《UL SUBJECT 199G-2012 UL Standard for Safety OUTLINE OF INVESTIGATION FOR FIRE TESTING OF SPECIFIC APPLICATION SPRINKLERS FOR USE IN ATTIC SPACES (Issue 1)《用于阁楼空间中特定应用洒水装置火灾试验调查大纲的U.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 199G-2012 UL Standard for Safety OUTLINE OF INVESTIGATION FOR FIRE TESTING OF SPECIFIC APPLICATION SPRINKLERS FOR USE IN ATTIC SPACES (Issue 1)《用于阁楼空间中特定应用洒水装置火灾试验调查大纲的U.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAugust 9, 20121UL 199GOUTLINE OF INVESTIGATIONFORFIRE TESTING OF SPECIFIC APPLICATION SPRINKLERS FOR USE INATTIC SPACESISSUE NO. 1August 9, 2012Summary of TopicsThis is the First Issue of the Sub
2、ject 199G, Outline of Investigation for FireTesting of Specific Application Sprinklers for Use In Attic SpacesCOPYRIGHT 2012 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 9, 2012UL 199G2No Text on This Pa
3、geUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .44 Undated References 5PERFORMANCE5 Fire Test 55.1 General .55.2 Test Arrangement 55.3 Test method .6AUGUST 9, 2012 UL 199G 3
4、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover the fire testing of specific application sprinklers for use in Light Hazard atticspaces when installed in accordance with the manufacturers instruc
5、tions and the Standard for theInstallation of Sprinkler Systems, NFPA 13.1.2 Sprinklers investigated in accordance with this Outline shall also comply with the applicablerequirements in the Standard for Automatic Sprinklers for Fire-Protection Service, UL 199, not includingthe fire and water distrib
6、ution requirements.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the
7、application of the component in theproduct covered by this Outline, orb) Is superseded by a requirement in this Outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in construction features or restric
8、ted in performance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.3 Units of Measurement3.1 Values stated without parentheses are the requirement. Valu
9、es in parentheses are explanatory orapproximate information.AUGUST 9, 2012UL 199G4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline
10、 shall beinterpreted as referring to the latest edition of that code or standard.PERFORMANCE5 Fire Test5.1 General5.1.1 When fire tested as described in 5.2.1 5.3.6, the water discharged from the sprinklers shall becapable of controlling the fires originating in an attic such that compliance with th
11、e following requirementsis demonstrated:a) The maximum area of breach (opening) in the roof deck caused by the fire shall not exceed6ft2(0.56 m2).b) The maximum number of operated sprinklers shall not exceed the number of sprinklersrequired to be included in the sprinkler system hydraulic design as
12、referenced in themanufacturers installation instructions.c) The sprinklers installed at the peak nearest each end of the attic test room shall not operate.5.1.2 Sprinklers in each temperature rating are to be subjected to the tests specified in 5.2.1 5.3.6.5.2 Test Arrangement5.2.1 Test room5.2.1.1
13、Simulated attic test rooms are to be constructed having a slope or slopes representative of therange of attic slopes intended to be protected by the sprinklers. In every case, the testing shall include theminimum attic slope referenced intended to be protected by the sprinklers. A simulated attic te
14、st roomshall be constructed having a length not less than 52 ft (15.8 m) and the maximum attic width intended tobe protected by the sprinklers. The attic is to be constructed of wood trusses manufactured from 2 by 4inch and 2 by 6 inch trade size lumber installed on 24 inch (61 cm) centers. The wood
15、 trusses constructedfrom 2 by 6 inch trade size lumber shall be installed along the slope. Nominal inch thick plywood shallbe installed along the attic slope as roof deck sheathing and also installed on the underside of the attictest room. The sheathing shall be terminated flush with the ends of the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT199G2012ULSTANDARDFORSAFETYOUTLINEOFINVESTIGATIONFORFIRETESTINGOFSPECIFICAPPLICATIONSPRINKLERSFORUSEINATTICSPACESISSUE1

链接地址:http://www.mydoc123.com/p-1069210.html