ETSI EN 305 200-3-1-2018 Access Terminals Transmission and Multiplexing (ATTM) Energy management Operational infrastructures Global KPIs Part 3 ICT Sites Sub-part 1 DCEM (V1 1 1).pdf
《ETSI EN 305 200-3-1-2018 Access Terminals Transmission and Multiplexing (ATTM) Energy management Operational infrastructures Global KPIs Part 3 ICT Sites Sub-part 1 DCEM (V1 1 1).pdf》由会员分享,可在线阅读,更多相关《ETSI EN 305 200-3-1-2018 Access Terminals Transmission and Multiplexing (ATTM) Energy management Operational infrastructures Global KPIs Part 3 ICT Sites Sub-part 1 DCEM (V1 1 1).pdf(34页珍藏版)》请在麦多课文档分享上搜索。
1、 ETSI EN 305 200-3-1 V1.1.1 (2018-02) Access, Terminals, Transmission and Multiplexing (ATTM); Energy management; Operational infrastructures; Global KPIs; Part 3: ICT Sites; Sub-part 1: DCEM EUROPEAN STANDARD ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)2 Reference REN/ATTM-005 Keywords broadband, ener
2、gy management, ICT, sustainability ETSI 650 Route des Lucioles F-06921 Sophia Antipolis Cedex - FRANCE Tel.: +33 4 92 94 42 00 Fax: +33 4 93 65 47 16 Siret N 348 623 562 00017 - NAF 742 C Association but non lucratif enregistre la Sous-Prfecture de Grasse (06) N 7803/88 Important notice The present
3、document can be downloaded from: http:/www.etsi.org/standards-search The present document may be made available in electronic versions and/or in print. The content of any electronic and/or print versions of the present document shall not be modified without the prior written authorization of ETSI. I
4、n case of any existing or perceived difference in contents between such versions and/or in print, the only prevailing document is the print of the Portable Document Format (PDF) version kept on a specific network drive within ETSI Secretariat. Users of the present document should be aware that the d
5、ocument may be subject to revision or change of status. Information on the current status of this and other ETSI documents is available at https:/portal.etsi.org/TB/ETSIDeliverableStatus.aspx If you find errors in the present document, please send your comment to one of the following services: https
6、:/portal.etsi.org/People/CommiteeSupportStaff.aspx Copyright Notification No part may be reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying and microfilm except as authorized by written permission of ETSI. The content of the PDF version shall not be
7、modified without the written authorization of ETSI. The copyright and the foregoing restriction extend to reproduction in all media. ETSI 2018. All rights reserved. DECTTM, PLUGTESTSTM, UMTSTMand the ETSI logo are trademarks of ETSI registered for the benefit of its Members. 3GPPTM and LTETMare trad
8、emarks of ETSI registered for the benefit of its Members and of the 3GPP Organizational Partners. oneM2M logo is protected for the benefit of its Members. GSMand the GSM logo are trademarks registered and owned by the GSM Association. ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)3 Contents Intellectual
9、Property Rights 7g3Foreword . 7g3Modal verbs terminology 7g3Introduction 8g31 Scope 9g32 References 9g32.1 Normative references . 9g32.2 Informative references 10g33 Definitions, symbols and abbreviations . 11g33.1 Definitions 11g33.2 Symbols 12g33.3 Abbreviations . 12g34 Energy management of ICT si
10、tes . 13g34.1 General . 13g34.1.1 Measured energy . 13g34.1.2 Dedicated ICT sites . 13g34.1.3 Mixed-use ICT sites 14g34.1.4 Groups of ICT sites . 14g34.2 Related standards 14g35 Global KPI for ICT sites (KPIDCEM) . 16g35.1 General . 16g35.1.1 Global KPI (KPIDCEM) for ICT sites 16g35.1.2 Objective KP
11、Is 16g35.1.2.1 Energy consumption (KPIEC) 16g35.1.2.2 Task effectiveness (KPITE) 17g35.1.2.3 Energy re-use (KPIREUSE) 17g35.1.2.4 Renewable energy (KPIREN) 18g35.2 Scale . 18g35.3 Utilization and evolution 18g35.4 Definition of boundaries . 19g35.4.1 General 19g35.4.2 Flows of electrical energy . 19
12、g35.4.3 Flows of thermal energy . 20g35.4.3.1 ICT site cooling (heat discharge systems) . 20g35.4.3.2 Heat distribution networks 21g35.4.4 Inclusion in Objective KPIs 21g35.5 Formulae. 22g35.5.1 Global KPI for ICT sites (KPIDCEM) 22g35.5.1.1 General 22g35.5.1.1.1 KPIEC. 22g35.5.1.1.2 KPIEP. 22g35.5.
13、1.2 Definition of terms 22g35.5.1.3 Clarity . 23g35.5.1.4 Criteria 23g35.5.1.5 Weighting factors 23g35.5.1.5.1 General 23g35.5.1.5.2 Energy re-use (WREUSE) 23g35.5.1.5.3 Renewable energy (WREN) 23g35.5.2 Objective KPIs for ICT sites . 24g35.5.2.1 Energy consumption (KPIEC) 24g35.5.2.1.1 Formula . 24
14、g35.5.2.1.2 Definitions of terms . 24g35.5.2.1.3 Clarity 24g3ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)4 5.5.2.1.4 Criteria . 24g35.5.2.2 Task effectiveness (KPITE) 25g35.5.2.2.1 Formula . 25g35.5.2.2.2 Definitions of terms . 25g35.5.2.2.3 Clarity 25g35.5.2.2.4 Criteria. 25g35.5.2.3 Energy re-use (KP
15、IREUSE) 25g35.5.2.3.1 Formula . 25g35.5.2.3.2 Definitions of terms . 26g35.5.2.3.3 Clarity 26g35.5.2.3.4 Criteria. 26g35.5.2.4 Renewable energy (KPIREN) 26g35.5.2.4.1 Formula . 26g35.5.2.4.2 Definitions of terms . 27g35.5.2.4.3 Clarity 27g35.5.2.4.4 Criteria. 27g35.6 Measurement points and procedure
16、s 27g35.6.1 Objective KPIs for ICT sites . 27g35.6.1.1 Energy consumption (KPIEC) 27g35.6.1.1.1 Measurement points . 27g35.6.1.1.2 Measurement procedures . 29g35.6.1.2 Task effectiveness (KPITE) 29g35.6.1.2.1 Measurement points . 29g35.6.1.2.2 Measurement procedures . 30g35.6.1.3 Task effectiveness
17、(KPITE) 30g35.6.1.3.1 Measurement points . 30g35.6.1.3.2 Measurement procedures . 30g35.6.1.4 Energy re-use (KPIREUSE) 30g35.6.1.4.1 Measurement points . 30g35.6.1.4.2 Measurement procedures . 30g35.6.1.5 Renewable energy (KPIREN) 30g35.6.1.5.1 Measurement points . 30g35.6.1.5.2 Measurement procedur
18、es . 30g35.7 Classifications 31g35.7.1 KPIECpresented as DCG31g35.7.2 KPIEPpresented as DCCLASS31g35.7.3 Application to groups of ICT sites 31g35.8 Reporting 31g3Annex A (informative): Weighting values 32g3A.1 General . 32g3A.2 Industry organizations 32g3A.2.1 CRIP . 32g3A.2.2 eG4U 33g3History 34g3E
19、TSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)5 List of figures Figure 1: Schematic of the functional elements of an ICT site .13g3Figure 2: Schematic of energy measurement of a dedicated ICT site .13g3Figure 3: Schematic of energy measurement of a mixed-use ICT site 14g3Figure 4: Electrical energy flows
20、19g3Figure 5: Energy flows for heat sinks 20g3Figure 6: Schematic of Objective and Global KPIs.21g3Figure 7: Measurement points for energy consumption 26g3ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)6 List of tables Table 1: Implementation of Availability Class 15g3Table A.1: DCGbands used by CRIP .31g
21、3Table A.2: Weighting values used by CRIP 31g3Table A.3: DCCLASSbands used by CRIP 31g3Table A.4: DCGbands used by eG4U .32g3Table A.5: Weighting values used by eG4U .32g3Table A.6: DCCLASSbands used by eG4U .32g3ETSI ETSI EN 305 200-3-1 V1.1.1 (2018-02)7 Intellectual Property Rights Essential paten
22、ts IPRs essential or potentially essential to normative deliverables may have been declared to ETSI. The information pertaining to these essential IPRs, if any, is publicly available for ETSI members and non-members, and can be found in ETSI SR 000 314: “Intellectual Property Rights (IPRs); Essentia
23、l, or potentially Essential, IPRs notified to ETSI in respect of ETSI standards“, which is available from the ETSI Secretariat. Latest updates are available on the ETSI Web server (https:/ipr.etsi.org/). Pursuant to the ETSI IPR Policy, no investigation, including IPR searches, has been carried out
24、by ETSI. No guarantee can be given as to the existence of other IPRs not referenced in ETSI SR 000 314 (or the updates on the ETSI Web server) which are, or may be, or may become, essential to the present document. Trademarks The present document may include trademarks and/or tradenames which are as
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ETSIEN305200312018ACCESSTERMINALSTRANSMISSIONANDMULTIPLEXINGATTMENERGYMANAGEMENTOPERATIONALINFRASTRUCTURESGLOBALKPISPART3ICTSITESSUBPART1DCEMV111PDF

链接地址:http://www.mydoc123.com/p-730601.html