《UL SUBJECT 199J-2014 UL Outline for Investigation Fire Testing of Specific Application Sprinklers for Use on Windows (Issue 1)《在窗户上使用的特定应用喷淋器火灾试验的UL调查大纲 (议题1)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 199J-2014 UL Outline for Investigation Fire Testing of Specific Application Sprinklers for Use on Windows (Issue 1)《在窗户上使用的特定应用喷淋器火灾试验的UL调查大纲 (议题1)》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMay 16, 20141UL 199JOutline of Investigation for Fire Testing of Specific Application Sprinklersfor Use on WindowsIssue No. 1May 16, 2014Summary of TopicsThis First Issue of the Outline of Invest
2、igation for Fire Testing of SpecificApplication Sprinklers for Use on Windows, UL 199J, is being issued toadd requirements for sprinkler types not currently covered by UL 199.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of Investigation shou
3、ld be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2014 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODU
4、CTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMAY 16, 2014UL 199J2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .54 Undated References 5PERFORMANCE5 Fire
5、 Tests for Sprinklers Used to Protect Heat Strengthened, Tempered Glazing Materials withInstructions to Keep Combustibles at Least 2 inches (50.8 mm) Away from the Glazing Surface.56 Fire Tests for Sprinklers Used with a Fire Rated Glazing Material without a Limitation for KeepingCombustibles at Lea
6、st 2 inches (50.8 mm) Away from the Glazing Surface .56.1 General .56.2 Test Arrangement 66.3 Test method .8MAY 16, 2014 UL 199J 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover the fire testing
7、of specific application sprinklers for use on non-operablewindows when the sprinklers are installed in accordance with the manufacturers instructions and theStandard for the Installation of Sprinkler Systems, NFPA 13.1.2 Sprinklers investigated in accordance with this Outline shall also comply with
8、the applicablerequirements in the Standard for Automatic Sprinklers for Fire-Protection Service, UL 199, not includingthe fire and water distribution tests.1.3 The requirements described herein are intended to investigate the ability of the sprinklers to providewater on the surface of a window to li
9、mit the transmission of heat from a fire to the glazing material andmaintain the integrity of the window.1.4 These sprinklers have not been investigated for use as a substitute for fire protection rated glazingmaterials investigated in accordance with ANSI/UL 9, Fire Tests of Window Assemblies.2 Com
10、ponents2.1 Except as indicated in 2.2, a component of a product covered by this Outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the compo
11、nent in theproduct covered by this Outline, orb) Is superseded by a requirement in this Outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in construction features or restricted in performance capab
12、ilities.Such components are intended for use only under limited conditions, such as temperatures not exceedingspecified limits, and shall be used only under those specific conditions.MAY 16, 2014UL 199J4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION
13、 FROM UL3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline shall beinterpreted as referring
14、to the latest edition of that code or standard.PERFORMANCE5 Fire Tests for Sprinklers Used to Protect Heat Strengthened, Tempered Glazing Materials withInstructions to Keep Combustibles at Least 2 inches (50.8 mm) Away from the Glazing Surface5.1 Sprinklers intended to protect heat strengthened, tem
15、pered glazing materials with instructions to keepcombustibles at least 2 inches (50.8 mm) away from glazing surface shall be tested in accordance withULC/ORD-C262.1-99, Sprinkler Protected Window Systems using the minimum glazing thicknessspecified in the manufacturers installation instructions.6 Fi
16、re Tests for Sprinklers Used with a Fire Rated Glazing Material without a Limitation forKeeping Combustibles at Least 2 inches (50.8 mm) Away from the Glazing Surface6.1 General6.1.1 In addition to complying with ULC/ORD-C262.1-99 when tested in accordance with 5.1 using a heatstrengthened, tempered
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT199J2014ULOUTLINEFORINVESTIGATIONFIRETESTINGOFSPECIFICAPPLICATIONSPRINKLERSFORUSEONWINDOWSISSUE1

链接地址:http://www.mydoc123.com/p-1069212.html