ASTM C1029-2009 Standard Specification for Spray-Applied Rigid Cellular Polyurethane Thermal Insulation.pdf
《ASTM C1029-2009 Standard Specification for Spray-Applied Rigid Cellular Polyurethane Thermal Insulation.pdf》由会员分享,可在线阅读,更多相关《ASTM C1029-2009 Standard Specification for Spray-Applied Rigid Cellular Polyurethane Thermal Insulation.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1029 09Standard Specification forSpray-Applied Rigid Cellular Polyurethane ThermalInsulation1This standard is issued under the fixed designation C1029; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last
2、revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers the types and ph
3、ysical proper-ties of spray applied rigid cellular polyurethane intended foruse as thermal insulation. The operating temperatures of thesurfaces to which the insulation is applied shall not be lowerthan 22F (30C) or greater than +225F (+107C). Forspecific applications, the actual temperature limits
4、shall be asagreed upon between the manufacturer and the purchaser.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.3 This standard d
5、oes not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM St
6、andards:2C165 Test Method for Measuring Compressive Propertiesof Thermal InsulationsC168 Terminology Relating to Thermal InsulationC177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC518 Test Method for Steady-State
7、 Thermal TransmissionProperties by Means of the Heat Flow Meter ApparatusC1303 Test Method for Predicting Long-Term ThermalResistance of Closed-Cell Foam InsulationC1363 Test Method for Thermal Performance of BuildingMaterials and Envelope Assemblies by Means of a HotBox ApparatusD883 Terminology Re
8、lating to PlasticsD1621 Test Method for Compressive Properties Of RigidCellular PlasticsD1622 Test Method for Apparent Density of Rigid CellularPlasticsD1623 Test Method for Tensile and Tensile Adhesion Prop-erties of Rigid Cellular PlasticsD2126 Test Method for Response of Rigid Cellular Plasticsto
9、 Thermal and Humid AgingD2842 Test Method for Water Absorption of Rigid CellularPlasticsD6226 Test Method for Open Cell Content of Rigid CellularPlasticsE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE96/E96M Test Methods for Water Vapor Transmission ofMaterials3. Terminolog
10、y3.1 DefinitionsFor definitions of terms used in this speci-fication, refer to Terminologies C168 and D883.4. Classification4.1 Spray-applied rigid-cellular polyurethane thermal insu-lation covered by this specification is classified into four typesas follows:4.1.1 Type ICompressive strength 15 psi
11、(104 kPa) mini-mum.4.1.2 Type IICompressive strength 25 psi (173 kPa)minimum.4.1.3 Type IIICompressive strength 40 psi (276 kPa)minimum.1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.22 onOrganic and Nonho
12、mogeneous Inorganic Thermal Insulations.Current edition approved Nov. 1, 2009. Published December 2009. Originallyapproved in 1985. Last previous edition approved in 2008 as C1029 08. DOI:10.1520/C1029-09.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer S
13、ervice at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.1.4 Type IVCompressive strength 60 psi
14、(414 kPa)minimum.5. Ordering Information5.1 Orders for materials purchased under this specificationshall include the following:5.1.1 ASTM designation, year of issue, and title.5.1.2 Type (see 4.1).5.1.3 R value or thickness required (see 10.1).5.1.4 Sampling, if different (see Section 8).5.1.5 If a
15、certificate of compliance is required (see 13.1).5.1.6 If packaging is other than specified (see 14.1).5.1.7 If marking is other than specified (see 14.4).6. Materials and Manufacture6.1 Spray-applied rigid-cellular polyurethane thermal insu-lation is produced by the catalyzed chemical reaction ofpo
16、lyisocyanates with polyhydroxyl compounds, with the addi-tion of other compounds such as stabilizers and blowingagents.6.2 The materials shall be capable of being mixed andapplied using commercial polyurethane spray equipment.NOTE 1The thermal insulation shall be formed directly on the surfaceto be
17、sprayed, unless agreed upon by the purchaser and the manufacturer.7. Physical Requirements7.1 Polyurethane thermal insulation shall have the limitingproperty values as shown in Table 1.7.2 Other physical properties shall be required, as agreedupon by the purchaser and the manufacturerNOTE 2Density i
18、s not a requirement of this specification, but if agreedupon by the purchaser and the manufacturer shall be determined inaccordance with Test Method D1622 for point-of-manufacture qualitycontrol.8. Sampling8.1 LotFor purposes of sampling, the lot shall consist ofall the polyurethane liquid component
19、s purchased at one time.8.2 Unit SampleThe unit sample shall consist of approxi-mately 50 lb (23 kg) of each of the two liquid components asrequired to prepare the foam test specimens specified inSection 9. Samples may be drawn from representative bulkstorage or from one or more shipping containers.
20、8.3 Sampling for qualification tests, if required, shall be inaccordance with statistically sound practice. Qualification testswill be conducted on the physical properties in Table 1.8.4 Sampling for inspection tests, if required, shall be forproperties agreed upon between the manufacturer and thepu
21、rchaser.9. Test Specimen Preparation9.1 Finished polyurethane foam insulation test panels shallbe made by spray application consistent with the manufactur-ers recommendations including: temperatures of the liquidcomponents, ambient temperature, temperature and type ofsubstrate, type and operation of
22、 spray equipment, and thicknessof foam per pass. Unless otherwise specified and reported, theambient and substrate temperature shall be 75 6 5F (24 63C). The relative humidity must not exceed 80%. The testpanels shall be of a sufficient quantity and size to satisfy testrequirements.NOTE 3Specific pa
23、nel sizes and thicknesses shall be based on therequirements of the individual tests.9.2 The test panels shall be allowed to cure for at least 72 hat 73 6 2F (23 6 1C) and 50 6 5% relative humidity priorto cutting or testing for physical properties.9.3 Core specimens, when required, shall be obtained
24、 byremoving both the external skin and the boundary skin found atthe substrate/foam interface.Atrim cut on each face to a depthof18 to14 in. (3 to 6 mm) is generally sufficient. Corespecimens may contain one or more internal skins at spray passboundaries.9.4 For Type III products the samples are spr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC10292009STANDARDSPECIFICATIONFORSPRAYAPPLIEDRIGIDCELLULARPOLYURETHANETHERMALINSULATIONPDF

链接地址:http://www.mydoc123.com/p-463100.html