1、05-08M 21 13 13 - 1 SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS SPEC WRITER NOTES: 1. Delete between / - / if not applicable to the project. Also delete any other item or paragraph including NFPA references which are not applicable and renumber the paragraphs. 2. References to pressure in the sectio
2、n are gage pressure unless otherwise noted. 3. The spec writer shall review the Physical Security Design Manual for VA Facilities to determine and include any Mission Critical or Life Safety requirements called out. PART 1 - GENERAL SPEC WRITER NOTE: Identify all areas to be sprinkler protected incl
3、uding all buildings by number. 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The design and installation of a hydraulically calculated automatic wet system complete and ready for operation, / for all portions of Building
4、 _ /, including the / penthouse, / mechanical equipment rooms, / attic space, / telephone rooms, / elevator machine rooms, / elevator pits, / and linen chutes /. /D. Modification of the existing sprinkler system as indicated on the drawings and as further required by these specifications. / 1.2 RELA
5、TED WORK A. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Section 33 10 00, WATER UTILITIES. C. Section 07 84 00, FIRESTOPPING, Treatment of penetrations through rated enclosures. D. Section 09 91 00, PAINTING. E. Section 21 10 00, WATER-BASED FIRE-SUPPRESSION SYSTEMS, Dry sprinkler
6、s, fire pumps, etc. F. Section 21 12 00, FIRE-SUPPRESSION STANDPIPES. F. Section 28 31 00, FIRE DETECTION AND ALARM, Connection to fire alarm of flow switches, pressure switches and valve supervisory switches. G. Section 21 05 11 COMMON WORK RESULTS FOR FIRE SUPPRESSION 1.3 QUALITY ASSURANCE SPEC WR
7、ITER NOTE: Most states do not have or issue fire sprinkler contractors Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-08M 21 13 13 - 2 licenses, therefore as a minimum, the contractor must hold a contractors license in the state where the work is
8、 to be performed. A. Installer Reliability: The installer shall possess a valid State of / (insert state in which work is being performed) / fire sprinkler / contractors license. The installer shall have been actively and successfully engaged in the installation of commercial automatic sprinkler sys
9、tems for the past ten years. B. Materials and Equipment: All equipment and devices shall be of a make and type listed by UL and approved by FM, or other nationally recognized testing laboratory for the specific purpose for which it is used. All materials, devices, and equipment shall be approved by
10、the VA. C. Submittals: Submit as one package in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Prepare detailed working drawings that are signed by a NICET Level III or Level IV Sprinkler Technician or stamped by a Registered Professional Engineer practicing in the field
11、 of Fire Protection Engineering. As Government review is for technical adequacy only, the installer remains responsible for correcting any conflicts with other trades and building construction that arise during installation. / Partial submittals will not be accepted. / Material submittals shall be a
12、pproved prior to the purchase or delivery to the job site. Suitably bind submittals in notebooks or binders and provide index referencing the appropriate specification section. Submittals shall include, but not be limited to, the following: 1. Qualifications: a. Provide a copy of the installing cont
13、ractors / fire sprinkler / and state / contractors license. b. Provide a copy of the NICET certification for the NICET Level III or Level IV Sprinkler Technician who prepared and signed the detailed working drawings unless the drawings are stamped by a Registered Professional Engineer practicing in
14、the field of Fire Protection Engineering. 2. Drawings: Submit detailed 1:100 (1/8 inch) scale (minimum) working drawings conforming to NFPA 13. Include a site plan showing the piping to the water supply test location. 3. Manufacturers Data Sheets: a. For backflow preventers, provide flow test curves
15、 from UL, FM, or the Foundation for Hydraulic Research and Cross-Connection Control to verify pressure loss calculations. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-08M 21 13 13 - 3 b. Provide for materials and equipment proposed for use on t
16、he system. Include listing information and installation instructions in data sheets. Where data sheet describes items in addition to that item being submitted, clearly identify proposed item on the sheet. 4. Calculation Sheets: Submit hydraulic calculation sheets in tabular form conforming to the re
17、quirements and recommendations of NFPA 13. 5. Final Document Submittals: Provide as-built drawings, testing and maintenance instructions in accordance with the requirements in Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submittals shall include, but not be limited to, the following:
18、a. One complete set of reproducible as-built drawings showing the installed system with the specific interconnections between the waterflow switch or pressure switch and the fire alarm equipment. b. Complete, simple, understandable, step-by-step, testing instructions giving recommended and required
19、testing frequency of all equipment, methods for testing all equipment, and a complete trouble shooting manual. Provide maintenance instructions on replacing any components of the system including internal parts, periodic cleaning and adjustment of the equipment and components with information as to
20、the address and telephone number of both the manufacturer and the local supplier of each item. c. Material and Testing Certificate: Upon completion of the sprinkler system installation or any partial section of the system, including testing and flushing, provide a copy of a completed Material and Te
21、sting Certificate as indicated in NFPA 13. d. Certificates shall document all parts of the installation. e. Instruction Manual: Provide one copy of the instruction manual covering the system in a flexible protective cover and mount in an accessible location adjacent to the riser. D. Design Basis Inf
22、ormation: Provide design, materials, equipment, installation, inspection, and testing of the automatic sprinkler system in accordance with the requirements of NFPA 13. Recommendations in appendices shall be treated as requirements. 1. Perform hydraulic calculations in accordance with NFPA 13 utilizi
23、ng the Area/Density method. Do not restrict design area reductions permitted for using quick response sprinklers throughout by the required use of standard response sprinklers in the areas identified in this section. 2. Sprinkler Protection: To determining spacing and sizing, apply the following cov
24、erage classifications: Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-08M 21 13 13 - 4 SPEC WRITER NOTE: Identify all areas on the contract drawings. Show all piping including fittings and sizes for calculation purposes, from the water supply tes
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2113132008WETPIPESPRINKLERSYSTEMSPDF