1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULNovember 29, 20111SUBJECT 1294OUTLINE OF INVESTIGATIONFORCOMPOSITE PANELSISSUE NUMBER: 1November 29, 2011Summary of TopicsThis is the First Issue of Subject 1294, Outline of Investigation forComp
2、osite Panels. Composite panels incorporate pre-installed branchcircuit electrical power distribution systems which are usually concealedand may not be accessible for inspection at the installation site.COPYRIGHT 2011 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER RE
3、PRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULNOVEMBER 29, 2011SUBJECT 12942No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Accessories 54 Units of Measurement .55 Undated
4、 References 56 Glossary .5CONSTRUCTION7 General 68 Interconnection of Panels 69 Mechanical Accessories .710 Electrical Accessories 7PERFORMANCE11 Outlet Box Support Test 8MANUFACTURING AND PRODUCTION LINE TESTS12 Grounding Continuity Test 8MARKINGS13 General .814 Installation and Operating Instructi
5、ons 10Appendix AStandards for ComponentsA1NOVEMBER 29, 2011 SUBJECT 1294 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 This Outline covers factory-built panel assemblies for use within or as part of the structure of b
6、uildingsfor commercial, industrial and residential use. These assemblies incorporate pre-installed branch circuitelectrical power distribution systems which are usually concealed and may not be accessible forinspection at the installation site. Some panels incorporate audio, lighting, ventilation fa
7、ns and otherutilization equipment.1.2 The panel systems are evaluated only for installation in ordinary locations in accordance with theNational Electrical Code, ANSI/NFPA 70. Special Occupancies as specified in ANSI/NFPA 70 are notaddressed by these requirements.1.3 Composite panel assemblies cover
8、ed by this outline are intended to be installed in accordance withthe National Electrical Code, ANSI/NFPA 70, where the acceptability of the field assembled panel systemis determined by the Authority Having Jurisdiction.1.4 The surface flammability or fire resistance of the panel or panel system is
9、not covered by this outlineexcept as related to the individual requirements of the electrical components used within the system.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component. See Appe
10、ndix A for a list of standards coveringcomponents generally used in the products covered by this Outline.2.2 A component need not comply with a specific requirement that:a) Involves a feature or characteristic not needed in the application of the component in theproduct covered by this outline; orb)
11、 Is superseded by a requirement in this Outline of Investigation.2.3 A component shall be used in accordance with its recognized rating established for the intendedconditions of use.2.4 Specific components are recognized as being incomplete in construction features or restricted inperformance capabi
12、lities. Such components are intended for use only under limited conditions, such ascertain temperatures not exceeding specified limits and shall be used only under those specific conditionsfor which they have been recognized.NOVEMBER 29, 2011SUBJECT 12944UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FU
13、RTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3 Accessories3.1 Proprietary electrical utilization equipment or proprietary electrical materials for use with a compositepanel system shall comply with the requirements for that equipment or material. See Appendix A.3.2 Proprietary equipme
14、nt or materials not assembled to the composite panel at the factory shall beprovided with installation instructions in accordance with 13.4.3.3 Proprietary equipment or materials not assembled to the composite panel at the factory shall bemarked for use with the composite panel system in accordance
15、with 13.4.4 Units of Measurement4.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4.2 Unless otherwise indicated, all voltage and current values mentioned in this standard areroot-mean-square (rms).5 Undated References5.1 Any u
16、ndated reference to a code or standard appearing in the requirements of this outline shall beinterpreted as referring to the latest edition of that code or standard.5.2 Undated references to the National Electrical Code (NEC), ANSI/NFPA 70, refer to the edition of theNEC to which the product was eva
17、luated. The edition of the NEC used during the evaluation is marked oneach panel. See 13.8.6 Glossary6.1 For the purposes of this Outline of Investigation, the following definitions apply:6.2 ACCESSORY Proprietary equipment such as ventilation fans, lighting, sound and lighting controlequipment, mec
18、hanical anchoring systems, panel joining brackets or proprietary electrical materialssuch as electrical enclosures and electrical outlet box supports for use and installation with a compositepanel system.6.3 COMPOSITE PANEL Two typically parallel surfaces provided with an integral spacer material or
19、separate spacers to separate the surfaces. The panel may be provided with insulation materialsbetween the surfaces. For the purpose of these requirements the panels are provided with an electricalsystem that may be concealed after the panel is assembled.6.4 PANEL SYSTEM Two or more composite panels
20、intended to be physically connected in the field.NOVEMBER 29, 2011 SUBJECT 1294 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONSTRUCTION7 General7.1 Wiring methods and materials shall be installed in accordance with the National Electric
21、Code,ANSI/NFPA 70, Chapter 3.7.2 Remote-Control, Signaling and Power-Limited Circuits shall be installed utilizing one of the methodsspecified in the National Electric Code, ANSI/NFPA 70, Article 725.7.3 Grounding and Bonding shall be provided as specified in the National Electric Code, ANSI/NFPA 70
22、,Article 250.8 Interconnection of Panels8.1 Panels that are intended to be electrically interconnected shall also be mechanically interconnected.8.2 Panels that are intended to be electrically interconnected shall be provided with a means to routeconductors from one panel to the next electrified pan
23、el. The means shall be consistent with therequirements of Chapter 3 of the National Electric Code, ANSI/NFPA 70. Some typical examples areshown in Figure 8.1. All splices shall be located in junction boxes that are accessible after the completepanel system is installed.This is generated text for fig
24、txt.Figure 8.1Electrical interconnectionsNOVEMBER 29, 2011SUBJECT 12946UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL8.3 One of the electrically powered panels in a system shall be provided with a means to routeconductors from the panel to t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT12942011OUTLINEOFINVESTIGATIONFORCOMPOSITEPANELSISSUE1 复合板 测试 纲要 PDF

链接地址:http://www.mydoc123.com/p-1069148.html