BS 5041-2-1987 Fire hydrant systems equipment - Specification for landing valves for dry risers《消防栓系统设备 干式水嘴接地阀规范》.pdf
《BS 5041-2-1987 Fire hydrant systems equipment - Specification for landing valves for dry risers《消防栓系统设备 干式水嘴接地阀规范》.pdf》由会员分享,可在线阅读,更多相关《BS 5041-2-1987 Fire hydrant systems equipment - Specification for landing valves for dry risers《消防栓系统设备 干式水嘴接地阀规范》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS5041-2: 1987 Incorporating Amendment No.1 Fire hydrant systems equipment Part 2: Specification for landing valves for dry risers UDC 614.843.1+621.643.51BS5041-2:1987 This British Standard, having been prepared under the directionof the Fire Standards Committee, was published unde
2、rthe authority of the BoardofBSI and comes into effect on 31 March1987 BSI 07-1999 First published February 1976 First revision March 1987 The following BSI references relate to the work on this standard: Committee reference FSM/6 Draft for comment86/35863 DC ISBN 0 580 15722 9 Committees responsibl
3、e for this British Standard The preparation of this British Standard was entrusted by the Fire Standards Committee (FSM/-) to Technical Committee FSM/6, upon which the following bodies were represented: Association of County Councils Association of Metropolitan Authorities British Coal British Fire
4、Services Association British Plastics Federation British Valve Manufacturers Association Ltd. Chief and Assistant Chief Fire Officers Association Convention of Scottish Local Authorities Copper Development Association Department of the Environment (Property Services Agency) Department of Transport (
5、Marine Directorate) Fire Extinguishing Trades Association Fire Offices Committee Fire Protection Association Greater London Council Home Office Institution of Fire Engineers Ministry of Defence Royal Institute of British Architects The following body was also represented in the drafting of the stand
6、ard, through subcommittees and panels: British Fire Protection Systems Association Ltd. Amendments issued since publication Amd. No. Date of issue Comments 5776 July 1988 Indicated by a sideline in the marginBS5041-2:1987 BSI 07-1999 i Contents Page Committees responsible Inside front cover Foreword
7、 ii Section 1. General 1 Scope 1 2 Definitions 1 3 Pressure rating 1 4 Nominal inlet sizes 1 5 Temperature rating 1 6 Marking 1 Section 2. Design 7 Materials 2 8 Valve bodies 2 9 Valve inlets 2 10 Valve outlets 3 11 Bonnets 3 12 Wedge gates 3 13 Stems 3 14 Stem sealing 3 15 Glands 3 16 Handwheels an
8、d operation 3 17 Bolting 4 18 Pressure retention 4 19 Strap 4 20 Blank cap and chain 4 Section 3. Production testing requirements and test certificate 21 Hydrostatic test requirements 5 22 Test certificate 5 Appendix A Hydrostatic test methods 6 Appendix B Recommendations for the information to be s
9、uppliedbythepurchaser to the manufacturer 6 Table 1 Choice of materials for components and parts 2 Table 2 Bolting for valves 4 Publications referred to Inside back coverBS5041-2:1987 ii BSI 07-1999 Foreword This revision of BS5041-2 has been prepared under the direction of the Fire Standards Commit
10、tee and supersedes BS5041-2:1976, which is withdrawn. It specifies requirements for copper alloy gate valves for use on dry risers, tests and marking. The subjects of the other Parts in the BS5041 series of general specifications for fire hydrant systems equipment are as follows. Part 1: Landing val
11、ves for wet risers; Part 3: Inlet breechings for dry riser inlets; Part 4: Boxes for landing valves for dry risers; Part 5: Boxes for foam inlets and dry riser inlets. These Parts give detailed requirements for most of the other special items required for wet and dry risers described in BS5306-1. A
12、full bore valve, as specified in this Part, is needed in dry risers to ensure minimum resistance to water flow, and stem diameters have been specified to ensure reliability. In this standard metric values are given in SI units; for further information reference should be made to BS3763. Some nominal
13、 bores and thread sizes are given in inches to accord with the standards referred to. A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of it
14、self confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pagesiandii, pages1to6, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had amendments incorporated. This will be indica
15、ted in the amendment table on the inside front cover.BS5041-2:1987 BSI 07-1999 1 Section 1. General 1 Scope This Part of BS5041 specifies requirements for copper alloy gate valves generally complying with BS5154, suitable for installation as landing valves on dry risers. The valves have screwed or f
16、langed inlets and also delivery hose connections complying with BS336. The standard covers valves of nominal pressure (PN) designation15 bar and nominal inlet size DN65 for flanged ends and2 for screwed ends. NOTE 1Unless otherwise stated all pressures are gaugepressures expressed in bar:1 bar=10 5N
17、/m 2 =100 kPa. NOTE 2Information which the purchaser is recommended to supply to the manufacturer is given in Appendix B and does not form part of the specification. NOTE 3The titles of the publications referred to in this standard are listed on the inside back cover. 2 Definitions For the purposes
18、of this Part of BS5401, the following definitions apply. 2.1 dry riser (dry rising main) a vertical pipe installed in a building for fire fighting purposes, fitted with inlet connections at fire service access level and outlet connections at specified points, which is normally dry but capable of bei
19、ng charged with water by pumping from fire service appliances 2.2 landing valve an assembly comprising a valve and outlet connection from a wet or dry riser 3 Pressure rating Valves shall be suitable for use at nominal inlet pressures up to15bar. 4 Nominal inlet sizes 4.1 Flanged end valves The nomi
20、nal inlet size (DN) shall be65. 4.2 Screwed end valves The nominal inlet size (DN) shall be2. 5 Temperature rating Valves shall be suitable for continuous use at the nominal pressure rating (seeclause3) throughout the temperature range from0C to38C. 6 Marking Each valve shall be marked with the foll
21、owing: a) the nominal size; b) the manufacturers name or trademark; c) the number of this standard, i.e.BS5041-2 1) . 1) Marking BS5041-2 on or in relation to a product is a claim by the manufacturer that the product has been manufactured to the requirements of the standard. The accuracy of such a c
22、laim is therefore solely the manufacturers responsibility. Enquiries as to the availability of third party certification should be addressed to the appropriate certification body.BS5041-2:1987 2 BSI 07-1999 Section 2. Design 7 Materials Each component or part of the valve shall be made from one of t
23、he materials given in Table 1. 8 Valve bodies 8.1 Flow-way dimensions The body inlet port and the seat bore shall be circular and have a diameter of not less than63.5mm. 8.2 Body wall thickness The body wall thickness at any point shall be not less than2.8mm and the distance from the back face or fl
24、ange face to the extremity of the chain retaining lug on the blank cap shall be not more than300mm, with the blank cap fitted to the outlet. 8.3 Body seat The body seat shall be either integral with the body or inserted in the form of a securely fitted but renewable ring. 8.4 Seating face The seatin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS504121987FIREHYDRANTSYSTEMSEQUIPMENTSPECIFICATIONFORLANDINGVALVESFORDRYRISERS 消防栓 系统 设备 干式水嘴 接地 规范

链接地址:http://www.mydoc123.com/p-544812.html