《UL SUBJECT 489D-2012 OUTLINE OF INVESTIGATION FOR US NAVAL COMMERCIAL-OFF-THE-SHELF (COTS) DESIGNATED MOLDED-CASE CIRCUIT BREAKERS AND ACCESSORIES FOR USE ON NON-NUCLEAR NAVAL COMB.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 489D-2012 OUTLINE OF INVESTIGATION FOR US NAVAL COMMERCIAL-OFF-THE-SHELF (COTS) DESIGNATED MOLDED-CASE CIRCUIT BREAKERS AND ACCESSORIES FOR USE ON NON-NUCLEAR NAVAL COMB.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAPRIL 27, 20121UL 489DOUTLINE OF INVESTIGATIONFORUS NAVAL COMMERCIAL-OFF-THE-SHELF (COTS) DESIGNATEDMOLDED-CASE CIRCUIT BREAKERS AND ACCESSORIES FOR USE ONNON-NUCLEAR NAVAL COMBATANT SHIPSIssue N
2、o. 1April 27, 2012Summary of TopicsThis is the first issue of the Outline of Investigation for US NavalCommercial-Off-the-Shelf (COTS) Designated Molded-Case CircuitBreakers and Accessories for Use on Non-Nuclear Naval CombatantShips.COPYRIGHT 2012 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERI
3、AL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAPRIL 27, 2012UL 489D2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Normative References .4CONSTRUCTION3
4、General 5RATINGS4 General 5PERFORMANCE5 Base Design .66 Initial Qualification Testing .66.1 General .66.2 Test program Q1 .76.3 Test program Q2 106.4 Test program Q3 117 Requalification Testing .127.1 General 127.2 Test program RQ1 .137.3 Test program RQ2 .137.4 Test program RQ3 .14MARKINGS8 General
5、 .14APRIL 27, 2012 UL 489D 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover commercial-off-the-shelf (COTS), three-pole and four-pole molded-casecircuit breakers and applicable accessories (under
6、voltage trip release devices, shunt trip release devices,electrical (motor) operators, auxiliary switches, plug-in mounting adapter blocks/bases, drawout cassette)intended for use aboard non-nuclear Naval combatant ships in electrical assemblies (switchboards andload centers) installed on shock isol
7、ators (mounts).1.2 Successful initial qualification testing and requalification testing of circuit breakers/accessories to therequirements of this Outline shall allow their use in shock-mounted electrical assemblies in non-nuclearNaval combatant ships.2 Normative References2.1 This Outline reference
8、s the following COTS specifications:a) UL 489, the Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosuresb) UL 489 Supplement SB, Molded-Case Circuit Breakers and Circuit Breaker Enclosures(Naval Use)c) IEC 60947-2, Low-voltage switchgear and controlgear Part
9、2: Circuit-breakers2.2 This Outline references the following military specifications/documents. Specifications/documents canbe accessed at https:/assist.daps.dla.mil/quicksearch/.a) MIL-E-917, Electric Power Equipment, Basic Requirementsb) MIL-HDBK-454, General Guidelines for Electronic Equipmentc)
10、MIL-STD-1399-300, Interface Standard Section 300, Electric Power, Alternating Currentd) MIL-STD-202, Test Method Standard, Electronic and Electrical Component Partse) MIL-STD-130, Department of Defense Standard Practice, Identification Marking of U.S.Military Propertyf) MIL-STD-461, Requirements for
11、 the Control of Electromagnetic Interference Characteristicsof Subsystems and Equipmentg) DI-EMCS-80200, Electromagnetic Interference Test Report (EMITR)h) DI-EMCS-80201, Electromagnetic Interference Test Procedures (EMITP)APRIL 27, 2012UL 489D4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPR
12、ODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONSTRUCTION3 General3.1 Circuit breakers and all accessories shall meet the Section 6 construction requirements of UL 489except as modified or added to by the requirements of this Outline.3.2 Mounting adapter blocks/bases shall be plug-in type and s
13、hall allow for rear connection of cableand/or bus bar. Drawout cassettes may also be used. Drawout cassettes shall enable the circuit-breakerto be disconnected from the main circuit, in the withdrawn position, to achieve an isolating distance.3.3 The following materials and coatings are non-preferre
14、d and shall be identified in the qualification andrequalification reports:a) Navy-prohibited materials as defined by MIL-E-917 Section 3.4.1 including estimatedmaximum weight per circuit breaker and per accessory.b) Insulating materials which contain halogens, e.g. chlorine, fluorine, and bromine, w
15、hichevolve gases during combustion including estimated maximum weight per circuit breaker andper accessory.c) Corrosion-susceptible materials and coatings not in accordance with MIL-E-917 Section 3.10requirements.d) Organic materials not inherently fungus resistant or validated to be fungus resistan
16、t. Refer toMIL-HDBK-454, Guideline 4.e) Lead free solder.3.4 All printed circuit boards shall be conformal coated.3.5 Aluminum conductors or terminals shall not be used.RATINGS4 General4.1 Rated voltage as defined by UL 489 shall be 480VAC and/or 250 VDC as applicable.4.2 Rated frequency as defined
17、by UL 489 shall be 60 Hz.4.3 Recommended frame sizes are shown in Table 4.1 of this Outline. Frame size (maximum continuouscurrent rating) shall be verified by temperature rise testing in accordance with Sections 6 and 7 of thisOutline.APRIL 27, 2012 UL 489D 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED F
18、OR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 4.1Circuit breaker ratingsFrame size (amps) AC voltage60 Hz60 HzHigh available faultcurrent rating (rmssymmetrical kA)DC voltage DC high available faultcurrent rating (kA)100 480 15 250 10100 480 100250 480 20 250 15250 480 10040
19、0 480 30 250 20400 480 100800 480 50800 480 1001600 480 751600 480 1004.4 High available fault current rating as defined by UL 489 shall be stated by the manufacturer in rmssymmetrical or DC amperes as applicable. Recommended high available fault current ratings are shownin Table 4.1 of this Outline
20、. High available fault current ratings greater than those shown in Table 4.1 maybe substituted to reduce the number of circuit breakers subjected to the testing required by this Outline.The high available fault current rating shall be verified by testing in accordance with Sections 6 and 7 ofthis Ou
21、tline.4.5 Recommended nominal operating voltages for accessories are 120 Vac, 480 Vac, and 125 Vdc.PERFORMANCE5 Base Design5.1 Circuit breakers shall comply with the performance requirements in IEC 60947-2 and/or Section 7.1of UL 489 and in addition shall comply with performance requirements in Sect
22、ions 6 and 7 of this Outline.6 Initial Qualification Testing6.1 General6.1.1 Test Programs Q1, Q2, and Q3 shall be conducted as defined by this Outline. Test order for eachprogram is shown in Table 6.1 of this Outline.APRIL 27, 2012UL 489D6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCT
23、ION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 6.1Initial qualification test programsTest program Q1 Test program Q2 Test program Q3Vibration High available fault current test sequence Electromagnetic interference (circuitbreakers with electronic devices only)Voltage spike (circuit breakers with
24、electronic devices only)Temperature rise 50C ambient Shock FragilityCircuit breaker endurance loadoperations (“with current”) and selectedaccessory temperature riseVerification of accessoriesCircuit breaker and selected accessorytemperature rise 50C ambientCalibration 50C ambientDielectric voltage w
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT489D2012OUTLINEOFINVESTIGATIONFORUSNAVALCOMMERCIALOFFTHESHELFCOTSDESIGNATEDMOLDEDCASECIRCUITBREAKERSANDACCESSORIESFORUSEONNONNUCLEARNAVALCOMBPDF

链接地址:http://www.mydoc123.com/p-1069439.html