ASTM C700-2011 Standard Specification for Vitrified Clay Pipe Extra Strength Standard Strength and Perforated《超强度及标准强度的多孔陶土管标准规格》.pdf
《ASTM C700-2011 Standard Specification for Vitrified Clay Pipe Extra Strength Standard Strength and Perforated《超强度及标准强度的多孔陶土管标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM C700-2011 Standard Specification for Vitrified Clay Pipe Extra Strength Standard Strength and Perforated《超强度及标准强度的多孔陶土管标准规格》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C700 11Standard Specification forVitrified Clay Pipe, Extra Strength, Standard Strength, andPerforated1This standard is issued under the fixed designation C700; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year
2、of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification establishes the
3、 criteria for acceptance,prior to installation, of extra strength and standard strengthvitrified clay pipe and fittings to be used for the conveyance ofsewage, industrial wastes, and storm water; and extra strengthperforated and standard strength perforated vitrified clay pipeto be used for underdra
4、inage, filter fields, leaching fields, andsimilar subdrainage installations.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.NOTE 1Att
5、ention is called to Specification C425, Test Method C828,Test Method C1091, Test Methods C301, and Terminology C896.1.3 The following precautionary caveat pertains only to theTest Method portion, 5.2-5.2.3.2 of this standard: This standarddoes not purport to address all of the safety concerns, if an
6、y,associated with its use. It is the responsibility of the user of thisstandard to establish appropriate safety and health practicesand determine the applicability of regulatory limitations priorto use.2. Referenced Documents2.1 ASTM Standards:2C301 Test Methods for Vitrified Clay PipeC425 Specifica
7、tion for Compression Joints for VitrifiedClay Pipe and FittingsC828 Test Method for Low-Pressure Air Test of VitrifiedClay Pipe LinesC896 Terminology Relating to Clay ProductsC1091 Test Method for Hydrostatic Infiltration Testing ofVitrified Clay Pipe Lines3. Terminology3.1 DefinitionsClay, fire cla
8、y, shale, and surface clay areas defined in Terminology C896.4. Materials and Manufacture4.1 Vitrified clay pipe shall be manufactured from fire clay,shale, surface clay, or a combination of these materials that,when formed into pipe and fired to suitable temperatures,yields a product that conforms
9、to this specification.5. Physical Properties5.1 Bearing Strength:5.1.1 Pipe shall meet the bearing strength requirements ofTable 1.5.1.2 The number of specimens to be tested shall not exceed0.5 % of the number of pipe of each size furnished, except thatno less than two specimens shall be tested.5.1.
10、3 If any of the test specimens fail to meet the require-ments, the manufacturer will be allowed a retest on twoadditional specimens for each one that failed. The pipe will beacceptable if all the retest specimens meet the test requirement.5.1.4 If, subsequent to an initial pipe strength failure, the
11、accuracy of the testing equipment is questioned, at the requestof the manufacturer, the equipment shall be recalibrated and aretest made or a retest made upon equipment of knownaccuracy.5.2 Hydrostatic Pressure Test or Absorption Test:5.2.1 The manufacturer shall at his option, apply either ahydrost
12、atic pressure test or an absorption test to all of the testspecimens in each size and run of the pipe.5.2.2 Hydrostatic Pressure Test:5.2.2.1 When the pipe is subjected to an internal hydrostaticpressure of 10 psi (68.9 KPa) for the elapsed time shown in thefollowing table, there shall be no leaking
13、 on the exterior of thepipe. Moisture appearing on the surface of the pipe in the form1This specification is under the jurisdiction of ASTM Committee C04 onVitrified Clay Pipe and is the direct responsibility of Subcommittee C04.20 onMethods of Test and SpecificationsCurrent edition approved Jan. 1,
14、 2011. Published January 2011. Originallyapproved in 1971. Last previous edition approved in 2009 as C700 09. DOI:10.1520/C0700-11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume informa
15、tion, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.of beads adhering to the surface shall not be consideredleakage. However, moisture which starts to run on the pipes
16、hall be construed as leakage regardless of quantity.Hydrostatic Pressure Test TimeThickness of Barrelin. (mm)Test Time (min.)Up to and including 1 (25) 7Over 1 (25) including 112 (38) 9Over 112 (38) including 2 (51) 12Over 2 (51) including 212(64)15Over 212 (64) including 3 (76) 18Over 3 (76) 215.2.
17、2.2 If any of the test specimens fail to meet the Hydro-static Pressure Test requirements, a retest will be allowed andthe pipe accepted as provided in 5.1.3.5.2.3 Absorption Test:5.2.3.1 The absorption of vitrified clay pipe shall not exceed8%.5.2.3.2 If any of the test specimens fail to meet the a
18、bsorp-tion requirements, a retest will be allowed and the pipeaccepted as provided in 5.1.3.5.3 Acid Resistance:5.3.1 This test is used to determine the resistance of pipe tothe action of acids encountered in sanitary sewers. The testshall be performed only when specified.5.3.2 The pipe of each size
19、 and shipment shall be acceptableif the acid-soluble matter, from specimens representing suchpipe, does not exceed 0.25 %.5.3.3 If any of the tests specimens fail to meet the acidresistance requirements, a retest, representative of the originalmaterial lot, in that particular acid will be allowed an
20、d the pipeaccepted as provided in 5.1.3.TABLE 1 Minimum Strength (3-Edge Bearing)NominalSize, in.(mm)Extra StrengthVitrified Clay PipeStandard StrengthVitrified Clay PipePerforated Vitrified Clay PipeExtra Strength Standard Strengthlbf/linearftkN/linearmlbf/linearftkN/linearmlbf/linearftkN/linearmlb
21、f/linearftkN/linearm3 (76) 2000 29 . . . . . .4 (100) 2000 29 1200 18 1250 18 1000 156 (150) 2000 29 1200 18 1600 23 1000 158 (205) 2200 32 1400 20 1600 23 1000 1510 (255) 2400 35 1600 23 1600 23 1100 1612 (305) 2600 38 1800 26 1800 26 1200 1815 (380) 2900 42 2000 29 2200 32 1400 2018 (455) 3300 48
22、2200 32 2640 39 1700 2521 (535) 3850 56 2400 35 3100 45 2000 2924 (610) 4400 64 2600 38 3520 51 2400 3527 (685) 4700 69 . . . . . .30 (760) 5000 73 . . . . . .33 (840) 5500 80 . . . . . .36 (915) 6000 88 . . . . . .39 (990) 6600 96 . . . . . .42 (1065) 7000 102 . . . . . .48 (1220) 8000 117 . . . .
23、. .TABLE 2 Available Limits for Dimensional VariationNominal Size, in. (mm)ALaying Length Limit of MinusVariation, in./ft (mm/m)Difference in Length of TwoOpposite Sides Max, in. (mm)Limit of Minus Variations fromNominal Size in Average InsideDiameter, in. (mm)3 (76)14 (21)516 (8)316 (5)4 (100)14 (2
24、1)516 (8)316 (5)6 (150)14 (21)38 (10)14 (6)8 (205)14 (21)716 (11)516 (8)10 (255)14 (21)716 (11)38 (10)12 (305)14 (21)716 (11)716 (11)15 (380)14 (21)12 (13)916 (14)18 (455)14 (21)12 (13)1116 (17)21 (535)38 (31)916 (14)1316 (21)24 (610)38 (31)916 (14)1516 (24)27 (685)38 (31)58 (16) 1116 (27)30 (760)38
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC7002011STANDARDSPECIFICATIONFORVITRIFIEDCLAYPIPEEXTRASTRENGTHSTANDARDSTRENGTHANDPERFORATED 强度 标准

链接地址:http://www.mydoc123.com/p-508056.html