ASTM C1629 C1629M-2006 Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels《防滥用无装饰室内石膏板产品和纤维增强水泥板的标准分类》.pdf
《ASTM C1629 C1629M-2006 Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels《防滥用无装饰室内石膏板产品和纤维增强水泥板的标准分类》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1629 C1629M-2006 Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels《防滥用无装饰室内石膏板产品和纤维增强水泥板的标准分类》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 1629/C 1629M 06Standard Classification forAbuse-Resistant Nondecorated Interior Gypsum PanelProducts and Fiber-Reinforced Cement Panels1This standard is issued under the fixed designation C 1629/C 1629M; the number immediately following the designation indicates theyear of original ad
2、option or, in the case of revision, the year of last revision. A number in parentheses indicates the year of lastreapproval. A superscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This standard establishes classifications of abuse resis-tance based
3、 on minimum abuse-resistance performance ofnondecorated interior gypsum panel products and fiber-reinforced cement panels (abuse resistant wall panels).1.2 The values stated in inch-pound and SI (metric) units areto be regarded separately as standard. Within the text, the SIunits are shown in bracke
4、ts. The values stated in each systemshall be used independent of the other. Values from the twosystems shall not be combined.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish app
5、ro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C11 Terminology Relating to Gypsum and Related Build-ing Materials and SystemsC 1154 Terminology for Non-Asbestos Fiber-ReinforcedCement ProductsD
6、4977 Test Method for Granule Adhesion to MineralSurfaced Roofing by AbrasionD 5420 Test Method for Impact Resistance of Flat, RigidPlastic Specimen by Means of a Striker Impacted by aFalling Weight (Gardner Impact)E 695 Test Method of Measuring Relative Resistance ofWall, Floor, and Roof Constructio
7、n to Impact Loading2.2 ISO Documents:ISO 6707-1 Building and Civil Engineering - Vocabulary -Part 1: General Terms3. Terminology3.1 Definitions of terms shall be in accordance with Termi-nologies C11and C 1154.3.2 Definitions of Terms Specific to This Standard:3.2.1 failure (hard body impact), ntest
8、 result constitutedeither by the penetration of the wall cavity by the impactinghead of the impacting arm or the denting of the panel resultingin an indentation of a depth that exceeds the thickness of thetest panel.3.2.1.1 DiscussionDepth of the indentation on the testpanel is measured from the fac
9、e side.3.2.2 failure (soft body impact), na test result constitutedeither by the breaking of the wall cavity by the soft bodyimpactor or the residual deflection of any area on the test panelthat exceeds the thickness of the test panel.3.2.2.1 DiscussionDeformation of the test panel in theform of res
10、idual deflection is measured from the face side.3.2.2.2 deformation, nchange of shape or dimension orboth. ISO 6707-13.2.2.3 surface damage, npulverization of the core of thetest panel at the point of impact, which is evidenced bycracking, creasing, or other visible damage short of failure asdefined
11、 in 3.2.2.3.2.3 residual deflection, npermanent deformation of abuilding element, component, or structure after removal ofapplied force.3.2.3.1 DiscussionAlso called permanent set or residualdeformation.4. Significance and Use4.1 Each abuse/impact property of abuse resistant wallpanels is divided in
12、to three classification levels. The threelevels of classification are: Level I, Level II, and Level III, withLevel I representing the lowest rating for any given property.The test methods specified are utilized to establish the abuse-resistance classification of an abuse resistant wall panel. Each1T
13、his classification is under the jurisdiction of ASTM Committee C11 onGypsum and Related Building Materials and Systems and is the direct responsibilityof Subcommittee C11.01 on Specifications and Test Methods for Gypsum Products.Current edition approved Nov. 1, 2006. Published November 2006. Origina
14、llyapproved in 2005. Last previous edition approved in 2005 as C 1629/C 1629M 05.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page
15、 onthe ASTM website.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.classification level requires a minimum overall specified per-formance.Any classified abuse resista
16、nt wall panel can be usedat a classification level which is rated lower than the highestlevel qualified.5. Basis of Classification5.1 Abuse resistant wall panels are classified into one ofthree levels of abuse resistance based on minimum perfor-mance when tested in accordance with test methods thate
17、valuate surface abrasion, indentation, soft body impact, andhard body impact as specified in 6.1 through 6.4.5.2 Minimum requirements for each level are as shown inTables 1-4.6. Test Methods6.1 Surface Abrasion TestThis test is conducted in accor-dance with Test Method D 4977 using a total load of 2
18、5.0 lb.The specimen is conditioned to constant weight at 70F and50 % relative humidity and subjected to 50 abrasion cycles.The abrasive motion on the specimen creates measurablesurface wear or indentation which is measured to determine thelevel of surface abrasion resistance.NOTE 1It is especially i
19、mportant to prepare the apparatus andcondition the brush as specified in Test Method D 4977.6.2 Indentation TestThis test, conducted in accordancewith Test Method D 5420 (Gardner Impact), utilizes procedureGC, with a58 in. hemispherical head and a 72 in.-lb. 12.6 Jimpact energy. The depth of the ind
20、entation is measured todetermine the level of indentation resistance.6.3 Soft Body Impact TestThis test, conducted in accor-dance with Method E 695, is performed with the use of thestandard leather bag filled with steel pellets to a weight of 60.0lb 27.2 kg and dropped through an angular distance un
21、til thespecimen is impacted.6.3.1 The specimen is mounted on nominal 2-by-4 woodstuds 16 in. 400 mm o.c. Point of impact is midway betweenstuds at the mid-height of the test panel.6.3.2 A single specimen is repeatedly impacted at a singlepoint of impact in one cavity with the drop height beingincrea
22、sed by 6 in. with each successive drop until structuralfailure as defined in 3.2.2 is achieved.6.3.2.1 Surface damage and deformation are recorded fol-lowing each impact, and the level of impact energy applied iscalculated. The residual deflection shall be measured from theface side of the panel.NOT
23、E 2Surface damage and deformation, which do not constitutestructural failure, may compound the results.6.3.3 Following structural failure in the initial cavity, theprocedure described in 6.3.2 is repeated on the next cavity,beginning with a drop height of 6 in. higher than the dropheight causing str
24、uctural failure in 6.3.2.6.3.3.1 If structural failure in the second cavity occurs withthe first drop, the test is terminated and the level of energyrequired to cause the single impact penetration or excessivedeformation is calculated to determine the soft body impactresistance.6.3.3.2 If structural
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC1629C1629M2006STANDARDCLASSIFICATIONFORABUSERESISTANTNONDECORATEDINTERIORGYPSUMPANELPRODUCTSANDFIBERREINFORCEDCEMENTPANELS

链接地址:http://www.mydoc123.com/p-465353.html