UL SUBJECT 199H-2014 UL Outline for Investigation for Fire Testing Of Specific Application Sprinklers For Use In Horizontal Concealed Spaces (Issue 1)《在水平隐蔽空间内使用的特定应用喷淋器火灾试验的UL调查大纲.pdf
《UL SUBJECT 199H-2014 UL Outline for Investigation for Fire Testing Of Specific Application Sprinklers For Use In Horizontal Concealed Spaces (Issue 1)《在水平隐蔽空间内使用的特定应用喷淋器火灾试验的UL调查大纲.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 199H-2014 UL Outline for Investigation for Fire Testing Of Specific Application Sprinklers For Use In Horizontal Concealed Spaces (Issue 1)《在水平隐蔽空间内使用的特定应用喷淋器火灾试验的UL调查大纲.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFebruary 17, 20141UL 199HOutline of Investigation for Fire Testing Of Specific Application SprinklersFor Use In Horizontal Concealed SpacesIssue No. 1February 17, 2014Summary of TopicsThis First
2、Issue of the Outline of Investigation for Fire Testing of SpecificApplication Sprinklers for Use in Horizontal Concealed Spaces, UL 199H,is being issued to add requirements for sprinkler types not currentlycovered by UL 199.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norel
3、ectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2014 UNDERWRITERS LABORATORIES INC.UL COPYRI
4、GHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFEBRUARY 17, 2014UL 199H2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of
5、 Measurement .44 Undated References 5PERFORMANCE5 Open Wood Truss Fire Tests 55.1 General .55.2 Test Arrangement 55.3 Test method 116 Solid Wood Joist Fire Tests 126.1 General 126.2 Test Arrangement .126.3 Test method 17FEBRUARY 17, 2014 UL 199H 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER RE
6、PRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover the fire testing of specific application sprinklers for use in Light Hazardhorizontal concealed spaces formed by open wood trusses and solid wood joists when the sprinklers areinstalled in accordance
7、with the manufacturers instructions and the Standard for the Installation ofSprinkler Systems, NFPA 13.1.2 Sprinklers investigated in accordance with this Outline shall also comply with the applicablerequirements in the Standard for Automatic Sprinklers for Fire-Protection Service, UL 199, not inclu
8、dingthe fire and water distribution tests.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characterist
9、ic not required in the application of the component in theproduct covered by this Outline, orb) Is superseded by a requirement in this Outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in construct
10、ion features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as temperatures not exceedingspecified limits, and shall be used only under those specific conditions.3 Units of Measurement3.1 Values stated without parentheses are the re
11、quirement. Values in parentheses are explanatory orapproximate information.FEBRUARY 17, 2014UL 199H4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Undated References4.1 Any undated reference to a code or standard appearing in the requiremen
12、ts of this Outline shall beinterpreted as referring to the latest edition of that code or standard.PERFORMANCE5 Open Wood Truss Fire Tests5.1 General5.1.1 When fire tested as described in 5.2.1 5.3.6, water discharged from the sprinklers shall becapable of controlling test fires originated in an ope
13、n truss concealed space such that compliance with thefollowing requirements is demonstrated:a) The sprinklers located beyond the draft curtains shall not operate.b) The sprinklers shall discharge water into the space in such a manner to prevent the loadedwood trusses from collapsing.5.1.2 The temper
14、ature rating of the sprinklers subjected to the tests specified in 5.2.1 5.3.6 shall berepresentative of the sprinkler temperature ratings referenced in the manufacturers installationinstructions.5.1.3 These sprinklers are intended to be installed within an area enclosed by draft currents notexceedi
15、ng 1000 sq. ft. which is to be referenced in the manufacturers installation instructions.5.2 Test Arrangement5.2.1 Test structure5.2.1.1 Fire tests shall be conducted using open wood trusses having the minimum and maximum depthreferenced in the manufacturers installation instructions, but no greater
16、 than 60 inches (1.5 m). Each teststructure shall be constructed to have nominal dimensions of 40 ft. (12.2 m) long by 24 ft. (7.3 m) wide tosimulate the maximum draft curtain area of 1000 sq. ft. referenced in the manufacturers installationinstructions. Each test structure shall be constructed usin
17、g a combination of 20 ft. (6.1 m) and 10 ft. (3 m)long trusses spaced a nominal 24 inches (610 mm) apart. Each truss shall be constructed of trade size 2by 4 inch (nominal 1.5 inch (3.8 cm) by 3.5 inch (8.9 mm) spruce, pine or fir lumber. Figure 5.1 illustratesthe typical wood trusses used to constr
18、uct the test structure. The distance between trusses shall bepermitted to be adjusted to provide the minimum obstruction distance to the sprinkler.This is generated text for figtxt.FEBRUARY 17, 2014 UL 199H 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMI
19、SSION FROM ULFigure 5.1Typical truss detailFEBRUARY 17, 2014UL 199H6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5.2.1.2 A draft curtain having a depth of 1/3 the height of the truss or 8 inches (204 mm), whichever isgreater, shall be insta
20、lled around the perimeter of the test structure. The draft curtain shall be constructedof nominal 1/4 inch (6.4 mm) thick plywood. Tongue and groove oriented strand board having a nominalthickness of 3/4 inch (19 mm) shall be installed onto the top of the trusses and nominal 1/2 inch (12.7 mm)thick
21、gypsum board shall be installed onto the bottom of the trusses. A noncombustible material such ascement board is to be installed on top of the orientated stand board in the location of the ignition to providefor the entrapment of hot gases in the event of a fire induced breach of the orientated stra
22、nd board. Thebottom plane of the test structure is to be located above the floor of the test room to provide foraccessibility to replace structure members between tests. See Figure 5.1 for an illustration of the typicaltest arrangement.5.2.1.3 To allow for the installation of sprinklers beyond the p
23、rimary test area surrounded by the draftcurtains, the upper plane of the structure is to be extended by 4 ft. (1.2 m) on each end. This extendedarea shall also be surrounded by draft curtains having the same depth as the draft curtains used for theprimary test area. See Figure 5.2 for additional det
24、ails regarding the location of the draft curtains.This is generated text for figtxt.FEBRUARY 17, 2014 UL 199H 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFigure 5.2Open wood truss fire test arrangementFEBRUARY 17, 2014UL 199H8UL COPYRIGHT
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT199H2014ULOUTLINEFORINVESTIGATIONFORFIRETESTINGOFSPECIFICAPPLICATIONSPRINKLERSFORUSEINHORIZONTALCONCEALEDSPACESISSUE1

链接地址:http://www.mydoc123.com/p-1069211.html