NAVY MIL-C-23742-1963 CONTROL CENTERS ALTERNATING CURRENT NAVAL SHIPBOARD《海军船交流电调度室》.pdf
《NAVY MIL-C-23742-1963 CONTROL CENTERS ALTERNATING CURRENT NAVAL SHIPBOARD《海军船交流电调度室》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-C-23742-1963 CONTROL CENTERS ALTERNATING CURRENT NAVAL SHIPBOARD《海军船交流电调度室》.pdf(15页珍藏版)》请在麦多课文档分享上搜索。
1、- MIL-C-23742 bL 7777706 0088931 8 MIL4 -23742(SHLPS) 12 July 1963 MILITARY SPECIFICATION CONTROL CENTERS, ALTERNATING CURRENT NAVAL SHIPBOARD 1. SCOPE 1.1 This specification covers High Impact (HI) shockproof group control and distribution sections for Naval shipboard use, 2. APPLICABLE DOCUMENTS 2
2、,l The following documents of the issue in effect on date of invitation for bids or request for proposal, form a part of the specification to the extent specified herein. SPECIFICATIONS FEDER4L QQ-C-504 - Copper Bus Bars (Including Bars, Rods and Shapes). MILITARY MIL-S-901 MIL-E-917 MIL-D-963 MIL-C
3、-2212 MIL-Q-9858 MIL-M-15071 - Manuals, Equipment and Systems, MIL-F-15160 - Fuses; Instrument, Power and Telephone. MIL-W-16878 - Wire, Electrical, Insulated, High Temperature. MIL-C-17361 - Circuit Breakers, Air, Electric, Insulated Enclosure, (Shipboard Use). MIL-F-19207 - Fuseholder, Extractor P
4、ost Type, Blown Fuse Indicating and Nonindicating. MIL-R-19523 - Relays, Auxiliary, Naval Shipboard. MIL-E-22843 - Equipment, Low Noise Level, (Naval Shipboard Use). - Shock Tests, H. I. (High-Impact); Shipboard Machinery, Equipment and Systems, - Electric Power Equipment, Basic Requirements for (Na
5、val Shipboard Use). - Drawings, Electrical, Hull and Mechanical Equipment for Naval Shipboard Use. - Controllers, Alternating Current, Naval Shipboard. - Quality Control System Requirements. Requirements for , STANDARDS MILITARY MIL-STD-167 - Mechanical Vibrations of Shipboard Equipment. MIL-STD-195
6、 - Marking of Connections for Electric Assemblies. MIL-STD-740 - Noise Measurements of Shipboard Machinery and Equipment. DRAWINGS BUREAU OF SHIPS 815-1853024 9000-S6202-74230 - Fuseholder, Single, Dead Front-Blown Fuse Indicating for 1-1/2 x 13/32 - Dead Front Fuseholder, Type FHL14G. Inch Fuses, T
7、ype 12FH1, 450 Volts. (Copies of specifications, standards, drawings, and publications required by suppliers in connection with specific procurement functions should be obtained from the procuring activity or as directed by the contract- ing officer.) 2.2 Other publications.- The following documents
8、 form a part of this specification to the extent speci- fied herein. Unless otherwise indicated, the issue in effect on date of invitation for bids or request for proposal shall apply. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-C-Z3742 bL W
9、99999Ob 0088932 T MIL-C-23742(SHIPS) OFFICIAL CLASSIFICATION COMMITTEE Uniform Freight Classification Rules. (Application for copies should be addressed to the Official Classification Committee, 1 Park Avenue at NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) 33rd Street, New York 16, New York)
10、, IC1 - Control, Industrial. (Application for copies should be addressed to the National Electrical Manufacturers Association, 155 East 44th Street, New York 17, New York). (Technical society and technical association specifications and standards are generally available for reference from libraries,
11、 They are also distributed among technical groups and using Federal agencies.) 3. REQUIREMENTS 3.1 Preproduction sample.- Prior to beginning production a sample of one control center shall be tested as specified in 4.2 (see 6.2). 3.2 Definitions.- The following definitions apply to terms used in thi
12、s specification: 3.2.1 Group control section.- A self-supporting, vertical structure containing controller units for the 3.2.2 Distribution section.- A self-supporting, vertical structure containing AQB circuit breakers, in 3.2.3 Group control and distribution section.- A section which contains cont
13、roller units and separately 3.2.4 Controlcenter.- Distribution and group control sections, or a combination thereof, serving as a 3.2.5 Controller unit.- An assembly consisting of a magnetic controller and protective devices suitable 3.3 General requirements.- The equipment shall conform to MIL-E-91
14、7 and MIL-C-2212. Whenever a supply and control of power to electrical auxiliaries. number asKimbution of power to miscellaneous ship service loads. mounted AQB circuit breakers for distribution of power to miscellaneous ship service loads. power distribution center for a selected system or distribu
15、tion area. for drawout mounting in a group control section or group control and distribution section. requirement of MIL-E-917 and MIL-C-2212 conflicts with a requirement of this specification, the require- ments of this specification shall govern, 3.4 Design,- 3.4.1 Group control and distribution s
16、ections.- A section shall be a vertical structure of a maximum height of 82 inches over the dpipshield, 20 inches wide and 12 inches deep. Controller units shall it over a space of either 12-1/2 inches or 25 inches in height. Individually mounted circuit breakers shall fit into a space of 12-1/2 inc
17、hes in height for 100 ampere units and 14 inches for 250 ampere units. Each section shall be provided with horizontal wiring space at the bottom, unless otherwise specified (see 6.1), which will line up with adjacent sections to form a convenient raceway the entire length of the load center. In addi
18、tion, each section shall have a vertical wire space either in the rear or on one side for unit wiring. The vertical wiring space shall be equipped with sufficient cable tie supports to hold cables and wiring in place. 3.4.2 Conpoller units.- Units shall be provided in accordance with the following s
19、tandards, as specified (see 6.1): Unit type A Twin size O B Single size 1 C Twin size 1 D Single size 2 E Single size 3 Description with fuses 5HP max. with fuses 1OHP max. with fuses 10HP max. with 100 amp. breaker 25HP max. with 100 amp. breaker 50HP Max. 2 Provided by IHSNot for ResaleNo reproduc
20、tion or networking permitted without license from IHS-,-,-MIL-C -23742 (SHIPS) Unit type F Single size 4 G Single size 4 H Single size 5 A2 Two size O B2 Two size 1 c2 Two size 2 Description with 100 amp. breaker 75HP max. with 250 amp. breaker 1OOHP max. with 250 amp. breaker 200HP max. with contro
21、l and line fuses for two with control and line fuses for two with control fuses for two speed, speed, 5HP max. speed, 1OHP max. 25HP max. Controller units of the same size and design shall be readily interchangeable. 3.4.3 Terminal boards.- If required by the contract or order, all control and power
22、 circuits shall be brought to terminal boards located horizontal in the wiring space at the bottom of the section unless otherwise specified (see 6.1). Provision shall be made for approximately 10 percent spare terminals on the board. Access to the terminal boards shall be from the front, To minimiz
23、e the possibility of breakage of the ter- minal boards, due to distortion of the mounting support under shock, the length of the terminal board shall not exceed 12 terminal points. fuses for size O and size 1 controllers shall be style F60 or F62 in accordance with MIL-F-15160. 3.4.4 Fuses.- Fuses f
24、or control circuis shall be style F60 in accordance with MIL-F-15160. Line 3.4.4.1 Fuseho1ders.- Fuseholders for control fuses shall be type 12FHl(FHL12G) 0-30 amp, 500 volt, deadfront,%blown fuse indicating fuseholders in accordance with Drawing 9000-S6202-74230 and MIL-F-19207. The fuseholders sha
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILC237421963CONTROLCENTERSALTERNATINGCURRENTNAVALSHIPBOARD 海军 交流电 调度室 PDF

链接地址:http://www.mydoc123.com/p-977599.html