《ASTM E1564-2000(2006) Standard Guide for Design and Maintenance of Low-Temperature Storage Facilities for Maintaining Cryopreserved Biological Materials《用于保存低温防腐生物材料的低温冷藏设备的设计与维护标准.pdf》由会员分享,可在线阅读,更多相关《ASTM E1564-2000(2006) Standard Guide for Design and Maintenance of Low-Temperature Storage Facilities for Maintaining Cryopreserved Biological Materials《用于保存低温防腐生物材料的低温冷藏设备的设计与维护标准.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 1564 00 (Reapproved 2006)Standard Guide forDesign and Maintenance of Low-Temperature StorageFacilities for Maintaining Cryopreserved BiologicalMaterials1This standard is issued under the fixed designation E 1564; the number immediately following the designation indicates the year ofor
2、iginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.INTRODUCTIONStorage facilities for maintaining cryopreserved biological
3、materials are generally comprised of twotypes of low-temperature systems: (1) freezers that are cooled by mechanical refrigeration and (2)freezers that are cooled passively with liquid nitrogen. Either system can be used for the storage offrozen biological materials as long as it meets the criteria
4、specific to the material being stored forensuring stability. Each system has its own unique handling requirements.1. Scope1.1 This guide covers recommended procedures for devel-oping and maintaining low-temperature storage facilities forfreezers with mechanical refrigeration.1.2 This guide covers re
5、commended procedures for devel-oping and maintaining low-temperature storage facilities forfreezers cooled with liquid nitrogen.1.3 This guide does not cover practices for preservation byfreezing which are covered in Practice E 1342.1.4 The values stated in SI units are to be regarded asstandard.1.5
6、 This standard does not purport to address all of thesafety problems, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Docu
7、ments2.1 ASTM Standards:2E 1342 Practice for Preservation by Freezing, Freeze-Drying, and Low Temperature Maintenance of Bacteria,Fungi, Protista,Viruses, Genetic Elements, andAnimal andPlant TissuesE 1565 Guide for Inventory Control and Handling of Bio-logical Material Maintained at Low Temperature
8、sE 1566 Guide for Handling Hazardous Biological Materialsin Liquid Nitrogen3. Terminology3.1 Definitions:3.1.1 cryogenic temperaturestemperatures below or equalto 100C.3.1.2 mechanical refrigerationa refrigeration system inwhich cooling is provided by mechanical means such as acompressor.3.1.3 passi
9、ve refrigerationa refrigeration system in whichcooling is provided by a refrigerant such as liquid nitrogen.4. Significance and Use4.1 The proper design of low-temperature storage facilitiesensures that sensitive biological materials are maintained underconditions providing maximum storage stability
10、.4.2 Properly designed and operated low-temperature storagefacilities ensure that the handling of sensitive biologicalmaterials at low temperatures does not compromise stability(see Guide E 1565).4.3 Properly designed low-temperature storage facilitiesensure that adequate safeguards are provided to
11、prevent unto-ward events from compromising the stability of sensitivebiological materials.5. Procedure5.1 Low-Temperature Mechanical Freezers:5.1.1 Ensure that adequate dedicated electrical power isavailable to support the number of mechanical freezers re-quired in the facility.1This guide is under
12、the jurisdiction ofASTM Committee E48 on Biotechnologyand is the direct responsibility of Subcommittee E48.02 on Characterization andIdentification of Biological Systems.Current edition approved Nov. 1, 2006. Published January 2007. Originallyapproved in 1993. Last previous edition approved in 2000
13、as E 1564 - 00.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor
14、 Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.5.1.2 Provide for emergency electrical power to maintainthe freezers when commercial power disruptions occur.5.1.3 Place the freezers in a temperature- and humidity-controlled area with adequate ventilation.5.1.4 Obtain a source of
15、 service support for the refrigerationsystems that is reliable and can respond to mechanical prob-lems rapidly. An alternative source should also be available.5.1.5 When selecting mechanical freezers, be sure that thelowest attainable temperature of the unit is cold enough toensure the stability of
16、the biological material to be stored inthem.5.1.6 The temperature of mechanical freezers shall be moni-tored daily to ensure that consistently low temperatures aremaintained. Most units have temperature-sensing devices builtin that allow both control and monitoring of the freezertemperature. These i
17、nternal units can malfunction and foolalarm systems. A temperature detecting probe should thereforebe inserted into each mechanical freezer, and the temperatureshould be read manually, or recorded automatically, on aremote sensing device.5.1.7 The temperature monitoring device shall be calibratedann
18、ually against a standard traceable to the National Institutefor Standards and Technology (NIST).35.2 Liquid Nitrogen Freezers:5.2.1 Liquid nitrogen freezers are passive cooling systemsthat use liquid nitrogen as the refrigerant. A reliable source ofliquid nitrogen shall be available to maintain liqu
19、id nitrogenfreezers.5.2.2 Liquid nitrogen freezers provide the greatest assur-ance of long-term stability because of the low temperatures thatcan be attained (150 to 196C).5.2.3 Choose a liquid nitrogen freezer that is compatiblewith inventory needs. Small units with large openings for easyaccess ar
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME156420002006STANDARDGUIDEFORDESIGNANDMAINTENANCEOFLOWTEMPERATURESTORAGEFACILITIESFORMAINTAININGCRYOPRESERVEDBIOLOGICALMATERIALS

链接地址:http://www.mydoc123.com/p-528955.html