VA 22 05 19-2010 METERS AND GAGES FOR PLUMBING PIPING.pdf
《VA 22 05 19-2010 METERS AND GAGES FOR PLUMBING PIPING.pdf》由会员分享,可在线阅读,更多相关《VA 22 05 19-2010 METERS AND GAGES FOR PLUMBING PIPING.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、02-10 22 05 19 - 1 SECTION 22 05 19 METERS AND GAGES FOR PLUMBING PIPING SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section describes the r
2、equirements for water meters and pressure gages. 1.2 RELATED WORK Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING. 1.3 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data: 1. Water Meter. 2. Pressure Gages. 3. BA
3、Cnet communication protocol 4. Product certificates for each type of meter and gauge C. Operations and Maintenance manual shall include: 1. System Description 2. Major assembly block diagrams 3. Troubleshooting and preventive maintenance guidelines 4. Spare parts information. D. Shop Drawings shall
4、include the following: 1. One line, wiring and terminal diagrams including terminals identified, protocol or communication modules, and Ethernet connections. 1.4 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are
5、referenced in the text by the basic designation only. B. American National Standards Institute (ANSI): American Society of Mechanical Engineers (ASME): (Copyrighted Society) B40.1-05 . Gauges-Pressure Indicating Dial Type-Elastic Provided by IHSNot for ResaleNo reproduction or networking permitted w
6、ithout license from IHS-,-,-02-10 22 05 19 - 2 C. American Water Works Association (AWWA): C700-07 (R 2003) . Standard for Cold Water Meters, Displacement Type, Bronze Main Case C701-07 Cold Water Meters-Turbine Type, for Customer Service AWWA/ ANSI C702-01 Cold water meters Compound Type D. Interna
7、tional Code Council (ICC): IPC-06 . (2007 Supplement) International Plumbing Code SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. 1.5 AS-BUILT DOCUMENTATION
8、 A. The electronic documentation and copies of the Operations and Maintenance Manual, approved submittals, shop drawings, and other closeout documentation shall be prepared by a computer software program complying with Section 508 of the Rehabilitation Act of 1973, as amended (29 U.S.C 794d). The ma
9、nufacturer or vendor of the software used to prepare the electronic documentation shall have a Voluntary Product Accessibility Template made available for review and included as part of the Operations and Maintenance Manual or closeout documentation. All available accessibility functions listed in t
10、he Voluntary Accessibility Template shall be enabled in the prepared electronic files. As Adobe Acrobat is a common industry format for such documentation, following the document, “Creating Accessible Adobe PDF files, A Guide for Document Authors“ that is maintained and made available by Adobe free
11、of charge is recommended.” B. Four sets of manufacturers literature and data updated to include submittal review comments and any equipment substitutions. C. Four sets of operation and maintenance data updated to include submittal review comments shall be inserted into a three ring binder. All aspec
12、ts of system operation and maintenance procedures, including piping isometrics, wiring diagrams of all circuits, a written description of system design, control logic, and sequence of operation shall be included in the operation and maintenance manual. The operations and maintenance manual shall inc
13、lude troubleshooting techniques and procedures for emergency situations. Notes on all Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 22 05 19 - 3 special systems or devices such as damper and door closure interlocks shall be included. A List o
14、f recommended spare parts (manufacturer, model number, and quantity) shall be furnished. Information explaining any special knowledge or tools the owner will be required to employ shall be inserted into the As-Built documentation. PART 2 PRODUCTS 2.1 DISPLACEMENT WATER METER A. For pipe sizes under
15、50 mm (2 inches), the water meter shall be displacement type, full size nutating disc, magnetic drive, sealed register, and fully conform to AWWA C700. Peak domestic flow shall be 2.2 L/S (34 gpm). The meter register shall indicate flow in liters (U.S. gallons). B. The water meter shall be rated for
16、 use at temperatures ranging from -40 C (-40 F) and +70 C (158 F) and operate at a working pressure of 1034 kPa (150-psig). C. The meter case, bottom caps, and register box lids shall be constructed from cast bronze. 2.2 TURBINE WATER METER A. The water meter shall be Turbine type, Class II, in-line
17、, horizontal axis, and fully conform to AWWA C701. Peak domestic flow shall be _L/S (_ gpm). The meter Register shall indicate flow in liters (U.S. gallons). B. The water meter shall be rated for use at temperatures ranging from -40 C (-40 F) and +70 C (158 F) and operate at a working pressure of 10
18、34 kPa (150-psig). C. The turbine case shall be constructed of bronze. D. The register box rings and lid shall be made of cast copper alloy containing not less that 75% copper. Forged or die cast copper alloy containing not less than 75% copper or a suitable synthetic polymer. E. The flow measuring
19、turbine shall be made of vulcanized hard rubber or suitable synthetic polymer with specific gravity approximately equal to that of water. The measuring turbine shall have sufficient dimensional stability to retain operating clearances at the full range of working temperatures. F. All external case c
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2205192010METERSANDGAGESFORPLUMBINGPIPINGPDF

链接地址:http://www.mydoc123.com/p-1074865.html