1、05-11 23 50 11 - 1 SECTION 23 50 11 BOILER PLANT MECHANICAL EQUIPMENT SPEC WRITER NOTES: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the project and renumber the paragraphs. 2. References to pressure in this section are gage pressure
2、unless otherwise noted. 3. The spec writer shall review the Physical Security Design Manual for VA Facilities to determine and include any Mission Critical or Life Safety requirements called out. 4. Contract drawings must include (as applicable) the VA National CAD Standards listed below: SD235011-0
3、1 Flash Tank SD235011-02 Chemical Feed System, Pumped Type SD235011-05 Boiler Blowoff Tank SD235011-06 Water Sample Coolers Boiler Water and Feedwater SD235011-07 Continuous Blowdown Heat Recovery Standard Piping Diagram SD235011-08 Boiler Chemical Feed System Shot Type SD235011-10 Anchoring Equipme
4、nt Packaged Boiler and Deaerator and Condensate Storage Tanks PART 1 - GENERAL 1.1 DESCRIPTION Feedwater deaerator, condensate and boiler feed pumps, condensate storage tank, fuel oil pumping and heating, compressed air systems, blowoff tank, blowdown heat recovery, chemical treatment systems, steam
5、 vent silencer, and other equipment that supports the operation of the boilers. 1.2 RELATED WORK A. Section 09 91 00, PAINTING. B. Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. C. Section 23 05 51, NOISE and VIBRATION CONTROL FOR BOILER PLANT. D. Section 23 07 11, HVAC, PLUMBI
6、NG, and BOILER PLANT INSULATION. E. Section 23 21 11, BOILER PLANT PIPING SYSTEMS. F. Section 22 31 11, WATER SOFTENERS. G. Section 22 67 21, WATER DEALKALIZING SYSTEM. H. Section 23 08 11, DEMONSTRATIONS and TESTS FOR BOILER PLANT. Provided by IHSNot for ResaleNo reproduction or networking permitte
7、d without license from IHS-,-,-05-11 23 50 11 - 2 I. Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS. Requirements for commissioning, systems readiness checklists, and training 1.3 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Feedwater Deaera
8、tor with Storage Tank and Accessories: 1. Drawings showing arrangement and overall dimensions of feedwater deaerator including storage tank. Show locations of tank-mounted devices. Show locations and sizes of pipe connections and access openings. Show design of all shell, head and nozzle welds. 2. W
9、eight of entire assembly empty and flooded. 3. Catalog data, drawings and specification sheets showing design and construction of feedwater deaerator, storage tank, recycle pumps, water flow control valves, safety valve, overflow control valve, water level and overflow control systems, vent orifice,
10、 vacuum breaker, alarm switches and all accessories. 4. Performance data and pressure and temperature limitations of feedwater deaerator, recycle pumps, water flow/level control valve and control system, safety valve, overflow control valve, vent orifice, vacuum breaker, alarm switches and all acces
11、sories. 5. Catalog data on oxygen test kit. 6. Oxygen sample and chemical feed probe design. 7. Deaerator inlet pressure requirements - steam and water. SPEC WRITER NOTE: Delete the following subparagraphs if not applicable. /8. Packaged feedwater deaerator/feedwater pump units: Boiler feedwater pum
12、p suction and discharge pipe sizing and arrangement. Design of support framework and access platforms./ /9. Seismic design of support framework for packaged system./ C. Condensate Storage Tank and Accessories: 1. Drawings showing arrangement and overall dimensions of tank and supports. Show location
13、s and sizes of all pipe connections and access openings. 2. Weight of entire assembly empty and flooded. 3. Design and construction (including pressure and temperature limitations) of tank, continuous blowdown heat exchanger (if provided), control valves, water level control system, level alarm swit
14、ches and all accessories. 4. Performance data on control valves and continuous blowdown heat exchanger (if provided). Refer to drawings (Schedules) for requirements. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-11 23 50 11 - 3 5. Interior Coati
15、ng: Material specification, service limitations, instructions for application, experience record under the required service conditions. SPEC WRITER NOTE: Delete Subparagraph if not applicable. /6. Continuous blowoff heat exchanger tube bundles: Dimensions, design, construction, heating surface, perf
16、ormance data. / D. Blowoff Tank and Accessories, Flash Tank: 1. Drawing showing outline dimensions, arrangement and weight of tank and accessories. Locations and sizes of all pipe connections and access openings. 2. Design and construction of tank, supports and accessories. 3. Design and performance
17、 of blowoff tank temperature control valve. E. Boiler Feed and Condensate Transfer Pumps: 1. Drawings with dimensions of assemblies of pumps and drivers. 2. Catalog data and specification sheets on design and construction of pumps, drivers and couplings (flexible-coupled units). 3. Motor efficiency
18、and power factor at full load. 4. Performance curves showing discharge head, required flow plus recirculation, NPSH required, efficiency, driver power, impeller diameter to be furnished. Refer to drawings for requirements. 5. Pressure and temperature limitations of pump unit and accessories. 6. Size
19、 and capacity of recirculation orifice. 7. Data on variable frequency drive units and pressure controllers (if VFD specified). F. Condensate Return Pumps (Electrical and/or Mechanical Types) and Vacuum Heating Pump Units: 1. Drawings with dimensions of entire unit. Drawing shall include locations an
20、d sizes of all pipe connections. 2. Catalog data and specification sheets on design and construction of pumps, receiver and accessories. 3. Catalog cuts and schematic diagram of controls. 4. Electric pump performance curves showing discharge head, flow, NPSH required, efficiency, motor power and imp
21、eller diameter to be furnished. Mechanical pump performance showing discharge head, flow, required inlet head and steam pressure. Refer to drawings for requirements. 5. Pressure and temperature limitations of pump unit. G. Fuel Oil Pumping Equipment: 1. Drawings with overall dimensions and arrangeme
22、nt of pumps, motors, couplings, bases, drip pans, duplex strainer, relief valves, back-Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-11 23 50 11 - 4 pressure control valve, entire fuel oil heating system (if provided) and supports and all access
23、ories. 2. Catalog data and specification sheets on the design and construction of pumps, motors, couplings, bases, drip pans, duplex strainer, relief valves, back pressure control valves, all valves and accessories. 3. Motor efficiency and power factor at full load. 4. Pressure and temperature limit
24、ations of pumps, duplex strainer, relief valves, back pressure control valve and all valves. 5. ASTM number and pressure rating of pipe and fittings. 6. Performance data on pumps including discharge head, flow, suction lift and motor power required at viscosity range shown. Refer to drawings for req
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2350112011BOILERPLANTMECHANICALEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-1074923.html