ASTM D7607-2011 7500 Standard Test Method for Analysis of Oxygen in Gaseous Fuels (Electrochemical Sensor Method)《分析气态燃料中氧的标准试验方法(电化学传感器法)》.pdf
《ASTM D7607-2011 7500 Standard Test Method for Analysis of Oxygen in Gaseous Fuels (Electrochemical Sensor Method)《分析气态燃料中氧的标准试验方法(电化学传感器法)》.pdf》由会员分享,可在线阅读,更多相关《ASTM D7607-2011 7500 Standard Test Method for Analysis of Oxygen in Gaseous Fuels (Electrochemical Sensor Method)《分析气态燃料中氧的标准试验方法(电化学传感器法)》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D7607 11Standard Test Method forAnalysis of Oxygen in Gaseous Fuels (ElectrochemicalSensor Method)1This standard is issued under the fixed designation D7607; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of
2、last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method is for the determination of oxygen (O2)in gaseous fuels and fuel type gases. It is applicable to them
3、easurement of oxygen in natural gas and other gaseous fuels.This method can be used to measure oxygen in helium,hydrogen, nitrogen, argon, carbon dioxide, mixed gases, pro-cess gases, and ambient air. The applicable range is 0.1 ppm(v)to 25% by volume.1.2 The values stated in either SI units or inch
4、-pound unitsare to be regarded separately as standard. The values stated ineach system may not be exact equivalents; therefore, eachsystem shall be used independently of the other. Combiningvalues from the two systems may result in non-conformancewith the standard.1.3 This standard does not purport
5、to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D4150 T
6、erminology Relating to Gaseous FuelsD5503 Practice for Natural Gas Sample-Handling and Con-ditioning Systems for Pipeline Instrumentation3. Terminology3.1 For general terminology see Terminology D41503.2 Definitions:3.2.1 electrochemical sensorAchemical sensor that quan-titatively measures an analyt
7、e by the electrical output producedby the sensor.3.2.2 span calibrationThe adjustment of the transmitterelectronics to the sensors signal output for a given oxygenstandard.3.2.3 zero calibrationThe adjustment of the transmitterelectronics to the sensors signal output for a sample gascontaining less
8、than 0.1ppm(v) oxygen.4. Summary of Test Method4.1 Measurement of oxygen is accomplished by comparingthe electrical signal produced by an unknown sample with thatof a known standard using an oxygen specific electrochemicalsensor. A gaseous sample at constant flow and temperature ispassed over the el
9、ectrochemical cell. Oxygen diffuses into thesensor and reacts chemically at the sensing electrode toproduce an electrical current output proportional to the oxygenconcentration in the gas phase. Experience has shown that thetypes of sensors supplied with equipment used in this standardtypically have
10、 a linear response over the ranges of applicationwhich remains stable during the sensors useful life. Theanalyzer consists of a sensor, a sample flow system, and theelectronics to accurately determine the sensor signal.5. Significance and Use5.1 This test method is primarily used to monitor theconce
11、ntration of oxygen in gases to verify gas quality foroperational needs and contractual obligations. Oxygen contentis a major factor influencing internal corrosion, fuel quality, gasquality, and user and operator safety.6. Interferences6.1 Interfering gases such as oxides of sulfur, oxides ofnitrogen
12、, and hydrogen sulfide can produce false readings andreduce the expected life of the sensor. Scrubbers are used toremove these compounds. Special sensors suitable for gascontaining high fractions of carbon dioxide are available frommanufacturers.7. Apparatus7.1 SensorThe sealed sensor is contained i
13、n a housingconstructed of stainless steel or other non-permeable material.The sensor contains a cathode and an anode in an electrolytesolution.Afluorocarbon membrane allows the oxygen from thesample to diffuse into the sensor. Oxygen in the sample isreduced at the cathode and is simultaneously oxidi
14、zed at theanode. The electrons released at the surface of the anode flowto the cathode surface when an external electrical path is1This test method is under the jurisdiction ofASTM Committee D03 on GaseousFuels and is the direct responsibility of Subcommittee D03.12 on On-Line/At-LineAnalysis of Gas
15、eous Fuels.Current edition approved June 1, 2011. Published July 2011. DOI: 10.1520/D7607-11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document
16、Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.provided. The current is proportional to the amount of oxygenreaching the cathode and is used to measure the oxygenconcentration in the gas phase. The el
17、ectrochemical reactionsfor a lead anode cell are as follows:O21 2H2O 1 4e24OH(cathode half reaction)2Pb 1 4OH22PbO 1 2H2O 1 4e2(anode half reaction)2Pb 1 O22PbO (overall cell reaction)Any electrochemical cell with different materials can be employed if the cell cangive the same performance for selec
18、tive oxygen detection with similar sensitiv-ity.7.2 ElectronicsVarious electronic circuits are used toamplify and filter the sensor signal. The signal output may becorrected for the gas sample temperature.7.3 OutputAutomatic digital or range selectable analogdisplay of parts per million or percent o
19、xygen reading byvolume.7.4 Sampling SystemSample gas must be introduced tothe sensor of the analyzer. A flow control metering valve ispositioned upstream of the analyzer to provide a gas sampleflow rate of 0.5 to 2 L/min 1 to 5 SCFM. If necessary, apressure regulator with a metallic diaphragm can be
20、 usedupstream of the flow control valve to provide 35 to 200 kPa 5to 30 psig inlet pressure. A leak-free sample pump may beused for low pressure sampling. Stainless steel tubing andconnections should be used to minimize any air intrusion intothe sampling system. Gas scrubbers may be necessary toremo
21、ve interfering gases such as oxides of sulfur, oxides ofnitrogen, and hydrogen sulfide. A suitable coalescing or par-ticulate filter can be used to remove condensation, moisture,and/or particulates to prevent erroneous analysis readings anddamage to the sensor. A meter, such as a rotameter, is used
22、tomonitor the sample gas flow through the analyzer.8. Hazards8.1 Use safe and proper venting if using this method for theanalysis of hazardous or flammable gases. Failure to followmanufacturers instructions for the instrumentation used in thistest method may result in a hazardous condition.8.2 Do no
23、t open the sensor. The sensor contains a corrosiveliquid electrolyte that could be harmful if touched or ingested.Refer to the Material Safety Data Sheet provided by the sensormanufacturer.9. Preparation of Apparatus and Calibration9.1 Zero alibrationIn theory the oxygen sensor producesno signal whe
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD760720117500STANDARDTESTMETHODFORANALYSISOFOXYGENINGASEOUSFUELSELECTROCHEMICALSENSORMETHOD 分析 气态

链接地址:http://www.mydoc123.com/p-525944.html