VA 23 40 00-2012 HVAC AIR CLEANING DEVICES.pdf
《VA 23 40 00-2012 HVAC AIR CLEANING DEVICES.pdf》由会员分享,可在线阅读,更多相关《VA 23 40 00-2012 HVAC AIR CLEANING DEVICES.pdf(19页珍藏版)》请在麦多课文档分享上搜索。
1、02-01-12 23 40 00 - 1 SECTION 23 40 00 HVAC AIR CLEANING DEVICES SPEC WRITER NOTE: Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. Air filters for heating, ventil
2、ating and air conditioning. B. Definitions: Refer to ASHRAE Standard 52.2 for definitions of face velocity, net effective filtering area, media velocity, initial resistance (pressure drop), MERV (Minimum Efficiency Reporting Value), PSE (Particle Size Efficiency), particle size ranges for each MERV
3、number, dust holding capacity and explanation of electrostatic media based filtration products versus mechanical filtration products. Refer to ASHRAE Standard 52.2 Appendix J for definition of MERV-A. 1.2 RELATED WORK A. Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION: General me
4、chanical requirements and items, which are common to more than one section of Division 23. B. Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS: Filter housing and racks. C. Section 23 73 13, PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS: Filter housing and racks. D. Section 23 08
5、00 COMMISSIONING OF HVAC SYSTEMS: Requirements for commissioning, systems readiness checklists, and training. 1.3 QUALITY ASSURANCE SPEC WRITER NOTE: Discuss the filter test age with manufacturers and revise it if different from the age stated in paragraph A.1. However, the filter test age should no
6、t be more than 5 years old. A. Air Filter Performance Report for Extended Surface Filters: 1. Submit a test report for each Grade of filter being offered. The report shall not be more than three (3) years old and prepared by using test equipment, method and duct section as specified by ASHRAE Standa
7、rd 52.2 for type filter under test and acceptable to Resident Engineer, indicating that filters comply with the requirements of this specification. Filters utilizing partial or complete synthetic media will be tested in compliance with pre-conditioning steps as Provided by IHSNot for ResaleNo reprod
8、uction or networking permitted without license from IHS-,-,-02-01-12 23 40 00 - 2 stated in Appendix J. All testing is to be conducted on filters with a nominal 24 inch by 24 inch face dimension. Test for 150 m/min (500 fpm) will be accepted for lower velocity rated filters provided the test report
9、of an independent testing laboratory complies with all the requirements of this specification. SPEC WRITER NOTE: Witness testing may be required by the Project Manager on clean room systems and bag-in bag-out systems. /2. Government Option: The Government at its option may take one of the filters fo
10、r each different type submitted and run an independent test to determine if the filter meets the requirements of this specification. When the filter meets the requirements, the Government will pay for the test. When the filter does not meet the specification requirements, the manufacturer will be re
11、quired to pay for the test and replace the filters with filters that will perform as required by the specifications./ /3. Guarantee Performance: The manufacturer shall supply ASHRAE 52.2 test reports on each filter type submitted. Any filter supplied will be required to maintain the minimum efficien
12、cy shown on the ASHRAE Standard 52.2 report throughout the time the filter is in service. Within the first 6-12 weeks of service a filter may be pulled out of service and sent to an independent laboratory for ASHRAE Standard 52.2 testing for initial efficiency only. If this filter fails to meet the
13、minimum level of efficiency shown in the previously submitted reports, the filter manufacturer/distributor shall take back all filters and refund the owner all monies paid for the filters, cost of installation, cost of freight and cost of testing. B. Filter Warranty for Extended Surface Filters: Gua
14、rantee the filters against leakage, blow-outs, and other deficiencies during their normal useful life, up to the time that the filter reaches the final pressure drop. Defective filters shall be replaced at no cost to the Government. C. Comply with UL Standard 900 for flame test. D. Nameplates: Each
15、filter shall bear a label or name plate indicating manufacturers name, filter size, rated efficiency, / UL classification, / and file number./ 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literature and Data: 1. Extended sur
16、face filters. 2. Holding frames. Identify locations. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-01-12 23 40 00 - 3 3. Side access housings. Identify locations, verify insulated doors. 4. HEPA filters. 5. Magnehelic gages. /6. Carbon Filters./
17、 C. Air Filter performance reports. D. Suppliers warranty. E. Field test results for HEPA filters as per paragraph 2.3.E.3. 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by basic de
18、signation only. B. American Society of Heating, Refrigerating and Air-conditioning Engineers, Inc. (ASHRAE): 52.2-2007.Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size, including Appendix J C. American Society of Mechanical Engineers (ASME): NQA-1-20
19、08 . Quality Assurance Requirements for Nuclear Facilities Applications D. Underwriters Laboratories, Inc. (UL): 900;Revision 15 July 2009 Test Performance of Air Filter Units SPEC WRITER NOTE: Update material requirements to agree with applicable requirements (types, grades, classes, and other rela
20、ted items) specified in the referenced Applicable Publications. DESIGNERS NOTE: The VA Master Specifications do not match with the minimum filtration requirements outlined in ASHRAE Standard 170-2008. The filtration requirements outlined in this section shall govern. PART 2 - PRODUCTS SPEC WRITER NO
21、TE: Refer to filter schedules on drawings for filter size. 2.1 REPLACEMENT FILTER ELEMENTS TO BE FURNISHED A. To allow temporary use of HVAC systems for testing and in accordance with Paragraph, TEMPORARY USE OF MECHANICAL AND ELECTRICAL SYSTEMS in Section 01 00 00, GENERAL REQUIREMENTS, provide one
22、 complete set of additional filters to the Resident Engineer. B. The Resident Engineer will direct whether these additional filters will either be installed as replacements for dirty units or turned over to VA for future use as replacements. Provided by IHSNot for ResaleNo reproduction or networking
23、 permitted without license from IHS-,-,-02-01-12 23 40 00 - 4 2.2 EXTENDED SURFACE AIR FILTERS A. Use factory assembled air filters of the extended surface type with supported or non-supported cartridges for removal of particulate matter in air conditioning, heating and ventilating systems. Filter u
24、nits shall be of the extended surface type fabricated for disposal when the contaminant load limit is reached as indicated by maximum (final) pressure drop. B. Filter Classification: UL listed and approved conforming to UL Standard 900. C. HVAC Filter Types HVAC Filter Types Table 2.2C MERV Value AS
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2340002012HVACAIRCLEANINGDEVICESPDF