1、Designation: C 1639 07Standard Specification forFabrication Of Cellular Glass Pipe And Tubing Insulation1This standard is issued under the fixed designation C 1639; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last r
2、evision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers fabrication techniques forcellular glass block into billets to fabricate pipe and tubinginsulatio
3、n. All materials shall be in accordance with Specifi-cation C 552.1.2 The purpose of this specification is to optimize thethermal performance of installed cellular glass insulationsystems. This is best achieved by limiting the number of joints,in particular through joints.1.3 The values stated in in
4、ch-pound units are to be regardedas the standard. The values given in the parentheses areprovided for information only.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-pri
5、ate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C 168 Terminology Relating to Thermal InsulationC 450 Practice for Fabrication of Thermal Insulating FittingCovers for NPS Piping, and Vessel LaggingC 55
6、2 Specification for Cellular Glass Thermal InsulationC 585 Practice for Inner and Outer Diameters of RigidThermal Insulation for Nominal Sizes of Pipe and Tubing(NPS System)D 312 Specification for Asphalt Used in Roofing2.2 ASTM Adjuncts:3ADJC0450A ASTM Recommended Dimensional Standardsfor Fabricati
7、on of Thermal Insulation Fitting Covers3. Terminology3.1 Terminology C 168 shall be considered as applying tothe terms in this specification.3.2 Definitions of Terms Specific to This Standard:3.3 billet / bun a single piece of insulation made up froma number of smaller blocks held together with an a
8、dhesive.3.4 lagspieces of insulation typically curved or taperedused for insulating pipes, tanks and other cylindrical equip-ment.3.5 precision cut V-grooved pipe insulation , nrigid insu-lation pieces cut into 4-sided polygons, of two parallel surfacesand two non-parallel surfaces of equal angles =
9、 180 / N, suchthat when N number of these sections are assembled, they forman approximate circle and can be installed around a pipe.3.5.1 Discussionthe adjective precision refers to the factthat when these N sections are installed onto a pipe, they fitexactly with no appreciable gaps between section
10、s.4. Classification4.1 Specification C 552 defines Type I and Type II materi-als. The same classifications shall be used in this standard.5. Workmanship, Finish, and Appearance5.1 The insulation shall have no visible defects that willadversely affect its performance.6. Standard Sizes, Dimensions, an
11、d FabricationConfigurations of Cellular Glass Pipe and TubingInsulation6.1 Cellular glass pipe and tubing insulation shall befabricated in lengths as agreed to by the purchaser and thesupplier. Typical lengths are 2312-in. (597mm), 24 in. (610mm), or 36 in. (914 mm).6.2 Cellular glass pipe and tubin
12、g insulation for NPS 4 (102mm) and smaller pipe shall be made to a minimum thickness of1-in. (25 mm). Pipe insulation for pipes larger than 4 in. NPS(102 mm) shall be made to a minimum 112-in. (38 mm)thickness. Sizes shall conform to Practice C 585.Aminimum 2in. (51 mm) thickness should be used for
13、pipe sizes larger than12 in. NPS (324 mm).6.3 Cellular glass pipe insulation must be provided in halfsections for up to and including 12 in. NPS (324 mm). Halfsections shall consist of hollow cylindrical sections splitlengthwise in a plane that includes the cylindrical axis.6.4 Cellular glass pipe i
14、nsulation for pipe sizes 14 in. (356mm) to 24 in. NPS (406 mm) must be fabricated in half-sections or in quarter-sections. At 26 in. NPS (660 mm) and1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.40 onInsu
15、lation Systems.Current edition approved April 1, 2007. Published May 2007.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe
16、ASTM website.3Available from ASTM International Headquarters. Order Adjunct No.ADJC0450A.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.above, segmented pipe insulation shall be furnished. Seg-mented pipe insulation (see Fig. 1) sha
17、ll be fabricated in equalwidths such that no additional field cuts are required.6.5 For operating temperatures above ambient, precision cutV-grooved pipe insulation specifically cut to fit the requireddiameter or segmented fabrication is an acceptable alternative.6.6 For operating temperatures betwe
18、en 0F (-18C) andambient, precision cut V-grooved pipe insulation, as shown onFig. 2, is an acceptable alternative provided an acceptablevapor retarder is used.6.7 For operating temperatures below 0 F (-18C),V-grooved material, as shown on Fig. 2 is not acceptable.7. Dimensional Tolerances7.1 Fabrica
19、tion tolerances for the bore diameter and wallthickness shall be as specified in Practice C 585.7.2 Tolerance for length of pipe and tubing insulation shallbe 614 in. (6 3.2 mm).7.3 The following dimensional tolerances apply only tocellular glass pipe and tubing insulation applied in halfsections:7.
20、3.1 Fit and Closure When fitted to the appropriate sizepipe by banding on 9 in. (230 mm) centers, the longitudinaljoints on both sides of the pipe insulation shall close to within116 in. (1.6 mm) along the entire length of the section.7.3.2 ConcentricityThe inner bore of the pipe insulationshall be
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC16392007STANDARDSPECIFICATIONFORFABRICATIONOFCELLULARGLASSPIPEANDTUBINGINSULATION 制作 海绵状 玻璃管 绝缘

链接地址:http://www.mydoc123.com/p-465381.html