《ASTM D6306-1998(2003) Standard Guide for Placement and Use of Diffusion Controlled Passive Monitors for Gaseous Pollutants in Indoor Air《室内空气中气态污染物用扩散控制无源检测器安置和使用的标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM D6306-1998(2003) Standard Guide for Placement and Use of Diffusion Controlled Passive Monitors for Gaseous Pollutants in Indoor Air《室内空气中气态污染物用扩散控制无源检测器安置和使用的标准指南》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 6306 98 (Reapproved 2003)Standard Guide forPlacement and Use of Diffusion Controlled Passive Monitorsfor Gaseous Pollutants in Indoor Air1This standard is issued under the fixed designation D 6306; the number immediately following the designation indicates the year oforiginal adoption
2、 or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide covers the placement and use of diffusioncontrolled monitors in
3、the indoor atmosphere.1.2 Diffusion controlled passive monitors within this guideinclude both area and personal monitors for use in residences,public buildings, offices, and other non-industrial workplacesand dwelling environments. A passive monitor is any airmonitor that does not utilize electrical
4、 or mechanical power inorder to supply air to the sorbent media or chemical reactantwithin the monitor and sample according to Ficks first law ofdiffusion.1.3 The purpose of this guide is to ensure uniformity ofsampling within a variety of indoor environments and tofacilitate comparison of results.1
5、.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Do
6、cuments2.1 ASTM Standards:2D 1356 Terminology Relating to Sampling and Analysis ofAtmospheresD 1357 Practice for Planning the Sampling of the AmbientAtmosphereD 4597 Practice for Sampling Workplace Atmospheres toCollect Gases or Vapors with Solid Sorbent DiffusiveSamplersD 3614 Guide for Laboratorie
7、s Engaged in Sampling andAnalysis of Atmospheres and Emissions3. Terminology3.1 DefinitionsFor definitions of terms used in this guiderefer to Terminology D 1356.3.2 Definitions of Terms Specific to This Standard:3.2.1 passive monitora diffusion controlled air monitorthat does not utilize electrical
8、 or mechanical power in order tosupply air to the sorbent media or chemical reactant within themonitor. These monitors may be worn by an individual(personal passive monitor) or used as sampling devices withinspecific locations (area passive monitor).4. Summary of Guide4.1 Contaminants in air are sam
9、pled by collection with asorbent or chemically reactive medium in order to undergosubsequent analysis for determination of concentration. Con-taminants in air are transported to the sorption medium orreacting chemical through vapor or gas diffusion. During thesampling process, the compounds, in a mo
10、lecular state, diffusefrom the environment adjacent to the sampler through a firstregion of defined geometric structure and into a secondadsorbing region containing the sorbent.4.2 Guidance is provided for the placement, handling, anduse of passive air monitors within an indoor environment.5. Signif
11、icance and Use5.1 The objective of this guide is to provide guidance for theplacement and use of passive monitors that when uniformlyapplied enables the user to eliminate many interferences in thesampling of indoor air. Since the analysis of the indoorenvironment by passive air monitors is influence
12、d by manyfactors other than the method of sampling, efforts are made tominimize interfering factors and maintain the air at conditionstypical of the measurement location within the vicinity of thepassive air monitor. However, when performing diagnostic orspecial measurements, non-typical indoor air
13、environmentconditions may be desirable or required. Thus, the objectives ofa sampling study may determine the conditions needed forsampling.5.2 Passive sampling provides for time integrated measure-ments. Passive monitors are usually placed in an indoorenvironment over a time period to obtain a cumu
14、lative sample;1This method is under the jurisdiction of ASTM Committee D22 on Samplingand Analysis of Atmospheres and is the direct responsibility of SubcommitteeD22.05 on Indoor Air.Current edition approved October 1, 2003. Published November 2003. Originallyapproved in 1998. Last previous edition
15、approved in 1998 as D 6306 - 98.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International
16、, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.hence, interfering factors should be anticipated and eliminatedwhere possible. Passive monitors often lack the sensitivity tomeasure short-term peak concentrations.5.3 With suitable instruction regarding placement
17、of passivemonitors, placement and retrieval of the monitors can beperformed by unskilled personnel (for example, occupants).6. General Principles6.1 The choice of a passive monitor, characteristics of thesampling site, number of sampling points, number of monitors,and number of sampling periods depe
18、nds on the objectives ofthe monitoring program.6.2 Passive monitors rely on air currents within an indoorenvironment for circulation of a representative sample atmo-sphere to the vicinity of the monitor. Therefore, it is essentialthat air circulation in the vicinity of the sampler be sufficient toke
19、ep the boundary layer thin enough so that the analyte candiffuse across it, preventing a localized concentration depletionby the monitor. The adequacy of the sampling is directlyinfluenced by the location and subsequent exposure of themonitor to a representative indoor atmosphere.6.3 The objective o
20、f the study may affect the type ofmonitor selected and the location of placement. In generalterms, Practice D 1357 will acquaint the user with establishedoverall study considerations.7. Sampling with Passive Monitors7.1 Inspect the monitor and package carefully. The monitoror its protective packagin
21、g may have been damaged duringshipment. The user should not directly contact the monitor withbare skin and, in no case, permit anything to contact thesampling face.7.2 Calibration of the Passive MonitorInformation relat-ing to calibration may be found in Practice D 4597. Thesedocuments also provide
22、information relating to the determina-tion of the required minimum sampling time.7.3 The sampling period begins when lid, cover, or protec-tive container of the monitor is removed to permit sampling bythe monitor. The starting time of the sampling period should betranscribed to a log-book or appropr
23、iate form and on themonitor label. The writing instrument, for example, markers,should not provide the potential of contamination to themonitor. A means of resealing or replacing the monitor lid orcover should be ensured.7.4 The monitor should have a permanently attached iden-tification code or seri
24、al number that should be transcribed to alog-book or an appropriate form. The logbook should includeinformation describing the location of the monitor and perti-nent information regarding the building and deployment area,such as construction, type of heating system, insulation,occupancy number and p
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD630619982003STANDARDGUIDEFORPLACEMENTANDUSEOFDIFFUSIONCONTROLLEDPASSIVEMONITORSFORGASEOUSPOLLUTANTSININDOORAIR

链接地址:http://www.mydoc123.com/p-522131.html