《ASTM E2886 E2886M-2014 Standard Test Method for Evaluating the Ability of Exterior Vents to Resist the Entry of Embers and Direct Flame Impingement《用于评估外部通风口抗余烬和直接火焰冲击进入的能力的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2886 E2886M-2014 Standard Test Method for Evaluating the Ability of Exterior Vents to Resist the Entry of Embers and Direct Flame Impingement《用于评估外部通风口抗余烬和直接火焰冲击进入的能力的标准试验方法》.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2886/E2886M 14Standard Test Method forEvaluating the Ability of Exterior Vents to Resist the Entryof Embers and Direct Flame Impingement1This standard is issued under the fixed designation E2886/E2886M; the number immediately following the designation indicates the yearof original adop
2、tion or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.A superscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This fire-test-response standard prescribes two indi-vidual methods to e
3、valuate the ability of a gable end, crawlspace (foundation) and other vents that mount on a verticalwall or in the under-eave area to resist the entry through thevent opening of embers and flame. The ability of such vents tocompletely exclude entry of flames or embers is not evaluated.Roof ridge and
4、 off-ridge (field) vents are excluded from thisstandard. Acceptance criteria are not provided in this standard.NOTE 1Test Method E2912 records information relevant to evaluatecompletely excluding the entry of flames through the venting device.1.2 Ember entry and flame penetration are evaluated sepa-
5、rately using different test procedures. A commentary andsummary of the development of the ember test apparatus aregiven in Appendix X1.1.3 These laboratory tests are used to evaluate the responseof vents when subjected to ember and flame exposures undercontrolled conditions.1.4 UnitsThe values state
6、d in either SI units or inch-pound units are to be regarded separately as standard. Thevalues stated in each system are not necessarily exact equiva-lents; therefore, each system shall be used independently of theother. Combining values from the two systems has the potentialto result in non-conforma
7、nce with the standard.1.5 Unless otherwise specified, the tolerance for dimensionsin figures and text in this document shall be 65%.1.6 This test method does not address interior fire spread.1.7 The standard is used to measure and describe theresponse of materials, products or assemblies to heat and
8、 flameunder controlled conditions, but does not by itself incorporateall factors required for fire hazard or fire risk assessments ofthe materials, products or assemblies and other claddingmaterials under actual fire conditions.1.8 This standard does not purport to address all of thesafety concerns,
9、 if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.9 Fire testing is inherently hazardous. Adequate safe-guards for personnel and proper
10、ty shall be employed inconducting these tests.2. Referenced Documents2.1 ASTM Standards:2D1929 Test Method for Determining Ignition Temperatureof PlasticsE108 Test Methods for Fire Tests of Roof CoveringsE176 Terminology of Fire StandardsE2257 Test Method for Room Fire Test of Wall and CeilingMateri
11、als and AssembliesE2707 Test Method for Determining Fire Penetration ofExterior Wall Assemblies Using a Direct Flame Impinge-ment ExposureE2912 Test Method for Fire Test of Non-Mechanical FireDampers Used in Vented Construction2.2 Other Documents:3SFM 12-7A-1, Exterior Wall Siding and Sheathing, Cal
12、ifor-nia Office of the State Fire Marshal, Sacramento, CASFM 12-7A-3, Under Eave, California Office of the StateFire Marshal, Sacramento, CA3. Terminology3.1 DefinitionsFor definitions of terms used in this testmethod refer to Terminology E176, Test Method E108, andTest Method E2912.3.2 Definitions
13、of Terms Specific to This Standard:3.2.1 ember, nsmall burning or glowing pieces of vegeta-tion or other cellulosic-based material.3.2.2 flaming combustion, nignition of combustible mate-rial that results in flaming combustion.1This test method is under the jurisdiction of ASTM Committee E05 on Fire
14、Standards and is the direct responsibility of Subcommittee E05.14 on External FireExposures.Current edition approved May 1, 2014. Published June 2014. DOI: 10.1520/E2886_E2886M-14.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org
15、. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from: http:/osfm.fire.ca.gov/codedevelopment/wildfireprotectionbuildingconstruction.phpCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken
16、, PA 19428-2959. United States13.2.3 smoldering combustion, nignition of combustiblematerial where a transition to flaming combustion does notoccur but a charred area indicating locations where emberslanded can be observed.3.2.4 sustained flaming, nexistence of flame on or overthe surface of the ven
17、t for continuous periods of at least 4 s.3.2.5 unexposed side, nthe face of the vent not directlyexposed to the fire in the Flame Intrusion Test.3.2.6 vent, na device or assembly placed in an exterioropening of a building (located in an eave, gable, wall, orfoundation) that allows for aeration (free
18、 exchange of air).4. Summary of Test Method4.1 This test method contains two procedures to assess theability of the vent to limit the entry of embers and flamepenetration.4.2 Ember Intrusion TestThis test method provides for adirect ember exposure to vents. The apparatus allows forembers to fall ver
19、tically and impinge on the vent mountedhorizontally on ledges within the test chamber. An inductionfan located at the bottom of the apparatus pulls the air streamthrough the vent, allowing any embers that pass through thevent to impinge on a combustible target material.4.2.1 Observations are made fo
20、r the occurrence of flamingcombustion of the combustible target material during the timethat embers are being generated and passing through the vent.4.2.2 This test method utilizes a vertical air flow apparatusfor the ember test.4.3 Flame Intrusion TestThis test method provides for theevaluation of
21、direct flame impingement on a vent mounted ina test assembly described in Test Method E2912.4.3.1 The flame source is directed into the test assembly anddirectly impinges the vent that is mounted in either a vertical orhorizontal position as described in Test Method E2912.4.3.2 This test method empl
22、oys a gas burner described inTest Method E2912 to produce flames that contact the vent.4.3.3 The fuel flow rate from the burner shall produce a heatrelease rate of 300 6 10 kW as described in Test MethodE2912.4.3.4 This test method includes an Integrity Test as de-scribed in Test Method E2912 to asc
23、ertain the presence ofsustained flaming. The Integrity Test includes the following:NOTE 2Integrity is defined in Test Method E2912.4.3.4.1 Visual observations are made for the presence andduration of any flame penetration through the vent.4.3.4.2 An Ignition Test Procedure as described in TestMethod
24、 E2912 is used to ascertain flaming combustion.4.3.5 This test method includes an optional Insulation Testas described in Test Method E2912. The optional InsulationTest includes surface thermocouples to measure the tempera-ture on the unexposed side of the vent.5. Significance and Use5.1 This test m
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME2886E2886M2014STANDARDTESTMETHODFOREVALUATINGTHEABILITYOFEXTERIORVENTSTORESISTTHEENTRYOFEMBERSANDDIRECTFLAMEIMPINGEMENT

链接地址:http://www.mydoc123.com/p-532056.html