1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJune 12, 20131UL 1362OUTLINE OF INVESTIGATIONFORGAS BOOSTERSIssue Number: 1June 12, 2013Summary of TopicsThis first issue of the Outline of Investigation for Gas Boosters, UL 1362,covers requirem
2、ents for gas boosters, rated 600 V or less, intended foruse in natural or manufactured gas piping systems to increase the gasline pressure to that indicated on the device.COPYRIGHT 2013 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHO
3、UT PERMISSION FROM ULJUNE 12, 2013UL 13622No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 General 42.1 Components .42.2 Units of measurement .52.3 Undated references .53 Glossary .54 Pressure
4、, Temperature and Gas Service Ratings .5CONSTRUCTION5 General 66 Electrical Connections .67 Accessibility 68 Motors 139 Gaskets, Seals, O-Rings 13PROTECTION AGAINST INJURY TO PERSONS10 General 1411 Sharp Edges .1412 Enclosures and Guards 1413 Materials .1514 Rotating or Moving Members .1615 Parts Su
5、bject to Pressure 16PERFORMANCE16 General 1617 Deformation Test .1618 Input Test 1719 Blocked Outlet Test .1720 Temperature Test .1820.1 General .1821 External Leakage Test 2122 Hydrostatic Strength Test 22MARKINGS23 General 22INSTRUCTIONS24 General 23JUNE 12, 2013 UL 1362 3UL COPYRIGHTED MATERIAL N
6、OT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover gas boosters, rated 600 V or less, intended for use in natural ormanufactured gas piping systems to increase the gas line pressure to that indicated on the device.1.2 Devic
7、es and equipment covered by these requirements are intended for use indoors and are intendedto be installed in systems covered by the National Fuel Gas Code, NFPA 54, or the National ElectricalCode, NFPA 70.1.3 These requirements do not cover devices intended to be installed on a vehicle.1.4 These r
8、equirements do not cover devices intended to be used:a) With liquids or gases other than as indicated above, orb) With liquids under cryogenic temperatures less than minus 60C (minus 76F).1.5 These requirements do not cover gas booster compressor equipment which is covered by theStandard for Househo
9、ld and Similar Electrical Appliances, Part 2: Particular Requirements forMotor-Compressors, UL 60335-2-34.2 General2.1 Components2.1.1 Except as indicated in 2.1.2, a component of a product covered by this outline shall comply with therequirements for that component.2.1.2 A component need not comply
10、 with a specific requirement that:a) Involves a feature or characteristic not needed in the application of the component in theproduct covered by this outline orb) Is superseded by a requirement in this outline.2.1.3 A component shall be used in accordance with its rating established for the intende
11、d conditions ofuse.2.1.4 Specific components are incomplete in construction features or restricted in performancecapabilities. Such components are intended for use only under limited conditions, such as certaintemperatures not exceeding specified limits, and shall be used only under those specific c
12、onditions.JUNE 12, 2013UL 13624UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2.2 Units of measurement2.2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.2.3 Undated ref
13、erences2.3.1 Any undated reference to a code or standard appearing in the requirements of this standard shallbe interpreted as referring to the latest edition of that code or standard.3 Glossary3.1 For the purpose of this Outline of Investigation, the term device refers to gas boosters covered bythe
14、 scope of this document. In addition, the following definitions apply.3.2 GAS Includes natural gas and manufactured gas.3.3 GAS BOOSTER A device that will increase the gas line pressure to a specified value.3.4 HERMETICALLY SEALED A method to prevent the entrance of an external atmosphere and inwhic
15、h the seal is made by fusion, such as soldering, brazing, welding, or the fusion of glass to metal.3.5 MANUFACTURED GAS Synthetically produced mixture of methane and other gases, such ascarbon monoxide, produced by chemically treating coal.3.6 NATURAL GAS A naturally occurring hydrocarbon gas mixtur
16、e consisting primarily of methane,along with other hydrocarbons, carbon dioxide, nitrogen, and hydrogen sulfide.4 Pressure, Temperature and Gas Service Ratings4.1 The pressure rating of a device shall include the inlet pressure and differential pressure (or outletpressure) and shall be marked on the
17、 product. See 23.1.4.2 Devices covered by these requirements are intended for use at ambient temperatures within therange of minus 40 to plus 130F (minus 40 to plus 55C).JUNE 12, 2013 UL 1362 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCO
18、NSTRUCTION5 General5.1 A gas booster shall include all of the components necessary for its intended function and installation,and shall be furnished as a single unit or assembly.5.2 For devices intended for use in a classified area, or devices rated for use in a classified area,electrical components
19、, including the motor, when incorporated into the assembly of a gas booster,including the means provided in the assembly for electrical connections, shall comply with therequirements for equipment for use in hazardous locations, Class I, Group D, Division 1 or 2, (or Zone 1or 2, respectively), as ap
20、propriate, in the National Electrical Code, NFPA 70, Articles 500 and 501 (Article505 for Zone Classification), depending upon the installation in accordance with National Fuel Gas Code,NFPA 54.5.3 With reference to 5.2, such electrical components shall comply with the applicable standard for thepro
21、tection technique employed; for example explosion proof equipment shall comply with the Standard forExplosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations,UL 1203.6 Electrical Connections6.1 Devices shall be connected by permanent wiring. No cord con
22、nection is allowed.6.2 Wiring connections shall be made within a junction box or explosion proof junction box as needed.The junction box shall be formed of metallic materials.7 Accessibility7.1 To reduce the likelihood of unintentional contact that may involve a risk of electric shock from anuninsul
23、ated live part or film-coated wire, or injury to persons from a moving part, an opening in anenclosure shall comply with either of the following:a) For an opening that has a minor dimension (see 7.5) less than 1 inch (25.4 mm), such apart or wire shall not be contacted by the probe illustrated in Fi
24、gure 7.1.b) For an opening that has a minor dimension of 1 inch or more, such a part or wire shall bespaced from the opening as specified in Table 7.1.Exception: A motor need not comply with these requirements if it complies with the requirements in 7.2.JUNE 12, 2013UL 13626UL COPYRIGHTED MATERIAL N
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT13622013OUTLINEOFINVESTIGATIONFORGASBOOSTERSISSUE1 气体 增压 调查 大纲 议题 PDF

链接地址:http://www.mydoc123.com/p-1069160.html