ASTM F1005-1991(2002) Standard Practice for HVAC Duct Shapes Identification and Description of Design Configuration《采暖、通风与空调导管形状 设计配置的描述和识别》.pdf
《ASTM F1005-1991(2002) Standard Practice for HVAC Duct Shapes Identification and Description of Design Configuration《采暖、通风与空调导管形状 设计配置的描述和识别》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1005-1991(2002) Standard Practice for HVAC Duct Shapes Identification and Description of Design Configuration《采暖、通风与空调导管形状 设计配置的描述和识别》.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 1005 91 (Reapproved 2002)An American National StandardStandard Practice forHVAC Duct Shapes; Identification and Description of DesignConfiguration1This standard is issued under the fixed designation F 1005; the number immediately following the designation indicates the year oforiginal
2、 adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the identification of design configu-rations
3、and descriptive nomenclature for sheetmetal HVACductwork shapes frequently used in shipbuilding. This practicealso covers parametric dimensions of these shapes. (See Table1.)1.2 This practice does not cover the location of seams orjoints within a shape or the method of joining shapes together.1.3 Si
4、nce this practice is not measurement sensitive, it isapplicable whether inch-pound or SI metric dimensions areused.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate
5、safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Terminology2.1 Definitions of Terms Specific to This Standard:2.1.1 branchportion of a duct system connection to amain duct.2.1.2 elbowa fitting used to change direction of air flow.2.1.3 flat oval
6、cross section that has flat sides and semi-circular ends.2.1.4 long axis of flat oval curved so that the flat sides ofthe flat oval remain in a plane.2.1.5 offsetfitting that changes the location of the ductwith the line of the duct remaining parallel.2.1.6 ogeea smoothly curved type of offset. The
7、insidecurve of each end is tangent to the outside curve of the otherend.2.1.7 radius cornercross section that is generally rectan-gular, but with the corners softened to a radius.2.1.8 rectangularrectangular or square cross section.2.1.9 reducera fitting that changes the size but not thecross-sectio
8、n type of duct.2.1.10 roundcircular cross section.2.1.11 short axis of flat ovalcurved so that the flat sides ofthe flat oval correspond to the curve.2.1.12 splitterinternal part of some elbows and offsets;sometimes required in diverging transitions. Used to providemore uniform velocity and distribu
9、tion of air flow. The numberand location of splitters is determined by calculation or from anomograph.2.1.13 straightduct that remains constant in cross sectionand size throughout its length.2.1.14 throatwrapper around the inside of a fitting.2.1.15 transitionfitting that changes the cross-sectionty
10、pe of the duct.2.1.16 vaneinternal part of vaned turns. Used to providemore uniform velocity of air flow. Configuration, number, andlocation of vanes is determined from drawing, NAVSHIPS No.S3801-385260.2The direction of airflow must be marked onvaned turns.2.1.17 vaned turna fitting containing vane
11、s that is used tochange the direction of air flow.2.2 Variables Specific to This Standard:AAngle. Included angle of an elbow, branch, vaned turn,or slant-top fitting.AIAir In indicates the length of the straight portion of avaned turn in the “air in-flow” side.AOAir Out indicates the length of the s
12、traight portion ofa vaned turn on the “air out-flow” side.BDistance from the intersection of the center lines of abranch and the main duct to the end of the main duct.CYDistance between centers of a Y branch.DDepth of a part.DBDepth of a branch.DIADiameter of a part.DIABDiameter of a branch.DIA1Majo
13、r diameter of a part.DIA2Minor diameter of a part.D1Major depth of a part.D2Minor depth of a part.FFlat section that softens the corner of a vaned turn.1This practice is under the jurisdiction of ASTM Committee F25 on Ships andMarine Technology and is the direct responsibility of Subcommittee F25.11
14、 onMachinery.Current edition approved July 15, 1991. Published September 1991. Originallypublished as F 1005 86. Last previous edition F 1005 86.2Drawing: Naval Sea Systems Command (NAVSEA) NAVSHIPS S3801-385260 Vanes Channels Ventilation Vane, available from Commander, PortsmouthNaval Shipyard, Nav
15、al Engineering Drawing Support Activity, Code 202.2, Ports-mouth, NH 03804-5000.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.LLength of a part.LBLength of a branch from the end of the branch to thepoint where the centerline of the
16、 branch intersects the center-line of the main duct.1.1Major length of a Y branch.1.2Minor length of a Y branch.OOffset in one direction.RRadius of a bellmouth.RCRadius corner.RV1Radius of first splitter at V extension.RV2Radius of second splitter at V extension.RV3Radius of third splitter at V exte
17、nsion.RZ1Radius of first splitter at Z extension.RZ2Radius of second splitter at Z extension.RZ3Radius of third splitter at Z extension.R1Radius of first splitter.R2Radius of second splitter.R3Radius of third splitter.S1Distance of first splitter from the outside curve of anogee offset.S2Distance of
18、 second splitter from the outside curve ofan ogee offset.S3Distance of third splitter from the outside curve of anogee offset.TRThroat radius is the radius of the inside surface of anelbow or offset. Normally TR is equal to the width (of arectangular elbow).TR1Major throat radius of a reducing offse
19、t.TR2Minor throat radius of a reducing offset.VExtension on one end of a part, opposite from Z.WWidth of a part.WBWidth of a branch.TABLE 1 HVAC Standard Nomenclature and Numbering System1. Straight:1.1 Straight-round1.2 Straight-flat oval1.3 Straight-rectangular2. Offset:2.1 Offset-round2.2.1 Offse
20、t-flat oval-long axis2.2.2 Offset-flat oval-short axis2.3.1 Offset-rectangular-without splitters2.3.2 Offset-rectangular-with splitters2.4.1 Offset-ogee-without splitters2.4.2 Offset-ogee-with splitters2.5.1 Offset-rectangular reducing-withoutsplitters2.5.2 Offset-rectangular reducing-with splitters
21、3. Elbow:3.1 Elbow-round3.2.1 Elbow-flat oval-long axis3.2.2 Elbow-flat oval-short axis3.3.1 Elbow-rectangular-without splitters3.3.2 Elbow-rectangular-with splitters3.4.1 Elbow-rectangular reducing-withoutsplitters3.4.2 Elbow-rectangular reducing-with splitters3.5.1 Elbow-rectangular transition-wit
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF100519912002STANDARDPRACTICEFORHVACDUCTSHAPESIDENTIFICATIONANDDESCRIPTIONOFDESIGNCONFIGURATION 采暖

链接地址:http://www.mydoc123.com/p-533959.html