ASTM C1639-2010 Standard Specification for Fabrication of Cellular Glass Pipe and Tubing Insulation.pdf
《ASTM C1639-2010 Standard Specification for Fabrication of Cellular Glass Pipe and Tubing Insulation.pdf》由会员分享,可在线阅读,更多相关《ASTM C1639-2010 Standard Specification for Fabrication of Cellular Glass Pipe and Tubing Insulation.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1639 10Standard Specification forFabrication Of Cellular Glass Pipe And Tubing Insulation1This standard is issued under the fixed designation C1639; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last rev
2、ision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers fabrication techniques forcellular glass block into billets to fabricate pipe and tubinginsulation.
3、All materials shall be in accordance with Specifi-cation C552.1.2 The purpose of this specification is to optimize thethermal performance of installed cellular glass insulationsystems. This is best achieved by limiting the number of joints,in particular through joints.1.3 The values stated in inch-p
4、ound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is ther
5、esponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC450 Practice for Fabrication of Thermal
6、Insulating FittingCovers for NPS Piping, and Vessel LaggingC552 Specification for Cellular Glass Thermal InsulationC585 Practice for Inner and Outer Diameters of ThermalInsulation for Nominal Sizes of Pipe and TubingD312 Specification for Asphalt Used in Roofing2.2 ASTM Adjuncts:3ADJC0450A ASTM Reco
7、mmended Dimensional Standardsfor Fabrication of Thermal Insulation Fitting Covers3. Terminology3.1 Terminology C168 shall be considered as applying tothe terms in this specification.3.2 Definitions of Terms Specific to This Standard:3.3 billet / buna single piece of insulation made up froma number o
8、f smaller blocks held together with an adhesive.3.4 lagspieces of insulation typically curved or taperedused for insulating pipes, tanks and other cylindrical equip-ment.3.5 precision cut V-grooved pipe insulation, nrigid insu-lation pieces cut into 4-sided polygons, of two parallel surfacesand two
9、non-parallel surfaces of equal angles = 180 / N, suchthat when N number of these sections are assembled, they forman approximate circle and can be installed around a pipe.3.5.1 Discussionthe adjective precision refers to the factthat when these N sections are installed onto a pipe, they fitexactly w
10、ith no appreciable gaps between sections.4. Classification4.1 Specification C552 defines Type I and Type II materials.The same classifications shall be used in this standard.5. Workmanship, Finish, and Appearance5.1 The insulation shall have no visible defects that willadversely affect its performan
11、ce.6. Standard Sizes, Dimensions, and FabricationConfigurations of Cellular Glass Pipe and TubingInsulation6.1 Cellular glass pipe and tubing insulation shall befabricated in lengths as agreed to by the purchaser and thesupplier. Typical lengths are 2312-in. (597mm), 24 in. (610mm), or 36 in. (914 m
12、m).6.2 Cellular glass pipe and tubing insulation for NPS 4 (102mm) and smaller pipe shall be made to a minimum thickness of1-in. (25 mm). Pipe insulation for pipes larger than 4 in. NPS(102 mm) shall be made to a minimum 112-in. (38 mm)thickness. Sizes shall conform to Practice C585. A minimum 21Thi
13、s specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.40 onInsulation Systems.Current edition approved March 1, 2010. Published March 2010. Originallyapproved in 2007. Last previous version approved in 2007 as C16390
14、7. DOI:10.1520/C1639-10.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from ASTM International He
15、adquarters. Order Adjunct No.ADJC0450A.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.in. (51 mm) thickness should be used for pipe sizes larger than12 in. NPS (324 mm).6.3 Cellular glass pipe insulation must be provided in halfsect
16、ions for up to and including 12 in. NPS (324 mm). Halfsections shall consist of hollow cylindrical sections splitlengthwise in a plane that includes the cylindrical axis.6.4 Cellular glass pipe insulation for pipe sizes 14 in. (356mm) to 24 in. NPS (406 mm) must be fabricated in half-sections or in
17、quarter-sections. At 26 in. NPS (660 mm) andabove, segmented pipe insulation shall be furnished. Seg-mented pipe insulation (see Fig. 1) shall be fabricated in equalwidths such that no additional field cuts are required.6.5 For operating temperatures above ambient, precision cutV-grooved pipe insula
18、tion specifically cut to fit the requireddiameter or segmented fabrication is an acceptable alternative.6.6 For operating temperatures between 0F (-18C) andambient, precision cut V-grooved pipe insulation, as shown onFig. 2, is an acceptable alternative provided an acceptablevapor retarder is used.6
19、.7 For operating temperatures below 0 F (-18C),V-grooved material, as shown on Fig. 2 is not acceptable.7. Dimensional Tolerances7.1 Fabrication tolerances for the bore diameter and wallthickness shall be as specified in Practice C585.7.2 Tolerance for length of pipe and tubing insulation shallbe 61
20、4 in. (6 3.2 mm).7.3 The following dimensional tolerances apply only tocellular glass pipe and tubing insulation applied in halfsections:7.3.1 Fit and ClosureWhen fitted to the appropriate sizepipe by banding on 9 in. (230 mm) centers, the longitudinaljoints on both sides of the pipe insulation shal
21、l close to within116 in. (1.6 mm) along the entire length of the section.7.3.2 ConcentricityThe inner bore of the pipe insulationshall be concentric with the outer cylindrical surface. Deviationfrom concentricity shall not exceed18 in. (3.2 mm) or 5% ofthe wall thickness, whichever is greater, at al
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC16392010STANDARDSPECIFICATIONFORFABRICATIONOFCELLULARGLASSPIPEANDTUBINGINSULATIONPDF

链接地址:http://www.mydoc123.com/p-465382.html