UL SUBJECT 489F-2016 UL Outline for Investigation Molded-Case Circuit Breakers and Molded-Case Switches for Use with Battery Power Supplies (Issue 2)《使用蓄电池电源供电的模制断路器和模制开关的UL调查大纲 (议.pdf
《UL SUBJECT 489F-2016 UL Outline for Investigation Molded-Case Circuit Breakers and Molded-Case Switches for Use with Battery Power Supplies (Issue 2)《使用蓄电池电源供电的模制断路器和模制开关的UL调查大纲 (议.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 489F-2016 UL Outline for Investigation Molded-Case Circuit Breakers and Molded-Case Switches for Use with Battery Power Supplies (Issue 2)《使用蓄电池电源供电的模制断路器和模制开关的UL调查大纲 (议.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJANUARY 12, 20161UL 489FOutline of Investigation for Molded-Case Circuit Breakers and Molded-CaseSwitches for Use with Battery Power SuppliesIssue Number: 2January 12, 2016Summary of TopicsThe Se
2、cond issue of the Outline of Investigation for Molded-Case CircuitBreakers and Molded-Case Switches for Use with Battery Power Supplies,UL 489F, is being issued to clarify the ratings for these devices and clarifythe test requirements for BPS switches.ULs Outlines of Investigation are copyrighted by
3、 UL. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2016 UNDERWRITER
4、S LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJANUARY 12, 2016UL 489F2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope
5、 .42 General 42.1 Components .42.2 Units of measurement .52.3 Undated references .52.4 Glossary 5MOLDED-CASE CIRCUIT BREAKERSPERFORMANCE3 General 54 Calibration Test .55 Overload Test 56 Endurance Test .67 Interrupting Test 68 Dielectric Voltage-Withstand Test .79 High Available Fault Current Test .
6、7RATINGS10 General .7MARKINGS11 General .7MOLDED CASE SWITCHESPERFORMANCE12 General .813 Overload Test .814 Endurance Test 815 Withstand Test 8RATINGS16 General .8MARKINGS17 General .8JANUARY 12, 2016 UL 489F 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PER
7、MISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover molded-case circuit breakers and molded-case switches rated greater than250 V dc but no greater than 1500 V dc and intended for use with battery power supplies (BPS) whichmay be wired with multiple poles in series, such as may be used in
8、 uninterruptible power supplies or forenergy storage in renewable energy systems. These devices are intended for use in accordance with theNational Electrical Code (NEC), ANSI/NFPA 70.1.2 A circuit breaker intended for use with battery power supplies shall comply with the applicablerequirements in t
9、he Standard for Molded-Case Circuit Breakers, Molded-Case Switches andCircuit-Breaker Enclosures, UL 489, hereafter referred to as UL 489, except as modified or supplementedby this Outline.1.3 These requirements do not cover circuit breakers rated 250 V dc or less.2 General2.1 Components2.1.1 Except
10、 as indicated in 2.1.2, a component of a product covered by this Outline shall comply withthe requirements for that component.2.1.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the component in thepr
11、oduct covered by this Outline; orb) Is superseded by a requirement in this Outline.2.1.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.1.4 Specific components are incomplete in construction features or restricted in performancecapabilities. S
12、uch components are intended for use only under limited conditions, such as certaintemperatures not exceeding specified limits, and shall be used only under those specific conditions.JANUARY 12, 2016UL 489F4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISS
13、ION FROM UL2.2 Units of measurement2.2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.2.3 Undated references2.3.1 Any undated reference to a code or standard appearing in the requirements of this Outline shall beinterpreted as
14、 referring to the latest edition of that code or standard.2.4 Glossary2.4.1 For the purpose of this Outline, the following definitions apply.2.4.2 BPS CIRCUIT BREAKER a molded-case circuit breaker intended for use in BPS systems rated greaterthan 250 V dc, but not greater than 1500 V dc.2.4.3 BPS SW
15、ITCH a molded-case switch intended for use in BPS systems rated greater than 250 V dc,but not greater than 1500 V dc.MOLDED-CASE CIRCUIT BREAKERSPERFORMANCE3 General3.1 The sample selection and performance test sequences shall be conducted as specified in UL 489,Section 7.1.4 Calibration Test4.1 The
16、 BPS CIRCUIT BREAKER shall be subjected to all of the applicable calibration and recalibration tests,including the adjustable instantaneous response calibration test specified in UL 489, Section 7.1.2.5.1.5 Overload Test5.1 The BPS CIRCUIT BREAKER shall be subjected to the overload test specified in
17、 UL 489, Section 7.1.3, atthe maximum rated voltage specified in Table 7.1. The number of operations and the test current of theoverload test shall be in accordance with Table 5.1.JANUARY 12, 2016 UL 489F 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISS
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT489F2016ULOUTLINEFORINVESTIGATIONMOLDEDCASECIRCUITBREAKERSANDMOLDEDCASESWITCHESFORUSEWITHBATTERYPOWERSUPPLIESISSUE2

链接地址:http://www.mydoc123.com/p-1069440.html