ASTM D3739-2006 Standard Practice for Calculation and Adjustment of the Langelier Saturation Index for Reverse Osmosis《反渗透用估算和校正Langclier饱和指数的标准实施规范》.pdf
《ASTM D3739-2006 Standard Practice for Calculation and Adjustment of the Langelier Saturation Index for Reverse Osmosis《反渗透用估算和校正Langclier饱和指数的标准实施规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM D3739-2006 Standard Practice for Calculation and Adjustment of the Langelier Saturation Index for Reverse Osmosis《反渗透用估算和校正Langclier饱和指数的标准实施规范》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 3739 06Standard Practice forCalculation and Adjustment of the Langelier SaturationIndex for Reverse Osmosis1This standard is issued under the fixed designation D 3739; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision,
2、the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the calculation and adjustment ofthe Langelier saturation index for the concentrate
3、stream of areverse osmosis device. This index is used to determine theneed for calcium carbonate scale control in the operation anddesign of reverse osmosis installations. This practice is appli-cable for concentrate streams containing xx 10 to 10 000 mg/Lof total dissolved solids. For concentrate c
4、ontaining over10 000 mg/L see Practice D 4582.1.2 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regul
5、atory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D511 Test Methods for Calcium and Magnesium In WaterD 1067 Test Methods for Acidity or Alkalinity of WaterD 1129 Terminology Relating to WaterD 1293 Test Methods for pH of WaterD 1888 Methods of Test for Particulate and Dissol
6、vedMatter in Water3D 4194 Test Methods for Operating Characteristics of Re-verse Osmosis and Nanofiltration DevicesD 4195 Guide for Water Analysis for Reverse OsmosisApplicationD 4582 Practice for Calculation and Adjustment of the Stiffand Davis Stability Index for Reverse OsmosisD 6161 Terminology
7、Used for Microfiltration, Ultrafiltra-tion, Nanofiltration and Reverse Osmosis Membrane Pro-cesses3. Terminology3.1 For definitions of terms used in this practice, refer toTerminology D 1129 and Terminology D 6161.3.2 Definitions of Terms Specific to This Standard:3.2.1 For descriptions of terms rel
8、ating to reverse osmosis,refer to Test Methods D 4194.3.2.2 Langelier Saturation Indexan index calculated fromtotal dissolved solids, calcium concentration, total alkalinity,pH, and solution temperature that shows the tendency of awater solution to precipitate or dissolve calcium carbonate.4. Summar
9、y of Practice4.1 This practice consists of calculating the Langelier Satu-ration Index for a reverse osmosis concentrate stream from thetotal dissolved solids, calcium ion content, total alkalinity, pH,and temperature of the feed solution, and the recovery of thereverse osmosis system.4.2 This pract
10、ice also presents techniques to lower theLangelier Saturation Index by decreasing the recovery, bydecreasing the calcium content of the feedwater, or by chang-ing the ratio of total alkalinity to free carbon dioxide in thefeedwater.5. Significance and Use5.1 In the design and operation of reverse os
11、mosis installa-tions, it is important to predict the calcium carbonate scalingproperties of the concentrate stream. Because of the increase intotal dissolved solids in the concentrate stream and the differ-ence in passages for calcium ion, bicarbonate ion, and freeCO2, the calcium carbonate scaling
12、properties of the concen-trate stream will generally be quite different from those of thefeed solution. This practice permits the calculation of the1This practice is under the jurisdiction of ASTM Committee D19 on Water andis the direct responsibility of Subcommittee D19.08 on Membranes and IonExcha
13、nge Materials.Current edition approved Dec. 15, 2006. Published January 2007. Originallyapproved in 1978. Last previous edition approved in 2005 as D 3739 05.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of A
14、STMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdrawn.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.Langelier Saturation Index for the concentrate stream from thefeed water anal
15、yses and the reverse osmosis operating param-eters.5.2 A positive Langelier Saturation Index indicates thetendency to form a calcium carbonate scale, which can bedamaging to reverse osmosis performance. This practice givesvarious procedures for the adjustment of the Langelier satura-tion index.5.3 T
16、he tendency to form CaCo3scale can be suppressed bythe addition of antiscalents or crystal modifiers. Suppliers ofantisealents and crystal modifiers can provide information onthe scale inhibition peformance of these types of chemical.Their use may be appropriate for reducing scale formation inRO sys
17、tems. The RO system supplier should be consulted priorto the use of antisealents and crystal modifiers to ensure theywill not have a negative impact on the RO system.6. Procedure6.1 Determine the calcium concentration in the feed solu-tion in accordance with Test Methods D511and express asCaCO3as de
18、monstrated in 6.6.6.2 Determine the total dissolved solids of the feed solutionusing Methods of Test D 1888.6.3 Determine the total alkalinity of the feed solution usingTest Methods D 1067, and express as CaCO3.6.4 Measure the pH of the feed solution using Test MethodsD 1293.6.5 Measure the temperat
19、ure of the feed solution.6.6 Convert feed water alkalinity and calcium as mg/LCaCO3:Caf5 Ca12# 3100gCaCo3mol31000mgg31eqCaCO31eqCa12(1)Alkf5 HCO3# 3100gCaCO3mol31000mgg31eqCaCO32eqHCO3(2)where:Cac= calcium concentration in concentrate as CaCO3,mg/L,Caf= calcium concentration in feed as CaCO3, mg/L,A
20、lkc= alkalinity in concentrate as CaCO3, mg/L, andAlkf= alkalinity in feed as CaCO3, mg/L.6.7 Measure the concentration of all major ions using themethods cited in Guide D 4195. At a minimum, measure theconcentration of Mg+,Na+,K+,SO4=, and Cl.7. Calculation7.1 Calculate the calcium concentration in
21、 the concentratestream from the calcium concentration in the feed solution, therecovery of the reverse osmosis system, and the calcium ionpassage as follows:Cac5 Caf31 2 YSPCa!1 2 Y(3)where:Cac= calcium concentration in concentrate, as CaCO3,mg/L,Caf= calcium concentration in feed, as CaCO3, mg/L,Y
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD37392006STANDARDPRACTICEFORCALCULATIONANDADJUSTMENTOFTHELANGELIERSATURATIONINDEXFORREVERSEOSMOSIS

链接地址:http://www.mydoc123.com/p-515376.html