 094B. More specifically, the proposal is to construct the post out of a formed 1/8” stainless steel plate with a buried length sufficient to expose at least two square feet of the posts surface to the soil below five feet in depth to meet the requirements for a plate ground
3、under Rule 094B3c. Questions: 1. Is it the intent of Rule 094B3, “Buried wire, strips or plates,” to restrict their use to only “in areas of high soil resistivity or shallow bedrock, or where lower resistance is required than attainable with driven rods”? 2. Does Rule 094B1 (for “Made electrodes, 1.
4、 General - Where made electrodes are used, they shall, as far as practical, penetrate permanent moisture level and below the frostline.”) dictate that the requirements for driven rods per Rule 094B2 must be met unless it is impractical to meet these requirements? 3. Is the term “ferrous,” as used in
5、 Rule 094B3c (“Ferrous metal electrodes shall not be less than 6 mm (0.25 in) in thickness.”) intended to include n on-corroding, iron-bearing metals such as stainless steel? Discussion of Question 1: One opinion is that the Code expresses a preference for driven rods over other made electrodes. The
6、 language at issue is the opening to Rule 094B3 which reads, “In areas of high soil resistivity or shallow bedrock, or where lower resistance is required than attainable with driven rods, one or more of the following electrodes may be more useful.” 2 Copyright 2012 IEEE. All rights reserved. It is s
7、uggested that this language means the use of buried plates, strips, or wires as ground electrodes may only be considered when one of the listed conditions is present where high soil resistivity is encountered, where shallow bedrock is present, or where drivenrods provide more resistance than needed.
8、 It is further suggested that Rule 094 generally is organized in preference order; that each Rule may be applied only if the next preceding Rule cannot be. A different opinion is that the quoted language is not mandatory; that is, it does not set any requirement or recommendation one way or the othe
9、r, but instead is meant to call the engineers attention to conditions in which the listed grounding methods might be more appropriate than a driven rod. Furthermore, there does not seem to be any technical reason why a ground rod should be preferred over a plate, strip or wire, provided that they ar
10、e each designed and installed to provide equivalent ground resistance and current capacity. Discussion of Question 2: One opinion is that unless conditions exist where using a driven rod is impractical, a driven rod must be used for making a made electrode. Another opinion is that one can use any of
11、 the types of made electrodes listed in Rule 094B, even where a driven rod is practical. Discussion of Question 3: One opinion is that the proposed post, being manufactured from stainless steel, falls into the category of ferrous metals for Rule 094B3c, for which a minimum thickness of 6 mm is requi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- IEEENESCIR5702012ENNATIONALELECTRICALSAFETYCODE 国家 电气 安全 规范 PDF

链接地址:http://www.mydoc123.com/p-1249372.html