UL SUBJECT 489G-2016 Outline of Investigation for Molded-Case Circuit Breakers Molded-Case Switches and Circuit-Breaker Enclosures 650 C 1000 Volts AC and 650 C 1500 Volts DC (Issu.pdf
《UL SUBJECT 489G-2016 Outline of Investigation for Molded-Case Circuit Breakers Molded-Case Switches and Circuit-Breaker Enclosures 650 C 1000 Volts AC and 650 C 1500 Volts DC (Issu.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 489G-2016 Outline of Investigation for Molded-Case Circuit Breakers Molded-Case Switches and Circuit-Breaker Enclosures 650 C 1000 Volts AC and 650 C 1500 Volts DC (Issu.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULDECEMBER 21, 20161UL 489GOutline of Investigation for Molded-Case Circuit Breakers, Molded-CaseSwitches, and Circuit-Breaker Enclosures, 650 1000 Volts AC and 650 1500 Volts DCIssue No. 1December
2、 21, 2016Summary of TopicsThis First issue of the Outline of Investigation for Molded-Case CircuitBreakers, Molded-Case Switches, and Circuit-Breaker Enclosures, 650 1000 Volts AC and 650 1500 Volts DC, covers molded-case circuitbreakers, molded-case switches, and circuit-breaker enclosures, rated a
3、t650 1000 volts AC and 650 1500 volts DC, 6000 amperes or less.ULs Outlines of Investigation are copyrighted by UL LLC. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights reg
4、ardingthose Outlines of Investigation shall remain the sole and exclusive property of ULLLC.COPYRIGHT 2016 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULDECEMBER 21, 2016UL 489G2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZE
5、D FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTS1 Scope .46 Construction 47 Tests 57.1.3 Overload Test 57.1.5 Endurance Test 77.1.7 Interrupting Test .97.1.9 Dielectric Voltage-Withstand Test 107.1.11 High Available Fault Current Test Sequence .107.2.3 Interrupting and Le
6、t-Through Measurement Test .118 Ratings .1214 Construction .1219 Performance .13DECEMBER 21, 2016 UL 489G 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL1 Scope1.1 These requirements cover molded-case circuit breakers, molded-case switches,
7、and circuit-breakerenclosures, rated at 650 1000 volts AC and 650 1500 volts DC, 6000 amperes or less. This Outlineis intended to be used with the Standard for Molded-Case Circuit Breakers, Molded-Case Switches, andCircuit-Breaker Enclosures, UL 489. Only the sections that are modified from UL 489 a
8、re included in thisOutline, all other Sections apply as written in UL 489.6 ConstructionSection 6 of UL 489 is modified as follows:Table 6.1.6.1.1Minimum spacings in millimeterse,f,gAt terminals Other than at terminalsBetween terminalsofopposite polarityBetween terminalsand anygrounded metalaBetween
9、uninsulatedlive parts ofopposite polaritybBetween uninsulatedlive parts and anyground metalaABCDcEdVoltagebetweenpartsThroughairOversurfaceThroughairOversurfaceThroughairOversurfaceThroughairOversurfaceThroughairOversurface0 130 12.7 19.1 12.7 12.7 6.4 9.5 12.7 12.7 6.4 9.5131 30019.1 31.8 12.7 12.7
10、 6.4 9.5 12.7 12.7 6.4 9.5301 60025.4 50.8 12.7 25.4 9.5 12.7 12.7 25.4 9.5 12.7650 100025.4 50.8 12.7 25.4 9.5 12.7 12.7 25.4 9.5 12.7aThe spacing to the enclosure or mounting means shall be permitted to be reduced if an acceptable liner of insulating material,not less than 0.8 mm (1/32 inch) thick
11、, is used to provide the required spacing through air.bNot applicable for spacings between parts of opposite polarity on a control circuit printed wiring board with conformal coating.See Table 6.1.6.2.1 and Printed Circuit and Wiring Board Assembly, 6.1.6.2.cIf indentation or deformation of the over
12、all enclosure or circuit breaker mounting means could reduce spacings to less thanthose indicated in Column E.dIf indentation or deformation of the overall enclosure or circuit breaker mounting means would not affect spacings.eAn isolated dead metal part (such as a screw head or a washer) interposed
13、 between uninsulated live parts of opposite polarityor between an uninsulated live part and a grounded dead metal part is considered to reduce the spacing by an amount equal tothe dimension of the interposed part along the path of measurement.fIn measuring an over surface spacing, any slot, groove,
14、or the like, 0.33 mm (0.013 inch) wide or less in the contour ofinsulating material shall be disregarded.gIn measuring spacings, an air spacing of 0.33 mm (0.013 inch) or less between a live part and an insulating surface shall bedisregarded, and the live part considered in contact with the insulati
15、ng material.mm 0.8 6.4 9.5 12.7 19.1 25.4 31.8 50.8inches 1/32 1/4 3/8 1/2 3/4 1 1-1/4 2DECEMBER 21, 2016UL 489G4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 6.1.6.2.1Minimum opposite polarity spacings on printed-wiringassemblies with
16、 conformal coatingsaMinimum spacingsVoltage between parts Power available mm Inch0 600 Unlimited 0.8 (1/32)650 1000 Unlimited 1.6 (1/16)1001 1500cUnlimited 2.4 (1/8)0 30 Limitedb0.4 (1/64)aMinimum spacing between live parts of opposite polarity. Spacing between live parts and dead metal shall comply
17、 withTable 6.1.6.1.1.bSee 6.1.6.3.1 and 6.1.6.3.2.cVolts dc.7 TestsSection 7 of UL 489 is modified as follows:7.1.3 Overload TestThis is generated text for figtxt.DECEMBER 21, 2016 UL 489G 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFigur
18、e 7.1.3.1Overload test connection diagramsA 1PoleB,C1-PoleTested in Pairs (also represents 2-Pole independent-trip type circuit breaker)D 2-Pole Common-Trip slant (120/240, 125/250 V) RatingE 2-Pole Common-Trip Rating other than DF3-PoleG 3-Pole wye connected system ratings such as 1000Y/577 VH 2-Po
19、le Common-Trip for 3-Phase RatingI 4-Pole wye connected system ratings such as 1000Y/577 VN NeutralZ Load Impedancef30Aground Fuse EnclosureDECEMBER 21, 2016UL 489G6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL7.1.5 Endurance TestThis is ge
20、nerated text for figtxt.DECEMBER 21, 2016 UL 489G 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFigure 7.1.5.1Endurance test connection diagramsA 1PoleB1-PoleTested in Pairs (also represents 2-Pole independent-trip type circuit breaker)C 2-
21、Pole Common-Trip slant (120/240, 125/250 V) RatingD 2-Pole Common-Trip Rating other than CE3-PoleF 3-Pole wye connected system ratings such as 1000Y/577 VG 2-Pole Common-Trip for 3-Phase RatingH 4-Pole wye connected system ratings such as 1000Y/577 VN NeutralZ Load Impedancef30Aground Fuse Enclosure
22、DECEMBER 21, 2016UL 489G8UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL7.1.7 Interrupting TestTable 7.1.7.1Interrupting test operationsPoles FrameratingCircuit breakerAC voltage ratingLetters indicate diagram in Figure 7.1.7.1 Totalnumber of
23、operationsOperations on each pole Common operationsOCOOOCOO1 All 650, 690, or 700 1000 A A A 32AlAny delta connected systemratings E E D 52 0 1200 AAny wye connected systemratings L L C 53 0 1200 AAny delta connected systemratings G G F 73 1200 UpAny delta connected systemratings G G F 73AlAny wye c
24、onnected systemratings K K I 74AlAny wye connected systemratings K K M 7Table 7.1.7.3Available current in test circuitsRMS symmetrical or DC amperes1 pole 2 pole 3 poleFrame rating IndividualaCommon IndividualaCommon100 A maximum, 251 1500 V 10,000 10,000 10,000 8,660b,c,d10,000aAt the option of the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT489G2016OUTLINEOFINVESTIGATIONFORMOLDEDCASECIRCUITBREAKERSMOLDEDCASESWITCHESANDCIRCUITBREAKERENCLOSURES650C1000VOLTSACAND650C1500VOLTSDCISSUPDF

链接地址:http://www.mydoc123.com/p-1069441.html